K2-1P275-M Mersen Surge Protector Type 2 SPD 1 Pole 230 Volt 20KA L-N Remote Indication

K2-1P275-M Mersen Surge Protector Type 2 SPD 1 Pole 230 Volt 20KA L-N Remote Indication

Mersen K2-1P275-M Type 2 surge protection device with integrated remote signalling, 275 V AC operating voltage, 50 kA maximum discharge current and pluggable DIN rail mounting for 230 V AC single-phase electrical systems.

SKU: 44020103Alt SKU: K2-1P275-MMPN: 44020103
Price
List Price £42.12 ex VAT
Your Price (ex VAT) Save 25%
£31.59 25% OFF
You save £10.53 per unit
Manufacturer Lead Time Please contact us for a delivery time before you order
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £31.59
Trade pricing is personalised to your account

Manufacturer Lead Time

£31.59

Why Choose the Mersen 44020103 K2-1P275-M Surge Protection Device?

The Mersen 44020103 K2-1P275-M is a high-performance Type 2 Surge Protection Device (SPD) engineered to protect single-phase low-voltage electrical installations from transient overvoltages caused by switching operations and indirect lightning activity. As part of the proven Mersen Surge-Trap® K - K2 Series, this pluggable SPD combines dependable surge protection with an integrated remote signalling contact, making it ideal for industrial, commercial and critical electrical installations.

Designed for installation within distribution boards, the K2-1P275-M features a compact DIN rail mounted housing with replaceable pluggable protection cartridges. Its integrated microswitch enables remote monitoring of the device status, allowing maintenance personnel to receive fault notifications without opening the enclosure, helping to minimise downtime and simplify preventative maintenance.

With a 275 V AC maximum continuous operating voltage (Uc), a 50 kA maximum discharge current (Imax) and a 20 kA nominal discharge current (In), the K2-1P275-M delivers dependable protection for 230 V AC single-phase L-N electrical systems.

Key Advantages

  • Reliable Type 2 surge protection for single-phase electrical installations.
  • Integrated remote signalling microswitch for continuous status monitoring.
  • High 50 kA maximum discharge current (Imax).
  • Pluggable cartridge design for fast servicing and replacement.
  • Compact DIN rail mounted construction saves valuable panel space.
  • Protects sensitive electrical equipment from transient overvoltages and switching surges.

Key Features

  • Mersen Surge-Trap® K - K2 Series.
  • IEC Class II / Type 2 surge protection device.
  • 275 V AC maximum continuous operating voltage (Uc).
  • 50 kA maximum discharge current (Imax).
  • 20 kA nominal discharge current (In).
  • Single-pole (1P) L-N protection.
  • Integrated remote indication microswitch.
  • Green (OK) / Not Green (Replace) visual status indicator.
  • Pluggable modular cartridge.
  • DIN rail mounted.

Reliable Protection Against Transient Overvoltages

The Mersen K2-1P275-M safely diverts transient surge currents away from connected electrical equipment before they can damage consumer units, control panels, PLCs, automation systems and other sensitive electronic devices. This helps reduce costly downtime, minimise maintenance requirements and extend the operational life of connected equipment.

Its combination of high discharge capacity, integrated remote monitoring and modular pluggable construction makes it an ideal solution for residential, commercial and industrial installations where reliable secondary surge protection is essential.

Typical Applications

  • Single-phase distribution boards.
  • Residential consumer units.
  • Commercial electrical installations.
  • Industrial control panels.
  • Building management systems.
  • Automation equipment.
  • Sensitive electronic equipment.
  • 230 V AC L-N power distribution systems.

Technical Specifications

Tick the specs you need, then view products that match.

SPD Type Type 2
Voltage 230 V
Phase Single Phase
Device Type Surge protection device
Earthing System TN-C, TN-S, TT
Nominal Discharge Current (In) 20 kA
Remote Signal Yes
Manufacturer Mersen
Series Surge-Trap® K - K2 Series
Model K2-1P275-M
Part Number 44020103
EAN 8435297889663
Product type Type 2 Surge Protection Device (SPD)
IEC SPD Type Class II
UL SPD Type Type 1 Component Assembly
Maximum continuous operating voltage (Uc) 275 V AC
Nominal operating voltage (Un) 230 V AC
Maximum discharge current (Imax) 50 kA (8/20 μs)
Nominal Discharge Current (In) 20 kA (8/20 μs)
Protection level (Up) ≤1.5 kV
Configuration TN-S, TN-C, TT
Network compatibility TNS, TNC, TT (L-N only)
Short-circuit withstand (ISCCR) 25 kA
Maximum back-up fuse 315 A gG
Response time ≤25 ns
Remote indication Integrated microswitch
Mounting type DIN rail
Format Pluggable
Protection rating IP20
Operating temperature -40°C to +80°C
Housing material PA6 CT1 & PA66 CT1
Dimensions (H × W × D) Approx. 90 × 18 × 90 mm
RoHS compliant Yes
HS Code 85363090
Country of Manufacture Spain

Frequently Asked Questions

What is the Mersen 44020103 K2-1P275-M used for?

It provides Type 2 surge protection for single-phase electrical installations against transient overvoltages caused by switching events and indirect lightning activity.

Does this model include remote monitoring?

Yes. The K2-1P275-M includes an integrated microswitch that enables remote indication of the surge protection device status.

Which electrical systems is this SPD suitable for?

The K2-1P275-M is designed for 230 V AC TNS, TNC and TT (L-N only) electrical systems.

What discharge current ratings does the device provide?

The device provides a 50 kA maximum discharge current (Imax) and a 20 kA nominal discharge current (In).

How is the K2-1P275-M installed?

The surge protection device mounts directly onto a standard DIN rail and features a replaceable pluggable cartridge for fast servicing and maintenance.

Trusted Protection for Modern Electrical Installations

Mersen Surge-Trap® K Series surge protection devices are trusted by electricians, panel builders and electrical engineers worldwide to protect low-voltage electrical systems from damaging transient overvoltages.