Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Finder 7P.13.9.000.0006 is a Type 1+2 photovoltaic DC surge protection device rated for 1050 V DC maximum continuous operating voltage, with 12.5 kA lightning impulse current, 20 kA nominal discharge current, 40 kA maximum discharge current, visual status indication and replaceable modules.
£166.38
The Finder 7P.13.9.000.0006 is a Type 1+2 DC surge protection device (SPD) from the Finder 7P Series, designed to protect photovoltaic (PV) electrical installations against transient overvoltages associated with lightning activity and electrical switching events. Suitable for photovoltaic systems with a maximum continuous operating voltage of 1,050 V DC, this combined lightning and surge arrester provides protection for solar power generation equipment, PV distribution assemblies and associated DC electrical infrastructure.
Featuring a 12.5 kA lightning impulse current rating and a 20 kA nominal discharge current (8/20 µs), the Finder 7P.13.9.000.0006 combines Type 1 and Type 2 surge protection capabilities in a single assembly. Its Y-circuit varistor protection arrangement is designed for photovoltaic DC applications, helping limit potentially damaging overvoltages before they reach connected electrical equipment.
The device incorporates replaceable protection modules and visual status indication, allowing maintenance engineers to identify protective elements requiring attention. With a compact 72 mm DIN rail-mounted construction, IP20 ingress protection and a wide −40 to +80 °C operating temperature range, it is particularly suitable for photovoltaic combiner boxes, solar inverter DC protection assemblies and industrial renewable energy installations.
Photovoltaic installations can be exposed to transient overvoltages caused by direct or nearby lightning strikes, induced lightning currents and electrical switching disturbances. Because PV arrays often incorporate extensive outdoor cabling and exposed mounting structures, appropriate surge protection is an important consideration when designing reliable solar power generation systems.
The Finder 7P.13.9.000.0006 provides combined Type 1+2 surge protection for photovoltaic DC circuits. Type 1 functionality supports the handling of high-energy lightning impulse currents, while Type 2 functionality provides protection against induced surges and transient overvoltages that may otherwise damage downstream equipment.
Its 1,050 V DC maximum continuous operating voltage makes it suitable for appropriately specified photovoltaic installations. Engineers must verify that the maximum PV array open-circuit voltage, including temperature-dependent voltage increases, remains within the permitted SPD operating voltage.
The device uses a Y-circuit varistor arrangement intended for photovoltaic DC surge protection. This configuration helps limit transient overvoltages within the DC installation, reducing the electrical stress experienced by connected components such as solar inverters, monitoring equipment and DC distribution assemblies.
With a 12.5 kA lightning impulse current rating, a 20 kA nominal discharge current and a 40 kA maximum discharge current, the Finder 7P.13.9.000.0006 provides substantial surge handling capability for compatible installations. Effective protection nevertheless depends on correct system design, earthing, conductor routing, protective device coordination and installation position.
The visual status indicator allows maintenance personnel to check the condition of the protective modules during routine inspections. Its replaceable cartridge construction also supports maintenance without necessarily replacing the complete SPD assembly.
This particular .0006 variant does not incorporate a remote signalling contact. Where remote status monitoring is required, engineers should consider the appropriate Finder 7P photovoltaic SPD variant with auxiliary signalling, such as the corresponding 7P.13.9.000.1006.
Installation and replacement should be carried out by qualified personnel in accordance with Finder's instructions and the applicable photovoltaic electrical installation standards. The SPD must be installed inside a suitable enclosure providing the environmental protection required by the installation.
Tick the specs you need, then view products that match.
| Impulse Current Iimp (kA) | 12.5 kA | |
|---|---|---|
| Manufacturer | Finder | |
| Product series | 7P Series | |
| Manufacturer part number | 7P.13.9.000.0006 | |
| Product type | Photovoltaic DC surge protection device | |
| Surge protection classification | Type 1+2 | |
| Application | Photovoltaic DC systems | |
| Maximum continuous operating voltage (Ucpv) | 1,050 V DC | |
| Lightning impulse current (Iimp), 10/350 µs | 12.5 kA | |
| Nominal discharge current (In), 8/20 µs | 20 kA | |
| Maximum discharge current (Imax), 8/20 µs | 40 kA | |
| Voltage protection level | 3.8 kV | |
| Protection technology | Varistor | |
| Protection arrangement | Y-circuit configuration | |
| Number of protected conductors | 3 | |
| Local status indication | Visual indication | |
| Remote signalling contact | Not included | |
| Protection modules | Replaceable | |
| Mounting method | 35 mm DIN rail | |
| Mounting standard | EN 60715 | |
| Modular width | 72 mm | |
| Number of modular spaces | 4 | |
| Ingress protection | IP20 | |
| Ambient operating temperature | −40 to +80 °C | |
| Applicable standard | EN 61643-31 | |
| EAN | 8012823446158 | |
| Country of origin | Czechia |
The Finder 7P.13.9.000.0006 is a Type 1+2 photovoltaic DC surge protection device designed to protect solar power installations against transient overvoltages caused by lightning activity and electrical switching disturbances. It is suitable for compatible photovoltaic systems operating up to 1,050 V DC.
The device has a 1,050 V DC maximum continuous operating voltage, a 12.5 kA lightning impulse current rating (10/350 µs), a 20 kA nominal discharge current (8/20 µs) and a 40 kA maximum discharge current (8/20 µs).
Yes. The Finder 7P.13.9.000.0006 is specifically designed for photovoltaic DC surge protection and is intended for installation in appropriately designed PV electrical systems. Engineers should verify the maximum array voltage, earthing arrangement and surge protection requirements before installation.
No. The 7P.13.9.000.0006 includes local visual status indication but does not incorporate a remote signalling contact. For applications requiring remote SPD status monitoring, the corresponding 7P.13.9.000.1006 variant provides an alternative.
Yes. The device incorporates replaceable protection modules, allowing the relevant cartridge to be changed when its visual indicator shows that replacement is required. The complete assembly mounts onto a 35 mm DIN rail and occupies 72 mm of panel width. Replacement should be performed by qualified personnel following appropriate electrical isolation procedures.
The Finder 7P.13.9.000.0006 combines Type 1+2 photovoltaic surge protection, a 1,050 V DC maximum continuous operating voltage, 12.5 kA lightning impulse current capability, 20 kA nominal discharge current and replaceable protective modules in a compact DIN rail-mounted assembly, providing a practical surge protection solution for commercial, industrial and renewable energy photovoltaic installations.