Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Mersen STPT23-20K320V-4PM Type 2+3 surge protection device with 20 kA discharge capacity, 320 V AC operating voltage, 4+0 TNS configuration and remote indication.
£102.00
The Mersen 83230133 is a high performance Type 2+3 Surge Protection Device (SPD) designed to protect low voltage electrical installations from transient overvoltages caused by lightning strikes and switching events. As part of the Mersen Surge-Trap® Pluggable STPT23 Series, it combines robust surge protection with a compact pluggable design, making it ideal for commercial, industrial and automation applications.
Designed for three-phase plus neutral systems, this four-pole SPD provides reliable protection for switchboards, control panels and critical electrical equipment. The pluggable cartridges simplify servicing, while the integrated remote indication contact enables continuous monitoring of the device status for proactive maintenance.
With a maximum discharge current of 20 kA (8/20 μs), a 320 V AC continuous operating voltage (Uc) and a 4+0 TNS configuration, the Mersen 83230133 is suitable for protecting installations operating on 230/400 V AC and 277/480 V AC networks.
Surge protection devices divert damaging transient overvoltages away from connected equipment before they can cause insulation failure, electronic damage or costly downtime. Installing an SPD helps improve system reliability while extending the service life of sensitive electrical equipment.
The Mersen Surge-Trap® STPT23 Series is designed as the final stage of protection within low voltage installations where upstream Type 2 protection is already provided. It is suitable for industrial automation, commercial buildings, motor control centres, telecommunications, data centres and renewable energy applications.
Tick the specs you need, then view products that match.
| Voltage | 480 V | |
|---|---|---|
| Phase | Three Phase | |
| Poles | 4-pole | |
| Device Type | Surge protection device | |
| SPD Type | Type 2+3 | |
| Earthing System | TN-S | |
| Nominal Discharge Current (In) | 10 kA | |
| Remote Signal | Yes | |
| Manufacturer | Mersen | |
| Series | Surge-Trap® Pluggable STPT23 Series | |
| Model | STPT23-20K320V-4PM | |
| SKU | 83230133 | |
| Product type | Surge Protection Device (SPD) | |
| SPD classification | Type 2+3 / Class II+III | |
| Maximum discharge current (Imax) | 20 kA (8/20 μs) | |
| Nominal Discharge Current (In) | 10 kA | |
| Combined discharge voltage (Uoc) | 10 kV | |
| Continuous operating voltage (Uc) | 320 V AC | |
| Nominal operating voltage (Un) | 230/400 V AC, 277/480 V AC | |
| System configuration | TN-S | |
| Protection modes | L-PE / N-PE | |
| Number of poles | 4 | |
| Number of modules | 4 | |
| Mounting type | DIN rail | |
| Format | Pluggable modular device | |
| Remote indication | Yes | |
| Protection rating | IP20 | |
| Short circuit withstand (ISCCR) | 25 kA | |
| Maximum back-up fuse | 63 A gG | |
| Response time | ≤25 ns | |
| Product dimensions (H × W × D) | 90 × 72 × 70 mm | |
| Product weight | Approx. 0.366 kg | |
| EAN | 8435297849346 | |
| HS Code | 85363090 | |
| Country of Manufacture | Spain |
It protects low voltage electrical installations and connected equipment from transient overvoltages caused by lightning strikes and switching events.
The Mersen 83230133 is a Type 2+3 / Class II+III surge protection device.
It is designed for 230/400 V AC and 277/480 V AC three-phase plus neutral TNS systems using a 4+0 configuration.
Yes. The integrated remote indication contact allows the surge protection device status to be monitored remotely.
Yes. The pluggable cartridge design enables quick replacement without removing the complete base from the DIN rail.
Mersen Surge-Trap® surge protection devices are trusted by electrical engineers, panel builders and industrial maintenance professionals to safeguard critical electrical infrastructure against damaging transient overvoltages.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.