ABB OVR T1-T2 1N 12.5-440s P TS QS is a combined Type 1 and Type 2 pluggable surge protective device for 1L+1N TT and TN-S systems, with 440 V AC maximum continuous operating voltage, 12.5 kA impulse current, 80 kA maximum discharge current and remote signalling.
£436.04
The ABB OVR T1-T2 1N 12.5-440s P TS QS, order code 2CTB815710R3000, is a combined Type 1 and Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations against lightning currents and transient overvoltages. Part of the ABB OVR QuickSafe range, it provides coordinated lightning and surge protection for single-phase plus neutral systems and is suitable for integration with ABB System pro M compact installations.
The 1N configuration is designed for 1L+1N networks and is suitable for TT and TN-S systems. The device combines high-energy lightning-current handling with protection against lower-energy switching and indirect-lightning surges. Its pluggable construction simplifies maintenance, while the TS potential-free changeover contact enables remote monitoring of the surge protector's operating condition.
With a nominal system voltage of 400 V AC, maximum continuous operating voltage (Uc) of 440 V AC, 12.5 kA impulse current (Iimp) and 80 kA maximum discharge current (Imax), the OVR T1-T2 1N 12.5-440s P TS QS provides substantial surge-handling capability. Its 1.9 kV voltage protection level (Up) helps limit transient voltage reaching downstream electrical and electronic equipment.
Type 1 surge protective devices are designed to discharge high-energy lightning currents entering an electrical installation, while Type 2 protection limits lower-energy transient overvoltages generated by indirect lightning effects and electrical switching. The ABB OVR T1-T2 1N 12.5-440s P TS QS combines both functions to provide coordinated protection for appropriate single-phase plus neutral distribution systems.
ABB QuickSafe technology adds practical maintenance benefits to this protection. The Safety Reserve design maintains a basic level of surge protection when the main protection element reaches end of life, giving maintenance personnel an opportunity to replace the affected cartridge. The integrated TS contact also allows SPD status to be incorporated into remote monitoring and building or industrial control systems.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Poles | 1-pole + N | |
| Earthing System | TN-S, TT | |
| Impulse Current Iimp (kA) | 12.5 kA | |
| Series | OVR T1-T2 QuickSafe | |
| ABB order code | 2CTB815710R3000 | |
| Product type | Combined lightning-current and surge protective device (SPD) | |
| SPD classification | Type 1 + Type 2 | |
| Configuration | 1N / 1L+1N | |
| Number of poles | 2 | |
| Network systems | TT, TN-S | |
| Nominal system voltage (Un) | 400 V AC | |
| Maximum continuous operating voltage (Uc) | 440 V AC | |
| Impulse current (Iimp, 10/350 µs) | 12.5 kA | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 80 kA | |
| Voltage protection level (Up) | 1.9 kV | |
| Remote signalling | Yes, TS potential-free changeover contact | |
| Safety Reserve | Yes | |
| Protection modules | Pluggable / replaceable | |
| Protection rating | IP20 | |
| Mounting type | DIN rail | |
| Width | 53.4 mm | |
| Height | 95.8 mm | |
| Depth | 76.7 mm | |
| Weight | approx. 0.45 kg | |
| Standard | EN / IEC 61643-11 | |
| EAN | 3660308525062 | |
| ABB product group | Surge Protection Devices |
It is a combined Type 1 and Type 2 surge protective device designed to protect appropriate single-phase plus neutral low-voltage electrical installations against lightning currents and transient overvoltages.
The device has a 12.5 kA impulse current (Iimp) for a 10/350 µs waveform, a 20 kA nominal discharge current (In) and an 80 kA maximum discharge current (Imax) for 8/20 µs surge currents.
The OVR T1-T2 1N 12.5-440s P TS QS has a maximum continuous operating voltage (Uc) of 440 V AC and a nominal system voltage of 400 V AC.
Yes. The TS version includes a potential-free changeover contact that allows the operating condition of the surge protective device to be monitored remotely.
The 1N / 1L+1N configuration is designed for appropriate TT and TN-S systems, providing combined Type 1 and Type 2 protection for the phase and neutral arrangement.