Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OT160GT03P is a 160 A 3-pole door-mounted switch-disconnector supplied with an IP65 external handle, shaft and mounting kit for industrial load switching and electrical isolation.
£215.26
The ABB OT160GT03P is a compact, high-performance 160 A 3-pole switch-disconnector designed for dependable load switching and electrical isolation in industrial low-voltage systems. Part of the ABB OT160G switch-disconnector range, it provides strong IEC switching performance together with UL/CSA ratings for machinery, switchboards and power distribution applications.
This OT160GT P-version is specifically designed for door mounting and is supplied with an OHB65J6 black external handle, OXP6X50 shaft and OHZX6 door-mounting kit. The external handle provides IP65 protection, while the switch uses protected clamp terminals for secure connection of the main power conductors.
The OT160GT03P provides 160 A AC-22A and AC-23A operational current at 690 V AC, with an AC-23A operational power rating of 132 kW at 690 V AC. It is also rated at 100 A UL 98 Listed and 125 A UL 98 Recognized at 600 V, supporting industrial equipment designed for IEC and North American markets.
The ABB OT160GT03P provides dependable three-phase load switching and electrical isolation with 160 A AC-23A capability throughout the 380–690 V AC range. Its AC-23A performance makes it suitable for demanding industrial loads, while its three-pole configuration simultaneously switches all three phase conductors.
The P-version provides a complete door-operating arrangement with the OHB65J6 external handle, OXP6X50 shaft and OHZX6 mounting kit. Combined with protected main terminals and an IP65 external handle, this configuration is particularly well suited to industrial machinery panels and electrical enclosures requiring externally accessible switching and isolation.
Tick the specs you need, then view products that match.
| Poles | 3-pole | |
|---|---|---|
| Device Type | Switch Disconnector | |
| Current | 160 A | |
| Power | 75 kW | |
| Product Series | ABB OT | |
| Series | OT160G | |
| ABB order code | 1SCA135141R1001 | |
| ABB product group | 311027-OT Switches | |
| Product type | Switch-disconnector | |
| Number of poles | 3 | |
| Conventional free-air thermal current | 160 A | |
| Fully enclosed thermal current | 160 A | |
| Rated operational current AC-21A at 380–415 V AC | 160 A | |
| Rated operational current AC-21A at 500 V AC | 160 A | |
| Rated operational current AC-21A at 690 V AC | 160 A | |
| Rated operational current AC-22A at 380–415 V AC | 160 A | |
| Rated operational current AC-22A at 500 V AC | 160 A | |
| Rated operational current AC-22A at 690 V AC | 160 A | |
| Rated operational current AC-23A at 380–415 V AC | 160 A | |
| Rated operational current AC-23A at 500 V AC | 160 A | |
| Rated operational current AC-23A at 690 V AC | 160 A | |
| Rated operational power AC-23A at 400–415 V AC | 75 kW | |
| Rated operational power AC-23A at 500 V AC | 90 kW | |
| Rated operational power AC-23A at 690 V AC | 132 kW | |
| Rated operational voltage | 1000 V | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 12 kV | |
| Rated short-time withstand current (Icw) | 4 kA for 1 s | |
| Rated short-circuit making capacity at 690 V | 12 kA | |
| UL 98 Listed rating at 600 V | 100 A | |
| UL 98 Recognized rating at 600 V | 125 A | |
| Operating mechanism | Mechanism at left end of switch | |
| Operating mode | Front and side operation | |
| Mounting type | Door mounted | |
| Terminal type | Protected clamp / screw terminals | |
| Cable cross-section | 10–70 mm² Cu | |
| External handle | OHB65J6 black handle included | |
| Shaft | OXP6X50 included | |
| Door-mounting kit | OHZX6 included | |
| External handle protection | IP65 | |
| Mechanical durability | 20,000 operations | |
| Standards | IEC 60947-3, UL 98, CSA C22.2 No. 4 |
The ABB OT160GT03P is a 160 A 3-pole door-mounted switch-disconnector designed for load switching and electrical isolation in industrial machinery, switchboards and low-voltage power distribution systems.
The OT160GT03P has a conventional free-air thermal current of 160 A and is rated at 160 A for AC-21A, AC-22A and AC-23A duties at 690 V AC.
The P-version includes an OHB65J6 black external handle, OXP6X50 shaft and OHZX6 door-mounting kit.
The supplied external operating handle provides IP65 protection, making it suitable for demanding industrial enclosure applications.
The protected clamp terminals accommodate copper conductors with cross-sectional areas from 10–70 mm².
Yes. The OT160GT03P is rated at 100 A UL 98 Listed and 125 A UL 98 Recognized at 600 V, in addition to its IEC ratings.
ABB OT switch-disconnectors are widely used in industrial machinery, switchboards and power distribution systems where dependable load switching, positive electrical isolation and internationally recognised electrical performance are required.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.