Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OTDC600UF11 is a UL 98B rated 600 A 2-pole 1000 V DC switch disconnector designed for reliable isolation of a single circuit in utility-scale photovoltaic and high-current DC power systems.
£626.21
The ABB OTDC600UF11, order code 1SCA158233R1001, is a high-performance 600 A 2-pole DC switch disconnector designed for reliable switching and isolation in demanding 1000 V DC power systems. Part of the ABB OTDC range, this UL-rated switch is particularly suited to utility-scale photovoltaic installations, power-conversion equipment and other high-current DC applications.
The OTDC600UF11 uses an optimised 2-pole, single-circuit architecture that allows one photovoltaic or DC circuit to be disconnected using a compact switching device. It is front operated with the operating mechanism positioned between the poles and is designed for base mounting, providing straightforward integration into combiner boxes, inverters and industrial DC distribution equipment.
Rated at 600 A at 1000 V DC under UL 98B, the OTDC600UF11 combines high-current capability with a compact footprint. It also carries IEC ratings up to 630 A DC-21B at 1000 V DC, a 1500 V insulation voltage and 12 kV impulse withstand voltage, providing robust electrical performance for demanding DC installations.
The ABB OTDC600UF11 is specifically engineered for high-current photovoltaic applications where dependable DC isolation is essential. Its UL 98B rating of 600 A at 1000 V DC makes it suitable for North American photovoltaic equipment, while its IEC ratings allow the same compact platform to support a broad range of international DC power applications.
ABB's optimised two-pole architecture enables the OTDC600UF11 to disconnect a single photovoltaic circuit while minimising installation space and electrical losses. With a width of just 150 mm and a height of approximately 122 mm, the design helps manufacturers create more compact combiner boxes, inverter assemblies and DC distribution equipment without compromising high-current switching capability.
Tick the specs you need, then view products that match.
| Poles | 2-pole | |
|---|---|---|
| Device Type | Switch Disconnector | |
| Current | 600 A | |
| Product Series | ABB OTDC | |
| Series | OTDC DC Switch Disconnectors | |
| ABB order code | 1SCA158233R1001 | |
| ABB product group | 311027-OT Switches | |
| Product type | DC / photovoltaic switch disconnector | |
| UL rated operational current | 600 A at 1000 V DC | |
| IEC rated operational current DC-21B | 630 A at 1000 V DC | |
| Rated operational current DC-22B | 400 A at 1000 V DC | |
| Rated operational current DC-PV1 | 500 A at 1000 V DC | |
| Rated operational current DC-PV2 | 500 A at 1000 V DC | |
| Rated operational voltage | 1000 V DC | |
| Number of poles | 2 | |
| Number of circuits | 1 | |
| Connection configuration | 2a / 2b | |
| Operating mode | Front operated | |
| Operating mechanism | Mechanism between the poles | |
| Conventional free-air thermal current | 630 A at 40 °C | |
| Conventional enclosed thermal current | 630 A | |
| Rated insulation voltage | 1500 V | |
| Rated impulse withstand voltage | 12 kV | |
| Rated short-circuit making capacity | 10 kA at 1000 V DC | |
| Rated short-time withstand current | 10 kA for 1 s | |
| Power loss | 30–32 W per pole at rated operating conditions | |
| Protection rating | IP20 at front | |
| Mounting type | Base mounting | |
| Terminal type | Lug terminals | |
| Terminal width | 30 mm | |
| Shaft diameter | 12 mm | |
| Mechanical durability | 10,000 cycles | |
| Pollution degree | 3 | |
| Handle | Not included | |
| Shaft | Not included | |
| Product width | 150 mm | |
| Product height | 122 mm | |
| Net weight | approx. 3.5 kg | |
| Standards | UL 98B, IEC 60947-1, IEC 60947-3 |
The ABB OTDC600UF11 is a 600 A 2-pole 1000 V DC switch disconnector designed primarily for utility-scale photovoltaic installations, including inverter, combiner-box and other high-current DC isolation applications.
The OTDC600UF11 is rated at 600 A at 1000 V DC under UL 98B, making it suitable for high-current photovoltaic disconnect applications requiring UL-approved switching equipment.
Under IEC 60947-3, the OTDC600UF11 provides a DC-21B operational current rating of 630 A at 1000 V DC. It also carries DC-22B, DC-PV1 and DC-PV2 ratings for applicable DC loads.
The OTDC600UF11 is a 2-pole switch configured for one DC circuit, making it suitable for disconnecting a single photovoltaic or other DC power circuit.
No. The OTDC600UF11 is supplied without a handle and operating shaft, allowing suitable ABB operating accessories to be selected according to the enclosure and installation requirements.