Lovato GL1600C1 is a 1600 A three-pole AC switch disconnector designed for reliable high-current isolation and switching in industrial power distribution systems and switchboards.
£1,196.84
The Lovato GL1600C1 is a heavy-duty 1600 A three-pole switch disconnector designed for safe isolation and switching of high-current AC circuits in industrial power distribution systems. Part of the Lovato GL switch disconnector series, it is engineered for switchboards, machinery and industrial installations requiring dependable high-current electrical isolation.
The GL1600C1 has a conventional free-air thermal current rating of 1600 A and maintains a 1600 A AC-21A operational current at 400, 500, 690 and 1000 V AC. It is also rated for AC-22A and AC-23A duties at specified voltages, making it suitable for a broad range of industrial switching and load-isolation applications.
With a rated insulation voltage of 1000 V, rated impulse withstand voltage of 12 kV and rated short-time withstand current of 50 kA for 1 s, the GL1600C1 is designed for demanding power installations. Its three-pole construction, M12 power terminals and screw-on-plate mounting make it particularly suitable for integration into large industrial switchboards and distribution assemblies.
High-current switch disconnectors provide a defined means of isolating electrical circuits and equipment from their power source, helping maintenance personnel establish safe isolation before servicing switchboards, machinery or downstream electrical equipment. The Lovato GL1600C1 is engineered for this demanding role in high-power AC distribution systems.
Its 1600 A three-pole architecture, high short-circuit withstand capability and AC-21A, AC-22A and AC-23A ratings make the GL1600C1 suitable for major industrial feeders and power distribution assemblies. The switch is designed for screw mounting onto a plate and can be combined with compatible Lovato GL operating and installation accessories to suit the switchboard design.
Tick the specs you need, then view products that match.
| Current | 1600 A | |
|---|---|---|
| Device Type | Switch Disconnector | |
| Power | 900 kW | |
| Product Series | Lovato GL | |
| Poles | 3-pole | |
| HS Code | 85365080 | |
| Manufacturer | Lovato Electric | |
| Series | GL | |
| Model | GL1600C1 | |
| Product type | Switch disconnector | |
| Number of poles | 3 | |
| Operating voltage type | AC | |
| Conventional free-air thermal current (Ith) | 1600 A | |
| AC-21A operational current | 1600 A at 400 / 500 / 690 / 1000 V AC | |
| AC-22A operational current | 1600 A at 400 / 500 / 690 V AC | |
| AC-23A operational current | 1600 A at 400 / 500 / 690 V AC | |
| Rated operational power AC-23A | 900 kW at 400 V; 1000 kW at 690 V | |
| Rated insulation voltage (Ui) | 1000 V | |
| Rated impulse withstand voltage (Uimp) | 12 kV | |
| Rated short-time withstand current (Icw) | 50 kA for 1 s | |
| Conditional short-circuit current | 100 kA | |
| Recommended short-circuit fuse protection | gG, 2 × 800 A | |
| AC-23A making capacity at 400 V | 16000 A | |
| AC-23A breaking capacity at 400 V | 12800 A | |
| Maximum power dissipation per pole | 63 W | |
| Mechanical life | 3000 cycles | |
| Terminal type | M12 | |
| Terminal tightening torque | 50–75 Nm | |
| Minimum IEC busbar arrangement | 2 × 50 × 10 mm per connection | |
| Mounting | Screw on plate | |
| Normal operating position | Vertical plane | |
| Permitted operating position | Any | |
| Operating temperature | -25 to +55 °C | |
| Storage temperature | -40 to +70 °C | |
| Maximum operating altitude | 3000 m | |
| Weight | approx. 16 kg |
The GL1600C1 is a three-pole switch disconnector designed to provide safe isolation and switching of high-current AC circuits in industrial power distribution, switchboards and machinery applications.
The GL1600C1 has a conventional free-air thermal current rating of 1600 A and an AC-21A operational current of 1600 A at 400, 500, 690 and 1000 V AC.
The Lovato GL1600C1 has three poles, making it suitable for simultaneous isolation of three conductors in three-phase AC power systems.
Yes. The GL1600C1 is rated at 1600 A AC-23A at 400, 500 and 690 V AC, with rated operational power of 900 kW at 400 V and 1000 kW at 690 V.
The switch has a rated short-time withstand current of 50 kA for 1 s and a conditional short-circuit current of 100 kA when used with the specified short-circuit protection.
The GL1600C1 is designed for screw-on-plate mounting in electrical switchboards and uses heavy-duty M12 power terminals for its main electrical connections.
Lovato Electric GL series switch disconnectors are engineered for reliable isolation and power management in industrial electrical systems, providing robust switching solutions for switchboards, machinery and high-current power distribution installations.