ABB OVR T1-T2 3N 12.5-275s P TS QS 2CTB815710R0700 is a four-line pluggable Type 1 + Type 2 surge protective device for 230/400 V AC TT and TN-S systems with 12.5 kA impulse current per pole, 80 kA maximum discharge current and remote signalling.
£260.99
The ABB OVR T1-T2 3N 12.5-275s P TS QS is a high-performance combined Type 1 + Type 2 surge protective device (SPD) designed to protect three-phase low-voltage electrical installations against lightning currents and transient overvoltages. Identified by ABB order code 2CTB815710R0700, it forms part of the ABB OVR QuickSafe surge protection range and combines lightning-current protection with low residual voltage protection in a single DIN-rail-mounted assembly.
Designed for 3L+N TT and TN-S electrical systems, this four-line SPD provides an impulse current rating of 12.5 kA per pole using a 10/350 µs waveform, together with an 80 kA maximum discharge current and 20 kA nominal discharge current. ABB's patented QuickSafe technology, integrated thermal disconnection and Safety Reserve system provide dependable operation while supporting preventive maintenance and reduced downtime.
The OVR T1-T2 3N 12.5-275s P TS QS is designed for 230/400 V AC systems with a 275 V AC maximum continuous operating voltage on L-N. Its pluggable construction simplifies servicing, while the TS auxiliary signalling contact enables remote monitoring of surge-protection status in industrial, commercial and building distribution systems.
Combined Type 1 + Type 2 SPDs are designed to handle both high-energy lightning currents with a 10/350 µs waveform and transient surge currents with an 8/20 µs waveform. The ABB OVR T1-T2 3N 12.5-275s P TS QS can therefore provide coordinated lightning and overvoltage protection at the main distribution level while maintaining a low residual voltage for downstream electrical equipment.
ABB's patented QuickSafe technology incorporates thermal disconnection, end-of-life indication and the Safety Reserve system. Combined with pluggable cartridges and remote TS signalling, these features simplify condition monitoring and maintenance while helping minimise interruption to protected industrial and commercial installations.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Poles | 3-pole + N | |
| Earthing System | TN-S, TT | |
| Impulse Current Iimp (kA) | 12.5 kA | |
| Series | OVR QuickSafe | |
| ABB order code | 2CTB815710R0700 | |
| EAN | 3660308524928 | |
| Product group | Surge Protection Devices | |
| Product type | Combined Type 1 + Type 2 surge protective device | |
| Test class | Class I + II | |
| Number of poles | 4 | |
| Number of protected lines | 4 | |
| Protection modes | L-N / L-PE / N-PE | |
| Low-voltage distribution systems | TT / TN-S | |
| Nominal system voltage | 230 / 400 V AC | |
| Maximum continuous operating voltage (L-N) | 275 V AC | |
| Maximum continuous operating voltage (L-PE) | 275 V AC | |
| Maximum continuous operating voltage (N-PE) | 255 V AC | |
| Frequency | 47–63 Hz | |
| Impulse current (Iimp, 10/350 µs) | 12.5 kA | |
| Total impulse current (10/350 µs) | 50 kA | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 80 kA | |
| Total discharge current | 100 kA | |
| Voltage protection level (Up L-N) | 1.2 kV | |
| Voltage protection level (Up L-PE) | 1.35 kV | |
| Voltage protection level (Up N-PE) | 1.1 kV | |
| Short-circuit withstand (ISCCR) | 100 kA | |
| Response time | <25 ns | |
| Integrated thermal disconnector | Yes | |
| End-of-life indicator | Yes | |
| Safety Reserve | Yes | |
| Preventive maintenance function | Yes | |
| Remote signalling | Yes | |
| Auxiliary contacts | 1 NO + 1 NC | |
| Maximum backup circuit breaker | 125 A, curve B or C | |
| Maximum backup fuse | 160 A gG / gL | |
| Mounting | DIN rail | |
| Construction | Pluggable | |
| Protection rating | IP20 | |
| Solid conductor range | 2.5–35 mm² | |
| Stranded conductor range | 2.5–25 mm² | |
| Stripping length | 12.5 mm | |
| Dimensions (H × W × D) | approx. 95 × 71.2 × 69.4 mm | |
| Weight | approx. 600 g | |
| Maximum installation altitude | 2,000 m | |
| Fire resistance | UL 94 V-0 | |
| Standards | IEC 61643-11 / EN 61643-11 |
It is a combined Type 1 + Type 2 surge protective device designed to protect three-phase TT and TN-S electrical installations against lightning currents and transient overvoltages.
The device has an impulse current rating of 12.5 kA per pole using a 10/350 µs waveform, with a total impulse current capability of 50 kA.
The OVR T1-T2 3N 12.5-275s P TS QS has a maximum discharge current Imax of 80 kA using an 8/20 µs waveform and a nominal discharge current of 20 kA.
Yes. The TS version provides auxiliary NO and NC contacts for remote monitoring of the surge protective device's operating condition.
It is designed for DIN-rail installation in main distribution switchboards and suitable sub-distribution boards, particularly in three-phase TT and TN-S electrical systems requiring combined lightning-current and surge protection.
ABB OVR Type 1 + Type 2 surge protective devices combine lightning-current handling, low residual voltage, QuickSafe technology, Safety Reserve functionality and practical remote monitoring to provide dependable protection for modern electrical distribution systems.