Mersen 83230001 SP23-20K150V Type 2+3 surge protection replacement cartridge with 20 kA maximum discharge current, 10 kA nominal discharge current and 150 V AC maximum continuous operating voltage for compatible Surge-Trap devices.
£19.43
The Mersen 83230001, also known as SP23-20K150V, is a compact Type 2+3 surge protection replacement cartridge designed for compatible Mersen Surge-Trap pluggable surge protection devices. It helps protect low-voltage electrical systems from transient overvoltages caused by switching operations, indirect lightning effects and network disturbances.
As part of the Mersen Surge-Trap STP T23 series, this replacement cartridge is intended for final-stage surge protection where sensitive equipment requires additional protection close to the point of use. Its plug-in format enables fast replacement during maintenance, helping restore protection without replacing the complete surge protection assembly.
With a 20 kA maximum discharge current, 10 kA nominal discharge current and 150 V AC maximum continuous operating voltage, the Mersen 83230001 is a practical choice for Type 2+3 surge protection applications on 120 V electrical systems.
Type 2+3 surge protection devices are commonly used as a final stage of protection close to sensitive electrical equipment. They help reduce residual transient overvoltages after upstream surge protection has handled larger surge currents, supporting improved protection for electronics, controls and building services systems.
The Mersen 83230001 replacement cartridge enables maintenance teams to restore surge protection quickly without replacing the complete SPD base. This makes it suitable for panel builders, electrical contractors and facilities engineers maintaining reliable low-voltage electrical systems.
Tick the specs you need, then view products that match.
| Voltage | 150 V | |
|---|---|---|
| Phase | Single Phase | |
| Poles | 1-pole | |
| Device Type | Replacement cartridge | |
| SPD Type | Type 2+3 | |
| Nominal Discharge Current (In) | 10 kA | |
| Manufacturer | Mersen | |
| Series | Surge-Trap STP T23 | |
| Model | SP23-20K150V | |
| Manufacturer part number | 83230001 | |
| Product type | Surge protection replacement cartridge | |
| SPD classification | Type 2+3 / Class II+III | |
| Number of poles | 1 pole | |
| Nominal voltage | 120 V AC | |
| Maximum continuous operating voltage (Uc) | 150 V AC | |
| Nominal discharge current (In) | 10 kA | |
| Maximum discharge current (Imax) | 20 kA | |
| Protection rating | IP20 | |
| Mounting | Pluggable replacement cartridge | |
| Compatible installation | DIN rail SPD assembly |
The Mersen 83230001 is a Type 2+3 replacement cartridge for compatible Mersen Surge-Trap surge protection devices used in low-voltage electrical systems.
The alternative product code for Mersen 83230001 is SP23-20K150V.
This replacement cartridge is designed for 120 V AC nominal systems and has a 150 V AC maximum continuous operating voltage.
The Mersen 83230001 is designed for Type 2+3 / Class II+III surge protection assemblies.
It is typically installed in compatible Mersen Surge-Trap pluggable SPD assemblies within distribution boards, switchboards and final-stage protection circuits close to sensitive equipment.
Mersen Surge-Trap surge protection products are widely used by electrical engineers, panel builders and contractors to protect commercial and industrial electrical installations from damaging transient overvoltages.