Mersen Surge Protector Type 1+2 SPD 3 Pole 400 Volt 20KA TNC

Mersen Surge Protector Type 1+2 SPD 3 Pole 400 Volt 20KA TNC

Mersen STPT12-12K275V-3P Type 1+2 pluggable surge protection device with 12.5 kA lightning impulse current, 275 V maximum continuous operating voltage, 230/400 V AC nominal voltage, 3 pole 3+0 TNC configuration and DIN rail mounting.

SKU: 83120130Alt SKU: STPT12-12K275V-3PMPN: 83120130

Why Choose the Mersen 83120130 Surge Protection Device?

The Mersen 83120130 STPT12-12K275V-3P is a reliable Type 1+2 Surge Protection Device (SPD) designed to protect low voltage electrical installations against transient overvoltages caused by lightning activity and electrical switching events. As part of the Mersen Surge-Trap® Pluggable STPT12 Series, it provides dependable first-stage surge protection for industrial, commercial and infrastructure power distribution systems.

This pluggable SPD combines Class I and Class II surge protection in a compact DIN rail mounted format. Its replaceable cartridge design and clear status indication help simplify inspection and maintenance, making it suitable for incoming supply panels and installations exposed to atmospheric surges.

With a 12.5 kA lightning impulse current rating, 230/400 V nominal operating voltage and 275 V maximum continuous operating voltage, the Mersen 83120130 is ideal for protecting three-phase TNC distribution systems, switchboards, control panels and sensitive electrical equipment from damaging voltage surges.

Key Advantages

  • Combined Type 1+2 surge protection for low voltage installations.
  • 12.5 kA lightning impulse current (Iimp) for robust surge handling.
  • 275 V maximum continuous operating voltage for 230/400 V systems.
  • Pluggable cartridge design supports fast replacement and maintenance.
  • Compact 3-pole, 3-module DIN rail format.
  • Suitable for main distribution boards, incoming panels and industrial control systems.

Key Features

  • Mersen Surge-Trap® Pluggable STPT12 Series.
  • Type 1+2 / Class I+II surge protection device.
  • 12.5 kA Iimp (10/350 μs).
  • 50 kA maximum discharge current (Imax 8/20 μs).
  • 20 kA nominal discharge current (In 8/20 μs).
  • 230/400 V nominal operating voltage.
  • 275 V maximum continuous operating voltage.
  • 3-pole configuration for 3+0 TNC systems.
  • DIN rail mounted IP20 construction.

Reliable Protection Against Electrical Surges

Surge protection devices help protect electrical systems by safely limiting transient overvoltages before they reach connected equipment. This reduces the risk of damage to switchgear, control systems, drives, PLCs, instrumentation, power supplies and other sensitive electrical components.

The Mersen STPT12 range is designed for use as the first level of protection in main distribution boards and incoming supply panels. Its Type 1+2 classification makes it suitable for installations exposed to atmospheric surges and applications requiring coordinated protection against lightning currents and voltage spikes.

Typical Applications

  • Main low voltage distribution boards.
  • Incoming power supply panels.
  • Three-phase TNC electrical systems.
  • Industrial automation and control panels.
  • Commercial building electrical installations.
  • Switchboards, panel building and infrastructure systems.

Technical Specifications

Tick the specs you need, then view products that match.

Impulse Current Iimp (kA) 12.5 kA
Voltage 400 V
Phase Three Phase
Poles 3-pole
Device Type Surge protection device
SPD Type Type 1+2
Earthing System TN-C
Nominal Discharge Current (In) 20 kA
Remote Signal No
Manufacturer Mersen
Series Surge-Trap® Pluggable STPT12
Model STPT12-12K275V-3P
SKU 83120130
Product type Type 1+2 Surge Protection Device
IEC classification Class I+II
Lightning impulse current (Iimp) 12.5 kA (10/350 μs)
Maximum discharge current (Imax) 50 kA (8/20 μs)
Nominal operating voltage (Un) 230/400 V AC
Maximum continuous operating voltage (Uc) 275 V
System configuration TN-C
Network type TN-C
Protection mode L-PE(N)
Number of poles 3
Number of modules 3
Mounting type 35 mm DIN rail
Protection rating IP20
Format Pluggable
Dimensions (W × H × D) approx. 63 × 90 × 117 mm
Weight approx. 0.537 kg
HS Code 85363090
Country of Manufacture Spain

Frequently Asked Questions

What is the Mersen 83120130 used for?

It is used to protect low voltage electrical installations against transient overvoltages caused by lightning activity and switching events.

What type of surge protection does this device provide?

The Mersen 83120130 provides combined Type 1+2 / Class I+II surge protection.

What is the maximum continuous operating voltage?

The device has a 275 V maximum continuous operating voltage, making it suitable for 230/400 V AC systems.

Is the Mersen 83120130 pluggable?

Yes. It uses a pluggable cartridge design, allowing the protection module to be replaced quickly when required.

Where is this surge protection device typically installed?

It is typically installed on a DIN rail inside main distribution boards, incoming panels or electrical switchboards.

Trusted for Critical Power Protection

Mersen Surge-Trap® surge protection devices are trusted by electrical engineers, panel builders and industrial facilities worldwide for dependable protection of power distribution systems and sensitive connected equipment.