SA0B2PA320R-ENC Lovato SURGE PROTECTION DEVICE TYPE 1-2 2P ENCLOSED

SA0B2PA320R-ENC Lovato SURGE PROTECTION DEVICE TYPE 1-2 2P ENCLOSED

Lovato SA0B2PA320R-ENC is an enclosed two-pole Type 1+2 surge protection device with 12.5 kA impulse current per pole, 50 kA maximum discharge current and 320 V AC maximum continuous operating voltage for low-voltage AC power systems.

SKU: SA0B2PA320R-ENC
Price
List Price £283.10 ex VAT
Your Price (ex VAT) Save 40%
£169.86 40% OFF
You save £113.24 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £169.86
Trade pricing is personalised to your account

Manufacturer Lead Time

£169.86

Why Choose the Lovato SA0B2PA320R-ENC Surge Protection Device?

The Lovato SA0B2PA320R-ENC is an enclosed two-pole Type 1+2 surge protection device (SPD) designed to protect low-voltage AC electrical installations against transient overvoltages caused by lightning and switching events. Built around the proven Lovato SA0B Type 1+2 monoblock SPD, it provides coordinated lightning-current and surge protection for power distribution applications.

The two-pole SPD has a maximum continuous operating voltage of 320 V AC and an impulse current Iimp of 12.5 kA per pole with a 10/350 µs waveform. It also provides a maximum discharge current Imax of 50 kA with an 8/20 µs waveform and a voltage protection level Up of less than 1.5 kV.

The SA0B2PA320R-ENC is based on a monoblock SPD with integrated thermal protection, frontal operating/end-of-life indication and a remote status contact. Its enclosed format provides a practical complete surge-protection assembly for electrical distribution systems where a housed Type 1+2 protective solution is required.

Key Advantages

  • Combined Type 1+2 surge protection for lightning-current and induced transient overvoltages.
  • Two-pole configuration suitable for corresponding AC power-line applications.
  • 12.5 kA Iimp per pole with a 10/350 µs lightning-current waveform.
  • 50 kA maximum discharge current Imax with an 8/20 µs waveform.
  • Low <1.5 kV voltage protection level Up.
  • Integrated remote contact enables remote monitoring of SPD status.
  • Enclosed construction provides a convenient assembled surge-protection solution.

Key Features

  • Lovato SA0B Type 1+2 surge protection technology.
  • Two-pole monoblock SPD.
  • Designed for AC power lines.
  • 320 V AC maximum continuous operating voltage Uc.
  • 12.5 kA impulse current Iimp per pole at 10/350 µs.
  • 20 kA nominal discharge current In at 8/20 µs.
  • 50 kA maximum discharge current Imax at 8/20 µs.
  • <1.5 kV voltage protection level Up.
  • Fast response time of <25 ns.
  • Frontal status indication and auxiliary remote contact.
  • Integrated thermal protection.

Reliable & Durable Surge Protection

Type 1+2 surge protection devices are designed to handle both high-energy lightning-current impulses and lower-energy transient overvoltages induced within an electrical installation. The Lovato SA0B2PA320R-ENC combines these functions in a two-pole enclosed solution suitable for installation near the incoming power distribution point.

Its 12.5 kA per-pole Iimp rating, 50 kA maximum discharge capability and voltage protection level below 1.5 kV provide robust protection for downstream electrical and electronic equipment. Integrated status indication and a remote contact also simplify inspection and remote monitoring of the protective device.

Typical Applications

  • Main low-voltage distribution boards.
  • Industrial and commercial electrical installations.
  • Single-phase power distribution systems.
  • Machinery and automation power supplies.
  • Building electrical distribution systems.
  • Installations exposed to lightning-related and induced transient overvoltages.

Technical Specifications

Tick the specs you need, then view products that match.

Impulse Current Iimp (kA) 12.5 kA
Device Type Surge protection device
SPD Type Type 1+2
Nominal Discharge Current (In) 20 kA
Remote Signal Yes
HS Code 85365080
Manufacturer Lovato Electric
Series SA0B
Model SA0B2PA320R-ENC
Product type Enclosed surge protection device (SPD)
SPD type / class Type 1+2
Number of poles 2
Application AC power lines
Rated system voltage 230 V AC
Maximum continuous operating voltage Uc 320 V AC
Impulse current Iimp (10/350 µs) 12.5 kA per pole
Nominal discharge current In (8/20 µs) 20 kA
Maximum discharge current Imax (8/20 µs) 50 kA
Voltage protection level Up <1.5 kV
Response time <25 ns
Thermal protection Integrated
Status indication Frontal operating / end-of-life indication
Remote indication Changeover auxiliary contact
SPD operating temperature −40 to +85 °C
Maximum altitude 2000 m
SPD mounting DIN rail
SPD flexible conductor capacity Up to 25 mm²
SPD rigid conductor capacity Up to 35 mm²
Standard IEC/EN 61643-11

Frequently Asked Questions

What is the Lovato SA0B2PA320R-ENC used for?

The SA0B2PA320R-ENC is an enclosed Type 1+2 surge protection device used to protect low-voltage AC electrical systems and connected equipment against lightning-current impulses and transient overvoltages.

What is the impulse current rating of the SA0B2PA320R-ENC?

The underlying two-pole SA0B SPD has an impulse current Iimp rating of 12.5 kA per pole using the 10/350 µs waveform.

What maximum surge current can the SA0B2PA320R-ENC discharge?

The SPD has a maximum discharge current Imax of 50 kA using the 8/20 µs waveform.

What is the voltage protection level of this Lovato SPD?

The SA0B2PA320R provides a voltage protection level Up of less than 1.5 kV.

Does the SA0B2PA320R-ENC provide remote status indication?

Yes. The SA0B2PA320R incorporates an auxiliary changeover contact for remote status indication as well as frontal operating and end-of-life indication.

Trusted for Industrial Surge Protection

Lovato surge protection devices provide dependable protection for industrial, commercial and building electrical installations, helping safeguard power distribution systems and sensitive equipment against damaging lightning-related and switching overvoltages.