ABB 1SCA022860R5510 OT1250E03 is a 1250 A 3-pole front-operated switch-disconnector with 50 kA short-time withstand current for 1 s, supplied without a handle or shaft and with a terminal bolt kit included.
£1,317.49
The ABB 1SCA022860R5510, order code OT1250E03, is a heavy-duty 1250 A, 3-pole switch-disconnector designed for reliable high-current switching and electrical isolation. As part of the ABB 311027-OT Switches product group, it belongs to ABB's OT range of manually operated switch-disconnectors for industrial power distribution and switchboard applications.
The OT1250E03 is a front-operated, base-mounted 3-pole switch-disconnector. This specific version is supplied without an operating handle or shaft, allowing the appropriate ABB handle and shaft arrangement to be selected separately to suit the enclosure and installation depth. A terminal bolt kit is included with the switch.
With a conventional free-air thermal current of 1250 A and rated operational currents of 1250 A for both AC-22A and AC-23A duties, the OT1250E03 is engineered for demanding industrial loads. It also provides a 50 kA short-time withstand current for 1 s, a rated operational voltage of up to 1000 V and substantial AC-23A switching performance for high-power applications.
Switch-disconnectors provide a dedicated means of manually switching and safely isolating electrical circuits from their power source. The ABB OT1250E03 combines a substantial 1250 A current capacity with three-pole switching, making it suitable for high-current three-phase distribution systems, machinery supplies and industrial switchboards.
This OT1250E03 version is supplied without a handle and shaft, giving panel builders and system designers flexibility to select the appropriate ABB operating accessories for the enclosure depth and installation arrangement. Its 50 kA Icw for 1 s, high AC-23A switching capability and 1000 V operational rating make it a robust solution for demanding industrial isolation duties.
Tick the specs you need, then view products that match.
| Poles | 3-pole | |
|---|---|---|
| Device Type | Switch Disconnector | |
| Current | 1250 A | |
| Power | 710 kW | |
| Product Series | ABB OT | |
| Product group | 311027-OT Switches | |
| Series | OT1250 | |
| Order code | OT1250E03 | |
| Product ID / MPN | 1SCA022860R5510 | |
| Product type | Switch-disconnector | |
| Rated current | 1250 A | |
| Number of poles | 3 | |
| Conventional free-air thermal current (Ith) | 1250 A at 40 °C | |
| Fully enclosed thermal current | 1250 A | |
| Rated operational current AC-21A at 690 V | 1250 A | |
| Rated operational current AC-21A at 1000 V AC | 1250 A | |
| Rated operational current AC-22A at 500 V | 1250 A | |
| Rated operational current AC-22A at 690 V | 1250 A | |
| Rated operational current AC-23A at 500 V | 1250 A | |
| Rated operational current AC-23A at 690 V | 1250 A | |
| Rated operational power AC-23A at 400 V | 710 kW | |
| Rated operational power AC-23A at 415 V | 710 kW | |
| Rated operational power AC-23A at 500 V | 900 kW | |
| Rated operational power AC-23A at 690 V | 1200 kW | |
| Rated operational voltage | 1000 V | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 12 kV | |
| Rated short-time withstand current (Icw) | 50 kA for 1 s | |
| Operation | Front operated | |
| Mounting | Base mounting | |
| Operating mechanism | Mechanism at the end of the switch | |
| Handle | Not included | |
| Operating shaft | Not included | |
| Terminal bolt kit | Included | |
| Terminal type | Lug terminals | |
| Front protection | IP00 without external operating handle | |
| Dimensions (W × H × D) | approx. 334.5 × 306 × 145.5 mm | |
| Product net weight | approx. 17 kg | |
| EAN | 6417019309262 |
The ABB OT1250E03 is a 1250 A, 3-pole switch-disconnector designed for high-current switching and electrical isolation in industrial power distribution systems.
The OT1250E03 has a conventional free-air thermal current of 1250 A and provides 1250 A AC-22A and AC-23A rated operational current.
No. This specific OT1250E03 version is supplied without an operating handle and shaft. These components must be selected and ordered separately to suit the installation. The terminal bolt kit is included.
The OT1250E03 has a rated short-time withstand current (Icw) of 50 kA for 1 s, supporting use in demanding high-current distribution systems.
The ABB OT1250E03 has a rated operational voltage of up to 1000 V and a rated impulse withstand voltage of 12 kV.