Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 2TAM903100R4501 eOVR T2 3N 40-350 digital 3+1 Type 2 surge protective device for 230/400 V AC systems, with 40 kA Imax, 20 kA In, 350 V Uc, 1.5 kV Up and Modbus RS-485 monitoring.
£503.07
The ABB eOVR T2 3N 40-350 (2TAM903100R4501) is a digital Type 2 surge protective device (SPD) designed for three-phase electrical installations with neutral. Its 3+1 protection configuration provides coordinated transient overvoltage protection for 230/400 V AC systems, helping protect sensitive electrical and electronic equipment against surges generated by indirect lightning activity and switching events.
The eOVR T2 3N 40-350 provides a 40 kA maximum discharge current (Imax) and 20 kA nominal discharge current (In), both based on the 8/20 µs surge-current waveform. It has a maximum continuous operating voltage Uc of 350 V and a voltage protection level Up of 1.5 kV, making it suitable for Type 2 protection within low-voltage distribution systems.
ABB’s eOVR platform adds digital monitoring to conventional surge protection. The device can record 20 surge events and 10 SPD remote-signal status changes and provides Modbus RS-485 communication. Integration with ABB InSite Pro M and ABB Ability solutions supports remote visibility, maintenance planning and monitoring of surge protection status within connected electrical installations.
Type 2 SPDs are used within low-voltage installations to limit transient overvoltages and divert surge current before damaging voltage levels can reach downstream electrical and electronic equipment. They are particularly suited to protection against indirect lightning effects and switching transients and are commonly installed in main or sub-distribution boards according to the overall surge protection design.
The ABB eOVR T2 3N 40-350 combines this protective function with intelligent monitoring. Its 40 kA Imax, 20 kA In and 1.5 kV Up provide defined surge-protection performance, while event recording and Modbus RS-485 connectivity provide additional information for inspection, maintenance and connected electrical-management applications.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 3-pole + N | |
| Earthing System | TN-S, TT | |
| Series | eOVR | |
| Order code | 2TAM903100R4501 | |
| Product type | Digital Type 2 surge protective device | |
| Product group | Surge Protection Devices | |
| SPD classification | Type 2 | |
| Protection configuration | 3+1 | |
| Nominal system voltage (Un) | 230/400 V AC | |
| Maximum continuous operating voltage (Uc) | 350 V | |
| Maximum discharge current (Imax, 8/20 µs) | 40 kA | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Voltage protection level (Up) | 1.5 kV | |
| Event recording | 20 surge events and 10 SPD remote-signal status changes | |
| Communication | Modbus RS-485 | |
| Digital integration | ABB InSite Pro M / ABB Ability | |
| Mounting | DIN rail |
The ABB eOVR T2 3N 40-350 is a Type 2 digital surge protective device for three-phase systems with neutral, helping protect electrical equipment against transient overvoltages caused by indirect lightning and switching events.
It has a maximum discharge current Imax of 40 kA and a nominal discharge current In of 20 kA, specified using an 8/20 µs waveform.
The device is designed for a nominal 230/400 V AC system and has a maximum continuous operating voltage Uc of 350 V.
The 3N version provides a 3+1 protection configuration intended for three-phase electrical systems incorporating a neutral conductor.
Yes. It can record 20 surge events and 10 SPD remote-signal status changes and supports Modbus RS-485 communication for integration with ABB InSite Pro M and ABB Ability solutions.
ABB eOVR digital surge protective devices combine transient overvoltage protection with event recording and connected monitoring, with the eOVR T2 3N 40-350 providing 3+1 Type 2 protection for 230/400 V AC three-phase systems with neutral.
We use cookies