ABB 1SDA054642R1 is a 160 A four-pole PR222DS/PD-LSI electronic trip unit for SACE Tmax T4 circuit breakers with LSI protection and integrated Modbus RTU communication.
£2,452.55
The ABB 1SDA054642R1 is a PR222DS/PD-LSI electronic trip unit designed for use with four-pole ABB SACE Tmax T4 moulded-case circuit breakers. Rated at 160 A, it combines electronic LSI protection with integrated Modbus RTU communication for power distribution, industrial control and automation applications.
As part of the ABB Tmax T protection system, the PR222DS/PD provides overload (L), selective short-circuit (S) and instantaneous short-circuit (I) protection. Protection parameters can be configured through the trip unit, while its electronic architecture supports accurate protection and monitoring within compatible Tmax T4 installations.
The integrated communication unit allows the circuit breaker to be incorporated into a Modbus RTU network using an EIA RS-485 physical interface. Communication operates at speeds up to 19.2 kbps and requires a 24 V DC auxiliary supply, enabling connection with PLCs, PCs and compatible supervision or automation systems.
The ABB PR222DS/PD combines electronic circuit protection with communication capabilities for intelligent low-voltage distribution systems. Its LSI functions protect against overload and short-circuit conditions, while the protection section is powered from the trip unit current transformers so that protective tripping does not depend on the communication auxiliary supply.
Integrated Modbus RTU communication enables compatible Tmax T4 circuit breakers to participate in industrial supervision and automation networks. With the required 24 V DC auxiliary supply, operating information and protection parameters can be communicated remotely, supporting more effective monitoring and management of electrical distribution equipment.
| Product family | SACE Tmax T |
|---|---|
| Trip unit series | PR222DS/PD |
| ABB order code | 1SDA054642R1 |
| Product type | Electronic trip unit |
| Suitable for | Tmax T4 moulded-case circuit breaker |
| Number of poles | 4P |
| Rated current (In) | 160 A |
| Protection functions | LSI – overload, selective short-circuit and instantaneous short-circuit |
| Communication protocol | Modbus RTU |
| Communication interface | EIA RS-485 |
| Maximum communication speed | 19.2 kbps |
| Communication auxiliary supply | 24 V DC ±20% |
| Rated current at 24 V DC | 100 mA |
| Rated power at 24 V DC | 2.5 W |
| Standard | IEC |
| Configuration type | Loose or configurable |
| Product net weight | 1.3 kg |
The ABB 1SDA054642R1 is a PR222DS/PD-LSI electronic trip unit rated at 160 A for compatible four-pole ABB SACE Tmax T4 moulded-case circuit breakers.
It provides L, S and I protection, covering overload, delayed or selective short-circuit and instantaneous short-circuit protection.
Yes. The PR222DS/PD incorporates Modbus RTU communication using an EIA RS-485 interface for integration with compatible industrial monitoring and automation systems.
The communication functions require a 24 V DC auxiliary power supply, with ABB specifying a permitted supply tolerance of ±20%.
This electronic trip unit is designed for a four-pole ABB SACE Tmax T4 moulded-case circuit breaker configuration.
The trip unit has a rated current (In) of 160 A.
ABB SACE Tmax protection products are used in industrial and commercial low-voltage distribution systems where dependable circuit protection, system integration and effective electrical monitoring are required.