K2-3P320-M Mersen Surge Protector Type 2 SPD 3 Pole 480 Volt 20KA TNC Remote Indication

K2-3P320-M Mersen Surge Protector Type 2 SPD 3 Pole 480 Volt 20KA TNC Remote Indication

Mersen 44020305 K2-3P320-M Type 2 three-pole surge protection device for 277/480 V TN-C systems, featuring remote signalling, a 320 V AC maximum continuous operating voltage, 20 kA nominal discharge current and 50 kA maximum discharge current.

SKU: 44020305Alt SKU: K2-3P320-MMPN: 44020305
Price
List Price £131.24 ex VAT
Your Price (ex VAT) Save 25%
£98.43 25% OFF
You save £32.81 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £98.43
Trade pricing is personalised to your account

Manufacturer Lead Time

£98.43

Why Choose the Mersen 44020305 K2-3P320-M Surge Protection Device?

The Mersen 44020305, also identified as the K2-3P320-M, is a high-performance Type 2 surge protection device (SPD) designed to protect three-phase low-voltage electrical installations against transient overvoltages. Part of the trusted Mersen Surge-Trap K2 series, it is suitable for 277/480 V TN-C electrical systems and incorporates an integrated remote signalling contact for continuous condition monitoring.

The K2-3P320-M uses a compact pluggable construction, allowing the protection cartridges to be inspected or replaced without removing the complete DIN-rail base. A clear visual status indicator provides local confirmation of the device condition, while the integrated microswitch enables remote monitoring through PLCs, SCADA platforms, alarm circuits and building management systems.

Featuring a 320 V AC maximum continuous operating voltage, a 20 kA nominal discharge current and a 50 kA maximum discharge current, the Mersen 44020305 provides dependable protection against lightning-induced surges and switching transients. Its three-pole design is ideal for industrial switchgear, commercial distribution boards, motor control centres and automation installations where remote indication is required.

Key Advantages

  • Reliable Type 2 surge protection for three-phase 277/480 V systems.
  • Integrated remote signalling microswitch for continuous status monitoring.
  • 50 kA maximum discharge current for robust transient protection.
  • Pluggable protection cartridges simplify inspection and replacement.
  • Visual condition indicator enables rapid local status checks.
  • Compact three-module DIN-rail construction saves enclosure space.

Key Features

  • Mersen Surge-Trap K2 series.
  • Type 2 / Class II surge protection device.
  • Three-pole design.
  • 3+0 protection configuration.
  • 277/480 V AC nominal operating voltage.
  • 320 V AC maximum continuous operating voltage (Uc).
  • 20 kA nominal discharge current (In).
  • 50 kA maximum discharge current (Imax).
  • Protection mode: L-PE(N).
  • Integrated visual indication and remote signalling microswitch.
  • Dynamic thermal disconnection technology.
  • Replaceable plug-in protection cartridges.

Three-Phase Surge Protection with Remote Monitoring

Transient overvoltages produced by indirect lightning strikes, utility switching, motors, transformers and other inductive loads can damage PLCs, variable speed drives, communication equipment and power supplies. Although these voltage spikes are extremely brief, they can cause immediate equipment failure or gradually degrade sensitive electronic components.

The Mersen K2-3P320-M diverts excessive surge energy towards earth before it reaches connected equipment. Its integrated remote contact allows maintenance teams to monitor the protection status from a central control system, while the pluggable cartridges provide fast replacement when servicing becomes necessary.

Typical Applications

  • 277/480 V TN-C distribution boards.
  • Industrial switchgear assemblies.
  • Motor control centres.
  • PLC and automation control panels.
  • SCADA and building management systems.
  • Commercial and industrial power distribution installations.

Technical Specifications

Tick the specs you need, then view products that match.

Voltage 480 V
Phase Three Phase
Poles 3-pole
Device Type Surge protection device
SPD Type Type 2
Earthing System TN-C
Nominal Discharge Current (In) 20 kA
Remote Signal Yes
Manufacturer Mersen
Series Surge-Trap K2
Model K2-3P320-M
SKU / Part number 44020305
Product type Surge protection device
IEC SPD classification Type 2 / Class II
UL SPD classification Type 1 Component Assembly
Configuration TN-C
Number of poles 3
System configuration TN-C
Protection mode L-PE(N)
Nominal operating voltage 277/480 V AC
Maximum continuous operating voltage 320 V AC
Nominal discharge current 20 kA
Maximum discharge current 50 kA
Surge current waveform 8/20 µs
Voltage protection level ≤1.5 kV
Response time ≤25 ns
Residual current <1 mA
Short-circuit withstand rating 25 kA
Maximum back-up fuse 315 A gG
Thermal protection behaviour Open Circuit Mode
Dynamic thermal disconnection Yes
Status indication Green (OK) / Not green (replace)
Remote signalling Integrated microswitch
Terminal tightening torque 3 Nm
Construction Pluggable
Mounting type DIN rail
DIN rail modules 3
Dimensions (H × W × D) 90 × 54 × 74.4 mm
RoHS compliant Yes
EAN / UPC 8435297889908
HS Code 85363090
Country of Manufacture Spain

Frequently Asked Questions

What is the Mersen 44020305 used for?

The Mersen 44020305 protects three-phase 277/480 V electrical installations against transient overvoltages while providing remote indication of the surge protection device status.

What type of surge protection device is the K2-3P320-M?

It is a Type 2 / Class II surge protection device intended primarily as a second level of protection in low-voltage electrical installations.

Does the K2-3P320-M provide remote monitoring?

Yes. The integrated microswitch can transmit the device status to PLCs, alarm circuits, SCADA platforms and building management systems.

What discharge current can the Mersen 44020305 withstand?

The device has a 20 kA nominal discharge current and a 50 kA maximum discharge current, based on the standard 8/20 µs surge waveform.

Which electrical system is compatible with this SPD?

The K2-3P320-M is designed for three-phase 277/480 V TN-C electrical systems and has a maximum continuous operating voltage of 320 V AC per protection pole.

Can the protection cartridges be replaced?

Yes. The pluggable construction allows the protection cartridges to be replaced without disconnecting or removing the complete DIN-rail base.

Trusted Surge Protection from Mersen

Mersen Surge-Trap K2 surge protection devices are trusted by electrical engineers, panel builders and maintenance professionals to protect critical three-phase installations while providing straightforward servicing and dependable remote condition monitoring.