K2-2P275 Mersen Surge Protector Type 2 SPD 2 Pole 230 Volt 20KA TNS

K2-2P275 Mersen Surge Protector Type 2 SPD 2 Pole 230 Volt 20KA TNS

Mersen 44020202 K2-2P275 Type 2 surge protection device with 2+0 configuration, 275 V AC maximum continuous operating voltage, 20 kA nominal discharge current and 50 kA maximum discharge current.

SKU: 44020202Alt SKU: K2-2P275MPN: 44020202
Price
List Price £69.24 ex VAT
Your Price (ex VAT) Save 25%
£51.93 25% OFF
You save £17.31 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £51.93
Trade pricing is personalised to your account

Manufacturer Lead Time

£51.93

Why Choose the Mersen 44020202 K2-2P275 Surge Protection Device?

The Mersen 44020202, also identified as the K2-2P275, is a compact and reliable Type 2 surge protection device (SPD) designed to protect single-phase low-voltage electrical installations against transient overvoltages. As part of the proven Mersen Surge-Trap K2 series, it provides effective line-to-neutral surge protection for TN-S electrical systems, helping safeguard sensitive equipment from lightning-induced surges and switching transients.

The K2-2P275 features a pluggable cartridge design that enables quick inspection and replacement without removing the complete DIN-rail base. Its integrated visual status indicator makes it easy to identify the operating condition, reducing maintenance time while ensuring continuous surge protection for critical electrical installations.

With a 230 V AC nominal operating voltage, a 275 V AC maximum continuous operating voltage, a 20 kA nominal discharge current and a 50 kA maximum discharge current, the Mersen 44020202 delivers dependable protection for commercial, industrial and infrastructure applications. Its compact two-module DIN-rail design allows straightforward installation in distribution boards, switchgear and control panels.

Key Advantages

  • Reliable Type 2 surge protection for single-phase TN-S electrical systems.
  • Two-pole (2+0) protection for line-to-neutral circuits.
  • 50 kA maximum discharge current for effective transient overvoltage protection.
  • Pluggable cartridge design simplifies servicing and replacement.
  • Compact DIN-rail mounting saves valuable panel space.
  • Visual operating status indicator enables quick maintenance checks.

Key Features

  • Mersen Surge-Trap K2 series.
  • Type 2 / Class II surge protection device.
  • 2+0 internal configuration.
  • Two-pole design.
  • 230 V AC nominal operating voltage.
  • 275 V AC maximum continuous operating voltage.
  • 20 kA nominal discharge current.
  • 50 kA maximum discharge current.
  • Voltage protection level of ≤1.5 kV.
  • Visual operating status indicator.
  • Dynamic thermal disconnection technology.
  • Compact pluggable DIN-rail construction.

Reliable Surge Protection for Single-Phase Electrical Systems

Transient overvoltages generated by indirect lightning strikes, switching operations and inductive loads can damage drives, PLCs, power supplies, communication equipment and other sensitive electronics. Installing a dedicated Type 2 surge protection device helps reduce costly equipment failures while improving overall electrical system reliability.

The Mersen Surge-Trap K2 series combines high discharge capability, rapid response and replaceable protection cartridges, making routine maintenance straightforward while providing dependable long-term protection for valuable electrical infrastructure.

Typical Applications

  • Single-phase distribution boards.
  • Industrial switchgear and control panels.
  • Commercial electrical installations.
  • Building management systems.
  • Automation and PLC control cabinets.
  • Protection of drives, power supplies and sensitive electronic equipment.

Technical Specifications

Tick the specs you need, then view products that match.

Voltage 230 V
Poles 2-pole
Device Type Surge protection device
SPD Type Type 2
Earthing System TN-S
Nominal Discharge Current (In) 20 kA
Remote Signal No
Manufacturer Mersen
Series Surge-Trap K2
Model K2-2P275
SKU / Part number 44020202
Product type Surge protection device
IEC SPD classification Type 2 / Class II
UL SPD classification Type 1 Component Assembly
Internal configuration 2+0
Number of poles 2
System compatibility TN-S
Protection mode L-N
Nominal operating voltage 230 V AC
Maximum continuous operating voltage 275 V AC
Nominal discharge current 20 kA
Maximum discharge current 50 kA
Voltage protection level ≤1.5 kV
Maximum back-up fuse 315 A gG
Short-circuit withstand rating 25 kA
Protection rating IP20
Mounting type DIN rail
DIN rail modules 2
Dimensions (H × W × D) approx. 90 × 36 × 68.2 mm
Weight approx. 0.232 kg
EAN 8435297889779
HS Code 85363090
Country of Manufacture Spain

Frequently Asked Questions

What is the Mersen 44020202 used for?

The Mersen 44020202 protects single-phase TN-S electrical installations against transient overvoltages caused by lightning activity and electrical switching events.

What type of surge protection device is the K2-2P275?

It is a Type 2 / Class II surge protection device designed for secondary surge protection in TN-S low-voltage electrical systems.

What discharge current can the device handle?

The K2-2P275 is rated for a 20 kA nominal discharge current and a 50 kA maximum discharge current using the standard 8/20 µs surge waveform.

Can the protection cartridges be replaced?

Yes. The pluggable cartridge design allows the protection modules to be replaced without removing the complete DIN-rail base.

Where is the device typically installed?

The device is typically installed in distribution boards, switchgear assemblies and industrial control panels to provide secondary surge protection for sensitive electrical equipment.

Trusted Surge Protection from Mersen

Mersen Surge-Trap K2 surge protection devices are trusted by electrical engineers, panel builders and maintenance professionals to protect critical electrical systems against damaging transient overvoltages.