ABB TMA200-2000T44pInN=100%In 1SDA054673R1 is a 200 A four-pole adjustable thermomagnetic trip unit with a 1000–2000 A magnetic trip range and fully rated neutral for compatible ABB SACE Tmax T4 moulded-case circuit breakers.
£2,764.81
The ABB TMA200-2000T44pInN=100%In, order code 1SDA054673R1, is a high-performance four-pole thermomagnetic trip unit designed for ABB SACE Tmax T4 moulded-case circuit breakers. Part of the ABB Tmax T4 protection system, it provides reliable overload and short-circuit protection for low-voltage AC and DC electrical distribution applications.
The TMA trip unit combines adjustable thermal overload protection with adjustable magnetic short-circuit protection in a robust electromechanical design. This allows protection settings to be matched more closely to the requirements of the electrical installation while providing dependable operation without relying on an external auxiliary power supply.
With a rated current of 200 A and an adjustable instantaneous magnetic trip range of 1000–2000 A, the TMA200-2000T44p is intended for four-pole ABB Tmax T4 circuit breakers. This version features a fully rated neutral at 100% of the phase current, making it suitable for four-wire distribution systems where full neutral conductor protection is required.
Thermomagnetic releases such as the ABB TMA200-2000T44p protect electrical circuits using complementary thermal and magnetic operating principles. The thermal element responds to sustained overload currents to help prevent excessive heating of cables and connected equipment, while the magnetic element provides rapid operation when high short-circuit currents occur.
The adjustable TMA design enables protection characteristics to be matched to the electrical installation. Combined with its four-pole configuration and fully rated neutral, the TMA200-2000T44p provides a practical protection solution for industrial and commercial four-wire distribution systems using compatible ABB Tmax T4 moulded-case circuit breakers.
| Series | SACE Tmax T4 |
|---|---|
| Order code | 1SDA054673R1 |
| Product group | 310511-T-Max T4 - T8 |
| Product type | Thermomagnetic trip unit / release |
| Trip unit type | TMA |
| Rated current | 200 A |
| Instantaneous magnetic trip setting (I3) | 1000–2000 A |
| Number of poles | 4 |
| Neutral rating | 100% In (fully rated neutral) |
| Protection functions | Adjustable thermal overload and magnetic short-circuit protection |
| Application | AC / DC circuit protection |
| Compatible circuit breaker family | ABB SACE Tmax T4 |
The ABB TMA200-2000T44pInN=100%In provides adjustable thermal overload and magnetic short-circuit protection when used with a compatible ABB SACE Tmax T4 moulded-case circuit breaker.
The trip unit has a rated current of 200 A.
The TMA200-2000T44p has an adjustable instantaneous magnetic trip setting of 1000–2000 A.
InN=100%In indicates that the neutral pole is fully rated at 100% of the phase rated current, providing a fully rated neutral for suitable four-wire electrical distribution systems.
The trip unit is designed for use with compatible ABB SACE Tmax T4 moulded-case circuit breakers.