Finder 7P.62.9.009.0485 is an ultra-slim Type 2+3 RS485 data line surge protection device featuring 8.5 V DC maximum continuous operating voltage, 5 kA nominal discharge current, core-to-core and core-to-earth protection, shield continuity and 7 mm DIN rail construction.
£55.25
The Finder 7P.62.9.009.0485 is a compact Type 2+3 surge protection device (SPD) specifically designed to protect RS485 communication networks, two-wire data lines and low-voltage signalling interfaces against transient overvoltages. Part of the Finder 7P Series, this specialised surge arrester combines coarse and fine surge suppression to help protect sensitive industrial communication equipment from lightning-induced disturbances and electrical switching transients.
Featuring a 6 V DC nominal voltage, an 8.5 V DC maximum continuous operating voltage (Uc) and a 5 kA nominal discharge current (In), the Finder 7P.62.9.009.0485 provides targeted protection for compatible RS485 data interfaces. Its protection arrangement addresses both longitudinal overvoltages (core-to-earth) and transverse overvoltages (core-to-core), helping reduce the risk of damage to communication transceivers, PLC interfaces, energy meters and industrial monitoring equipment.
With an ultra-slim 7 mm housing width, standard DIN rail mounting and an operating temperature range of −40 to +70 °C, the device is particularly suitable for space-constrained industrial control cabinets. Its serial connection arrangement also supports continuity of the communication cable shield, making it a practical solution for protecting two-wire RS485 networks without unnecessarily complicating the installation.
RS485 communication networks are widely used in industrial automation, energy monitoring, building management and remote control systems. These networks often connect equipment across long cable runs, between separate cabinets or through electrically noisy industrial environments. Lightning-induced disturbances, switching operations and differences in electrical potential can produce transient overvoltages that threaten sensitive communication interfaces.
The Finder 7P.62.9.009.0485 addresses these risks through a combination of coarse and fine surge suppression. Its protection arrangement is designed to limit both differential surges between the two data conductors and common-mode surges between the conductors and protective earth. This dual-mode protection is particularly valuable for RS485 transceivers, where excessive voltage can damage communication circuitry or cause network interruptions.
The device has a 5 kA C2 nominal discharge current for core-to-core protection and a 10 kA total discharge current for the cores-to-earth path. Its specified voltage protection levels of 18 V core-to-core and 30 V core-to-earth under C2 testing help define the residual voltage presented during standardised surge conditions. The additional C3 performance characteristics support fine protection of sensitive communication electronics.
Unlike conventional mains surge protection devices, this model is designed specifically for low-voltage data signals. Its 8.5 V DC maximum continuous operating voltage and 0.5 A nominal load current must be compatible with the connected interface. The specified 1.6 Ω series resistance per conductor and signal frequency characteristics should also be considered when designing communication networks, particularly where long cable runs or higher data rates are involved.
The ultra-slim 7 mm DIN rail housing makes the device suitable for installation in densely populated control cabinets, while the provision for cable shield continuity supports correct treatment of shielded communication wiring. For effective protection, the device should be installed with suitable earthing, appropriate cable routing and connection methods in accordance with Finder's technical documentation and relevant electrical installation standards.
| Manufacturer | Finder |
|---|---|
| Series | 7P Series |
| Product family | 7P.62 |
| Model | 7P.62.9.009.0485 |
| Manufacturer part number | 7P.62.9.009.0485 |
| Alternative reference | 7P6290090485 |
| Product type | Data and signal line surge protection device |
| SPD classification | Type 2+3 |
| Protected interface | RS485 |
| Number of protected signal conductors | 2 |
| Protection modes | Core-to-core and core-to-earth |
| Nominal voltage (Un) | 6 V DC |
| Maximum continuous operating voltage (Uc) | 8.5 V DC |
| Nominal load current (IL) | 0.5 A |
| C2 nominal discharge current (In, 8/20 µs), core-to-core | 5 kA |
| C2 total discharge current (8/20 µs), cores-to-earth | 10 kA |
| C2 voltage protection level (Up), core-to-core | 18 V |
| C2 voltage protection level (Up), core-to-earth | 30 V |
| C3 voltage protection level (Up), core-to-core at 1 kV/µs | 12 V |
| C3 voltage protection level (Up), core-to-earth at 1 kV/µs | 15 V |
| Response time, core-to-core | 1 ns |
| Response time, core-to-earth | 1 ns |
| Serial resistance per core | 1.6 Ω |
| Threshold frequency, core-to-core | 1 MHz |
| Connection arrangement | Serial, with shield continuity |
| Mounting | 35 mm DIN rail |
| Housing width | 7 mm |
| Housing height | 91 mm |
| Housing depth | 58 mm |
| Maximum solid conductor cross-section | 4 mm² |
| Maximum stranded conductor cross-section | 2.5 mm² |
| Ingress protection | IP20 |
| Operating temperature | −40 to +70 °C |
| Applicable standard | EN 61643-21 / IEC 61643-21 |
| Net weight | Approximately 34.06 g |
| EAN | 8012823413341 |
| Country of origin | Czech Republic |
The Finder 7P.62.9.009.0485 is a Type 2+3 surge protection device designed to protect RS485 communication networks, two-wire data lines and compatible low-voltage signalling interfaces against transient overvoltages.
Yes. This model is specifically designed for RS485 data line protection, including compatible interfaces on PLCs, solar inverters, energy meters and industrial monitoring equipment.
The Finder 7P.62.9.009.0485 has a maximum continuous operating voltage (Uc) of 8.5 V DC and a nominal voltage of 6 V DC.
The device has a C2 nominal discharge current of 5 kA for core-to-core protection using the 8/20 µs surge waveform. Its specified total cores-to-earth discharge current is 10 kA.
The Type 2+3 designation describes a combination of coarse and fine surge suppression for data and signal circuits. The device provides protection against transient overvoltages affecting both the signal conductors and their relationship to protective earth.
Yes. The Finder 7P.62.9.009.0485 provides core-to-core protection against differential-mode surges and core-to-earth protection against common-mode surges.
Under C2 testing, the specified voltage protection levels are 18 V core-to-core and 30 V core-to-earth. Under C3 testing, the corresponding values are 12 V and 15 V.
The device has a nominal load current of 0.5 A. The connected communication circuit must operate within this limit and the specified voltage characteristics.
No. This is a specialised low-voltage data line surge protector with an 8.5 V DC maximum continuous operating voltage. It is not intended to replace an AC mains surge protection device.
The device has an ultra-slim housing width of approximately 7 mm, making it suitable for compact DIN rail control panel installations.
The Finder 7P.62.9.009.0485 mounts on a standard 35 mm DIN rail and is connected in series with the protected two-wire communication line. The installation arrangement supports continuity of the cable shield.
The 7P.62.9.009.0485 is intended for compatible RS485 communication circuits with an 8.5 V DC maximum operating voltage, while the 7P.62.9.036.0005 is designed for compatible higher-voltage signalling applications with a 36 V DC maximum operating voltage, including fire detection and telecommunications circuits.
The specified operating temperature range is −40 to +70 °C, making the device suitable for a wide range of protected industrial and commercial electrical environments.
The device is designed in accordance with EN 61643-21 and IEC 61643-21 requirements for surge protection devices connected to telecommunications and signalling networks, including relevant C2 and C3 test classifications.
Check the communication interface voltage, normal signal levels, nominal load current, operating frequency, cable shield arrangement, protective earthing and the manufacturer's wiring instructions to ensure compatibility with the protected network.
Finder 7P Series data line surge protection devices provide specialised solutions for protecting sensitive industrial communication interfaces against transient overvoltages. Combining Type 2+3 coarse and fine suppression, 5 kA nominal discharge current, low-voltage RS485 compatibility and an ultra-slim 7 mm DIN rail housing, the Finder 7P.62.9.009.0485 supports dependable communication network protection in industrial automation, energy monitoring and building management installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.