Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 7P.23.9.750.1020 is a three-pole Type 2 photovoltaic DC surge protection device rated for 750 V DC systems, featuring three replaceable varistor modules, 20 kA nominal discharge current, 40 kA maximum discharge current, optical status indication and an SPDT remote signalling contact.
£106.07
The Finder 7P.23.9.750.1020 is a high-performance Type 2 photovoltaic DC surge protection device (SPD) designed to protect solar power installations against transient overvoltages caused by lightning-induced disturbances and electrical switching events. Part of the Finder 7P Series, this three-pole surge arrester incorporates three metal oxide varistor protection elements in a Y-connected arrangement and is specifically engineered for photovoltaic systems with a maximum continuous operating voltage of 750 V DC.
Featuring a 20 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax), the Finder 7P.23.9.750.1020 provides substantial surge-handling capability for photovoltaic DC circuits. Its Type 2 classification makes it suitable for protecting solar inverter DC inputs, photovoltaic string connections and DC distribution equipment against induced lightning surges and switching transients.
This version includes an integrated remote signalling changeover contact (SPDT), allowing the condition of the protective elements to be monitored through compatible alarm, PLC and supervisory systems. The device also features three replaceable varistor cartridges, local optical status indication and compact DIN rail construction. With IP20 protection, an operating temperature range of −40 to +80 °C and compatibility with standard 35 mm mounting rails, it provides a practical protection solution for commercial, industrial and renewable energy installations.
Photovoltaic installations are particularly vulnerable to transient electrical disturbances because solar panels and their associated DC cabling are frequently installed on rooftops, open ground and other exposed locations. Nearby lightning strikes can induce significant overvoltages in photovoltaic circuits, potentially damaging solar inverters, monitoring equipment and other connected components. The Finder 7P.23.9.750.1020 is designed to help manage these disturbances through its three-varistor Type 2 surge protection arrangement.
Its 750 V DC UCPV rating supports suitably designed photovoltaic installations, while the Y-connected protection configuration provides coordinated surge discharge paths between the relevant DC conductors and protective earth. The 20 kA nominal discharge current describes the device's performance under standardised 8/20 µs surge testing, while its 40 kA maximum discharge current provides additional surge-handling capability for high-amplitude transient events.
The integrated remote signalling changeover contact provides a significant maintenance advantage in installations where photovoltaic protection equipment is located in rooftop cabinets, inverter stations or remote distribution enclosures. By connecting the status output to a compatible PLC, alarm system or supervisory controller, maintenance personnel can receive information about the condition of the protective elements without relying solely on manual inspection. The local Healthy/Replace indicator provides an additional method for identifying when a varistor cartridge requires attention.
The replaceable varistor modules help simplify maintenance and reduce the need to replace complete surge protection assemblies. Correct installation remains essential: the photovoltaic array's maximum possible open-circuit voltage, including increases caused by low ambient temperatures, must remain within the manufacturer's specified limits. The SPD must also be coordinated with the installation's earthing arrangement, prospective short-circuit current, protective devices and conductor routing.
| Manufacturer | Finder |
|---|---|
| Series | 7P Series |
| Product family | 7P.23 |
| Model | 7P.23.9.750.1020 |
| Manufacturer part number | 7P.23.9.750.1020 |
| Product type | Photovoltaic DC surge protection device |
| SPD classification | Type 2 |
| Application | Photovoltaic DC installations |
| Maximum continuous PV operating voltage (UCPV) | 750 V DC |
| Number of poles | 3 |
| Protection configuration | Three-varistor Y connection |
| Protection technology | Metal oxide varistor |
| Nominal discharge current (In, 8/20 µs) | 20 kA |
| Maximum discharge current (Imax, 8/20 µs) | 40 kA |
| Remote signalling | Yes |
| Remote signalling contact | 1 changeover contact (SPDT) |
| Remote contact rating | 0.5 A AC / 0.1 A DC |
| Remote contact reference voltages | 250 V AC / 30 V DC |
| Remote signalling connector | Finder 07P.01, included |
| Local status indication | Optical Healthy/Replace indicator |
| Protective elements | Three replaceable varistor modules |
| Mounting | 35 mm DIN rail, EN 60715 |
| Modular width | 3 modules |
| Housing width | 53.8 mm |
| Housing height | 89.6 mm |
| Housing depth | 65.9 mm |
| Net weight | Approximately 316.6 g |
| Ingress protection | IP20 |
| Operating temperature | −40 to +80 °C |
| Maximum stated conductor cross-section | 25 mm² |
| Applicable standards | IEC/EN 61643-31 |
| EAN | 8012823376820 |
| Country of origin | Czech Republic |
The Finder 7P.23.9.750.1020 is a Type 2 photovoltaic DC surge protection device designed to help protect solar power installations against transient overvoltages caused by induced lightning surges and electrical switching events.
The device has a maximum continuous photovoltaic operating voltage (UCPV) of 750 V DC. The maximum possible photovoltaic array voltage, including temperature-related increases in open-circuit voltage, must remain within the manufacturer's specified operating limits.
It is a Type 2 surge protection device, intended primarily to protect against transient surges such as induced lightning disturbances and switching overvoltages. It does not replace Type 1 lightning-current protection where that classification is required.
The Finder 7P.23.9.750.1020 has a nominal discharge current (In) of 20 kA, tested using the standard 8/20 µs surge waveform.
The device has a maximum discharge current (Imax) of 40 kA, measured using the 8/20 µs surge waveform.
Yes. This model includes one SPDT changeover contact for remote indication of the varistor protection status. The contact can be connected to compatible alarm, PLC or monitoring equipment.
Yes. The remote-signalling version includes the compatible Finder 07P.01 connector for connection of the auxiliary status circuit.
Both models are three-pole Type 2 photovoltaic surge protectors rated for 750 V DC applications, with a 20 kA nominal discharge current. The 7P.23.9.750.1020 includes a remote signalling changeover contact, while the 7P.23.9.750.0020 is the corresponding version without remote signalling.
The Finder 7P.23.9.750.1020 incorporates three metal oxide varistor protection elements arranged in a Y-connected photovoltaic DC protection configuration.
Yes. The device uses replaceable varistor modules. Replacement should be carried out using the correct manufacturer-approved cartridges after the electrical installation has been safely isolated.
The optical indicator provides local information about the condition of the varistor protection elements. A Healthy indication identifies normal protective element condition, while a Replace indication identifies a cartridge requiring maintenance or replacement.
The Finder 7P.23.9.750.1020 is specifically designed for photovoltaic DC applications. It should not be substituted for an AC surge protection device unless Finder explicitly approves the intended application.
The device mounts on a standard 35 mm DIN rail inside a suitable electrical enclosure. Its three-module construction occupies approximately 53.8 mm of rail width.
The Finder 7P.23.9.750.1020 has an operating temperature range of −40 to +80 °C, supporting installation in appropriately protected photovoltaic electrical enclosures.
The Finder 7P.23.9.750.1020 is designed in accordance with IEC/EN 61643-31, the surge protection standard applicable to devices connected to photovoltaic DC installations.
Check the photovoltaic array's maximum open-circuit voltage, including cold-weather conditions, the required surge protection classification, earthing arrangements, prospective short-circuit current, conductor sizing, upstream protection requirements and Finder's installation instructions.
Finder 7P Series photovoltaic surge protection devices provide practical solutions for reducing the effects of transient overvoltages in solar generation systems. Combining Type 2 protection, 750 V DC photovoltaic compatibility, 20 kA nominal discharge current, replaceable varistor modules and remote condition signalling, the Finder 7P.23.9.750.1020 supports dependable protection and efficient maintenance of modern renewable energy installations.
We use cookies