ABB OVR T1-T2 12.5-275s C QS 2CTB815710R2600 is a single-pole replacement cartridge for compatible QuickSafe Type 1 + Type 2 surge protective devices with 12.5 kA impulse current, 80 kA maximum discharge current and 275 V AC maximum continuous operating voltage.
£69.59
The ABB OVR T1-T2 12.5-275s C QS is a high-performance replacement surge protection cartridge for compatible ABB OVR QuickSafe combined Type 1 + Type 2 surge protective devices. Identified by ABB order code 2CTB815710R2600, this single-pole cartridge is designed to restore lightning-current and transient-overvoltage protection without replacing the complete installed SPD assembly.
As part of the ABB OVR QuickSafe range, the cartridge provides combined Type 1 and Type 2 protection, with a 12.5 kA impulse current rating using a 10/350 µs waveform, a 20 kA nominal discharge current and an 80 kA maximum discharge current. Its mechanical status indication enables straightforward inspection of the protection element during routine electrical maintenance.
With a 230/400 V AC nominal system voltage, 275 V AC maximum continuous operating voltage and 1.4 kV voltage protection level, the OVR T1-T2 12.5-275s C QS is suitable for compatible ABB surge protection assemblies used on TN-C, TN-S and TT low-voltage distribution systems. The plug-in design enables rapid cartridge replacement while retaining the installed DIN-rail base and associated wiring.
Combined Type 1 + Type 2 surge protection is designed to handle both high-energy lightning currents characterised by a 10/350 µs waveform and transient surge currents characterised by an 8/20 µs waveform. The ABB OVR T1-T2 12.5-275s C QS provides the replaceable phase protection element for compatible OVR QuickSafe assemblies, helping restore their protective capability when an existing cartridge reaches the end of its service life.
The plug-in cartridge format allows maintenance personnel to replace the active protection module while retaining the existing SPD base and electrical connections. This helps reduce servicing time and avoids unnecessary rewiring, while the mechanical condition indicator provides an immediate visual indication of cartridge status.
Tick the specs you need, then view products that match.
| Device Type | Replacement cartridge | |
|---|---|---|
| Impulse Current Iimp (kA) | 12.5 kA | |
| Series | OVR QuickSafe | |
| ABB order code | 2CTB815710R2600 | |
| EAN | 3660308525031 | |
| Product group | Surge Protection Devices | |
| Product type | Replacement surge protection cartridge | |
| SPD classification | Type 1 + Type 2 / Class I + II | |
| Number of poles | 1 | |
| Compatible distribution systems | TN-C / TN-S / TT | |
| Nominal system voltage | 230 / 400 V AC | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Temporary overvoltage test value (UT) | 337 V | |
| Impulse current (Iimp, 10/350 µs) | 12.5 kA | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 80 kA | |
| Voltage protection level (Up L-N) | 1.4 kV | |
| Voltage protection level (Up L-PE) | 1.4 kV | |
| Short-circuit withstand | 100 kA | |
| Status indication | Mechanical | |
| Remote signalling | No | |
| Construction | Plug-in replacement cartridge | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Dimensions (H × W × D) | approx. 57 × 17.6 × 67 mm | |
| Standards | IEC 61643-11 / EN 61643-11 |
It is a single-pole replacement cartridge for compatible ABB OVR QuickSafe Type 1 + Type 2 surge protective devices, providing combined lightning-current and transient-overvoltage protection.
The cartridge has an impulse current rating of 12.5 kA using a 10/350 µs waveform for Type 1 lightning-current protection.
The cartridge has a 20 kA nominal discharge current and an 80 kA maximum discharge current using an 8/20 µs waveform.
It is designed for compatible 230/400 V AC systems and has a maximum continuous operating voltage of 275 V AC.
Yes. It is a plug-in replacement cartridge, allowing the active protection module to be renewed in a compatible ABB OVR QuickSafe assembly while retaining the installed base and wiring.
ABB OVR QuickSafe replacement cartridges provide a practical way to maintain combined lightning-current and transient-overvoltage protection, combining high surge capability, mechanical status indication and convenient plug-in replacement.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.