Finder 7P.21.8.150.0015 - 7P Series Surge Protection Devices

Finder 7P.21.8.150.0015 – 7P Series Surge Protection Devices

Finder 7P.21.8.150.0015 is a single-pole DIN rail-mounted Type 2 surge protection device for compatible 120 V AC electrical systems, featuring 150 V AC maximum continuous operating voltage, 15 kA nominal discharge current, 40 kA maximum discharge current, 0.74 kV voltage protection level, replaceable varistor cartridge and visual protection status indication.

SKU: 7P.21.8.150.0015Alt SKU: 7P2181500015MPN: 7P.21.8.150.0015
Price
List Price £55.58 ex VAT
Your Price (ex VAT) Save 25%
£41.69 25% OFF
You save £13.90 per unit
Manufacturer Lead Time Standard Manufacturer Lead Time 6-8 Weeks, Call For Express Delivery Options
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £41.69
Trade pricing is personalised to your account

Manufacturer Lead Time

£41.69

Why Choose the Finder 7P.21.8.150.0015 Type 2 Surge Protection Device?

The Finder 7P.21.8.150.0015 is a compact, single-pole Type 2 surge protection device (SPD) designed to protect compatible low-voltage AC electrical installations against transient overvoltages. Part of the Finder Series 7P surge protection range, this DIN rail-mounted surge arrester uses metal oxide varistor technology to help safeguard industrial control equipment, electrical power supplies and sensitive electronic components against switching transients and induced lightning surges.

Designed for electrical systems with a nominal voltage of 120 V AC, the Finder 7P.21.8.150.0015 features a 150 V AC maximum continuous operating voltage (Uc), a 15 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax). Its 0.74 kV voltage protection level (Up) helps limit transient voltages reaching connected equipment when the SPD is correctly selected, installed and coordinated with the electrical system.

The device incorporates a replaceable varistor protection cartridge and a visual protection status indicator, allowing maintenance engineers to identify when the protective module requires replacement. Its compact 17.5 mm DIN rail format, IP20 protection rating and wide operating temperature range make it a practical solution for industrial automation panels, low-voltage distribution boards and electrical control cabinets.

Key Advantages

  • Type 2 surge protection helps protect electrical equipment against switching transients and induced lightning surges.
  • Single-pole configuration for compatible low-voltage AC installations.
  • 150 V AC maximum continuous operating voltage for correctly specified electrical systems.
  • 15 kA nominal discharge current provides robust surge-handling capability.
  • 40 kA maximum discharge current supports protection against higher-energy transient events.
  • 0.74 kV voltage protection level helps limit surge voltage reaching connected equipment.
  • Metal oxide varistor technology provides rapid response to transient overvoltages.
  • Replaceable varistor cartridge simplifies maintenance without requiring replacement of the complete SPD base.
  • Visual protection status indicator enables straightforward inspection of the protective element.
  • Compact 17.5 mm module width helps conserve space inside electrical enclosures.
  • 35 mm DIN rail mounting supports convenient installation in standard control panels.
  • −40 to +80 °C operating temperature range supports demanding industrial environments.
  • IP20 ingress protection rating for installation within suitable electrical distribution equipment.

Key Features

  • Finder Series 7P surge protection device.
  • 7P.21 single-pole Type 2 SPD configuration.
  • Metal oxide varistor (MOV) protection technology.
  • 120 V AC nominal system voltage.
  • 150 V AC maximum continuous operating voltage (Uc).
  • 15 kA nominal discharge current (In) using an 8/20 µs waveform.
  • 40 kA maximum discharge current (Imax) using an 8/20 µs waveform.
  • 0.74 kV voltage protection level (Up).
  • 0.6 kV protection level at 5 kA.
  • Replaceable varistor protection module.
  • Visual varistor status indication showing whether the protective element is serviceable or requires replacement.
  • No integrated remote signalling contact on the 7P.21.8.150.0015 version.
  • 35 mm DIN rail mounting in accordance with EN 60715.
  • 17.5 mm nominal module width.
  • IP20 protection rating.
  • −40 to +80 °C ambient operating temperature range.
  • Replaceable cartridge reference: Finder 7P.20.8.150.0015.
  • IEC/EN 61643-11 surge protection device classification.
  • Suitable for installation at the LPZ 1 / LPZ 2 boundary within a coordinated surge protection arrangement.

Reliable Type 2 Surge Protection for Industrial Electrical Systems

Industrial electrical installations can experience transient overvoltages caused by switching operations, inductive loads, power network disturbances and lightning-related events. These short-duration voltage surges may damage electronic components, interrupt automated processes and reduce the reliability of connected electrical equipment. Correctly selected Type 2 surge protection devices help limit these transient voltages and reduce the risk of equipment damage.

The Finder 7P.21.8.150.0015 is designed for compatible 120 V AC electrical systems and provides a 150 V AC maximum continuous operating voltage. This makes it suitable for designated low-voltage AC applications where the surge protection device must be matched to the operating voltage of the electrical supply.

The SPD uses metal oxide varistor technology, which becomes conductive during a transient overvoltage and diverts surge current through the intended protective path. With a 15 kA nominal discharge current, 40 kA maximum discharge current and 0.74 kV voltage protection level, the device offers defined surge-limiting characteristics for properly designed electrical installations.

A practical feature of the Finder 7P.21.8.150.0015 is its replaceable varistor cartridge. The integrated visual indicator enables maintenance personnel to identify whether the protective element remains serviceable or requires replacement. When necessary, the cartridge can be replaced with the designated Finder 7P.20.8.150.0015 module while retaining the existing SPD base, provided the base remains in suitable working condition.

The device mounts onto a standard 35 mm DIN rail and occupies approximately 17.5 mm of panel width. It is intended for installation as part of a coordinated surge protection arrangement, typically at the boundary between lightning protection zones LPZ 1 and LPZ 2. Correct selection of the SPD, upstream protective devices, earthing arrangement and connection lengths is essential for effective protection.

Typical Applications

  • Compatible 120 V AC electrical distribution systems.
  • Industrial automation and PLC control cabinets.
  • Electrical control panels and machine control systems.
  • Low-voltage AC power distribution boards.
  • Industrial instrumentation and monitoring equipment.
  • Electronic control power supplies.
  • Motor control and manufacturing equipment control panels.
  • Industrial machinery and process control installations.
  • Building services and electrical infrastructure.
  • Electrical installations exposed to induced lightning surges.
  • Equipment requiring protection against switching transients.
  • DIN rail-mounted surge protection in compact electrical enclosures.

Technical Specifications

Manufacturer Finder
Series 7P Surge Protection Devices
Model 7P.21.8.150.0015
Product type Type 2 surge protection device
SPD classification Type 2
Number of poles 1
Protection technology Metal oxide varistor (MOV)
Nominal system voltage (Un) 120 V AC
Maximum continuous operating voltage (Uc) 150 V AC
Nominal discharge current (In) 15 kA (8/20 µs)
Maximum discharge current (Imax) 40 kA (8/20 µs)
Voltage protection level (Up) 0.74 kV
Voltage protection level at 5 kA 0.6 kV
Response time 25 ns
Short-circuit current rating (Isccr) 50 kA, subject to specified installation conditions
Maximum associated backup fuse 160 A gL/gG, subject to manufacturer's coordination requirements
Protection element Replaceable varistor cartridge
Replacement cartridge Finder 7P.20.8.150.0015
Local status indication Visual varistor status indicator
Integrated remote signalling contact No
Remote signalling version Finder 7P.21.8.150.1015
Mounting method DIN rail
DIN rail size 35 mm
DIN rail standard EN 60715
Module width 17.5 mm nominal
Installation space 1 modular spacing unit
Ingress protection IP20
Operating temperature −40 to +80 °C
Applicable standard IEC/EN 61643-11
Typical installation location LPZ 1 / LPZ 2 boundary or higher protection zone
EAN / GTIN 8012823453576

Frequently Asked Questions

What is the Finder 7P.21.8.150.0015 used for?

The Finder 7P.21.8.150.0015 is a single-pole Type 2 surge protection device designed to protect compatible low-voltage AC electrical installations against transient overvoltages caused by electrical switching and induced lightning surges.

Is the Finder 7P.21.8.150.0015 a complete surge protection device?

Yes. The 7P.21.8.150.0015 is a complete DIN rail-mounted Type 2 surge protection device incorporating a replaceable varistor protection cartridge and a visual protection status indicator.

What is the maximum continuous operating voltage of this SPD?

The Finder 7P.21.8.150.0015 has a maximum continuous operating voltage (Uc) of 150 V AC and is designed for compatible electrical systems with a nominal voltage of 120 V AC.

What is the nominal discharge current of the Finder 7P.21.8.150.0015?

The device has a 15 kA nominal discharge current (In), measured using the standard 8/20 µs surge current waveform.

What is the maximum discharge current of this surge protector?

The Finder 7P.21.8.150.0015 has a 40 kA maximum discharge current (Imax), measured using an 8/20 µs surge waveform.

What is the voltage protection level of the Finder 7P.21.8.150.0015?

The SPD has a specified 0.74 kV voltage protection level (Up) and a protection level of approximately 0.6 kV at 5 kA, indicating its surge-limiting performance under the relevant test conditions.

Does the Finder 7P.21.8.150.0015 have a remote signalling contact?

No. The 7P.21.8.150.0015 does not include an integrated remote signalling contact. The alternative Finder 7P.21.8.150.1015 version is available with remote signalling capability.

Does this surge protection device have a visual status indicator?

Yes. The Finder 7P.21.8.150.0015 includes a visual varistor status indicator that allows maintenance personnel to determine whether the protection element remains serviceable or requires replacement.

Can the varistor cartridge be replaced without replacing the complete SPD?

Yes. The replaceable varistor module allows the protective cartridge to be changed while retaining the existing SPD base, provided the base remains serviceable. The designated replacement cartridge is Finder 7P.20.8.150.0015.

How is the Finder 7P.21.8.150.0015 installed?

The device mounts onto a standard 35 mm DIN rail in accordance with EN 60715. It occupies approximately 17.5 mm of DIN rail width and should be installed inside a suitable electrical enclosure.

Can the Finder 7P.21.8.150.0015 be used on a 230 V AC mains supply?

No. The Finder 7P.21.8.150.0015 has a maximum continuous operating voltage of 150 V AC and is not suitable for direct installation on a nominal 230 V AC mains supply. A correctly rated SPD must be selected for higher-voltage electrical systems.

What is the operating temperature range of this surge protection device?

The Finder 7P.21.8.150.0015 is designed for ambient operating temperatures from −40 to +80 °C, supporting use in a wide range of industrial electrical installations.

What is the difference between Type 1 and Type 2 surge protection?

A Type 1 SPD is tested for high-energy lightning impulse currents using a 10/350 µs waveform, while a Type 2 SPD is tested using an 8/20 µs surge waveform and is commonly used to protect against induced lightning surges and switching transients. The Finder 7P.21.8.150.0015 is a Type 2 device.

Where is the Finder 7P.21.8.150.0015 typically installed?

The device is typically installed in industrial control cabinets, compatible low-voltage AC distribution boards, automation panels and electrical equipment enclosures requiring single-pole Type 2 surge protection.

Trusted by Electrical Installation and Industrial Automation Professionals Worldwide

Finder Series 7P surge protection devices provide practical, modular solutions for protecting electrical installations against transient overvoltages. Combining established metal oxide varistor technology, replaceable protection cartridges and convenient visual status indication, the Finder 7P.21.8.150.0015 offers dependable Type 2 surge protection for compatible low-voltage AC industrial electrical systems.