ABB TMA250-2500T44pInN=100%In 1SDA054674R1 is a 250 A four-pole thermomagnetic trip unit with an adjustable 1250–2500 A instantaneous magnetic trip setting and fully rated neutral for compatible ABB SACE Tmax T4 moulded-case circuit breakers.
£2,952.87
The ABB TMA250-2500T44pInN=100%In, order code 1SDA054674R1, is a four-pole thermomagnetic trip unit designed for ABB SACE Tmax T4 moulded-case circuit breakers. As part of the ABB Tmax T4 protection system, it provides reliable thermal overload and magnetic short-circuit protection for low-voltage AC and DC electrical distribution applications.
The TMA release combines adjustable thermal overload protection with adjustable instantaneous magnetic protection in a robust electromechanical design. This enables protection settings to be matched to the requirements of the installation while providing dependable circuit protection without requiring an external auxiliary power supply.
With a rated current of 250 A and an adjustable instantaneous magnetic trip setting of 1250–2500 A, the TMA250-2500T44p is designed for four-pole ABB Tmax T4 circuit breakers. This version incorporates a fully rated neutral at 100% of the phase rated current, making it particularly suitable for four-wire distribution systems requiring full neutral protection.
Thermomagnetic releases such as the ABB TMA250-2500T44p protect electrical circuits using complementary thermal and magnetic operating principles. The thermal element responds to sustained overload currents to help prevent excessive heating of conductors and connected equipment, while the magnetic element provides rapid operation when high short-circuit currents occur.
The adjustable TMA design allows protection to be coordinated with the characteristics of the electrical installation. Combined with its four-pole configuration and fully rated neutral, the TMA250-2500T44p provides dependable protection for industrial and commercial four-wire distribution systems using compatible ABB Tmax T4 moulded-case circuit breakers.
| Series | SACE Tmax T4 |
|---|---|
| Order code | 1SDA054674R1 |
| Product group | 310511-T-Max T4 - T8 |
| Product type | Thermomagnetic trip unit / release |
| Trip unit type | TMA |
| Rated current | 250 A |
| Instantaneous magnetic trip setting (I3) | 1250–2500 A |
| Number of poles | 4 |
| Neutral rating | 100% In (fully rated neutral) |
| Protection functions | Thermal overload and adjustable magnetic short-circuit protection |
| Application | AC / DC circuit protection |
| Compatible circuit breaker family | ABB SACE Tmax T4 |
The ABB TMA250-2500T44pInN=100%In provides thermal overload and adjustable magnetic short-circuit protection when installed with a compatible ABB SACE Tmax T4 moulded-case circuit breaker.
The trip unit has a rated current of 250 A.
The TMA250-2500T44p has an adjustable instantaneous magnetic trip setting of 1250–2500 A.
InN=100%In means the neutral pole is fully rated at 100% of the phase rated current, providing full neutral protection in suitable four-wire electrical distribution systems.
The trip unit is designed for use with compatible ABB SACE Tmax T4 moulded-case circuit breakers.
ABB SACE Tmax circuit protection equipment is designed for dependable low-voltage electrical distribution, combining robust construction with coordinated overload and short-circuit protection for industrial and commercial installations.