ABB OVR T1-T2 12.5-275s P TS QS is a combined Type 1+2 surge protective device for 230 / 400 V AC installations with 275 V AC maximum continuous operating voltage, 12.5 kA impulse current, 20 kA nominal discharge current, 80 kA maximum discharge current and auxiliary status signalling.
£149.18
The ABB OVR T1-T2 12.5-275s P TS QS is a high-performance combined Type 1+2 surge protective device (SPD) designed to protect low-voltage electrical installations against lightning currents and transient overvoltages. As part of the advanced ABB OVR QuickSafe surge protection range, it combines Type 1 lightning current protection and Type 2 surge protection within a compact single-pole device for industrial and commercial electrical installations.
Designed for TT, TN-C and TN-S distribution systems, the OVR T1-T2 12.5-275s P TS QS provides coordinated protection against direct lightning effects, induced surges and switching overvoltages. Its pluggable construction simplifies maintenance, while the integrated status indication and auxiliary signalling contact enable convenient monitoring of the SPD's operating condition.
With an impulse current (Iimp) of 12.5 kA using a 10/350 µs waveform, maximum discharge current (Imax) of 80 kA, nominal discharge current (In) of 20 kA and 275 V AC maximum continuous operating voltage, the OVR T1-T2 12.5-275s P TS QS provides robust protection for 230 / 400 V AC installations. The device is supplied under ABB order code 2CTB815710R0000.
Combined Type 1+2 surge protective devices provide protection against both high-energy lightning currents and lower-energy transient overvoltages. Type 1 capability allows the SPD to discharge lightning impulse currents with a 10/350 µs waveform, while Type 2 performance limits transient surges characterised by an 8/20 µs waveform, helping protect downstream electrical and electronic equipment.
The ABB OVR T1-T2 QuickSafe range is designed for coordinated protection of low-voltage installations. The OVR T1-T2 12.5-275s P TS QS combines high discharge capability, pluggable construction, visual status indication and auxiliary remote signalling in a compact DIN-rail device suitable for TT, TN-C and TN-S distribution systems.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Impulse Current Iimp (kA) | 12.5 kA | |
| Series | OVR T1-T2 QuickSafe | |
| ABB order code | 2CTB815710R0000 | |
| Product group | Surge Protection Devices | |
| Product type | Combined Type 1+2 surge protective device | |
| Test class | Type 1 + Type 2 | |
| Number of poles | 1 | |
| Number of protected lines | 1 | |
| Distribution systems | TT, TN-C, TN-S | |
| Nominal system voltage | 230 / 400 V AC | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Impulse current Iimp (10/350 µs) | 12.5 kA | |
| Nominal discharge current In (8/20 µs) | 20 kA | |
| Maximum discharge current Imax (8/20 µs) | 80 kA | |
| Total maximum discharge current | 80 kA | |
| Voltage protection level Up at In | 1.4 kV | |
| Short-circuit withstand capability (Icc) | 100 kA | |
| Auxiliary contacts | 1 NO + 1 NC | |
| Status indicator | Yes | |
| Preventive maintenance function | Yes | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Protection rating | IP20 | |
| Power loss | 37 mW | |
| Maximum operating altitude | 5,000 m | |
| Mounting type | DIN rail | |
| Module width | 1 modular step | |
| Dimensions (H × W × D) | 95.8 × 17.8 × 76.7 mm | |
| Weight | approx. 0.15 kg |
This device provides combined Type 1+2 lightning current and surge protection for low-voltage electrical installations, helping protect downstream equipment against lightning effects and transient overvoltages.
The device has an impulse current Iimp of 12.5 kA using a 10/350 µs waveform, together with a maximum discharge current Imax of 80 kA.
The ABB OVR T1-T2 12.5-275s P TS QS has a maximum continuous operating voltage Uc of 275 V AC and is designed for nominal 230 / 400 V AC systems.
Yes. The TS version includes auxiliary signalling contacts with 1 NO and 1 NC contact, allowing the SPD's status to be integrated into a remote monitoring or control system.
The ABB order code is 2CTB815710R0000.
ABB OVR combined Type 1+2 surge protective devices are designed to protect low-voltage installations against lightning currents and transient overvoltages, providing coordinated protection for electrical and electronic equipment in industrial, commercial and infrastructure applications.