2CTB815708R5700 ABB OVR T2 N 80-440s C QS Surge Protection Cartridge

2CTB815708R5700 ABB OVR T2 N 80-440s C QS Surge Protection Cartridge

ABB OVR T2 N 80-440s C QS is a Type 2 N-PE surge protection cartridge with 440 V AC maximum continuous operating voltage, 30 kA nominal discharge current and 80 kA maximum discharge current for compatible ABB OVR QuickSafe surge protective devices.

SKU: 2CTB815708R5700MPN: 2CTB815708R5700
Price
List Price £97.01 ex VAT
Your Price (ex VAT) Save 25%
£72.76 25% OFF
You save £24.25 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £72.76
Trade pricing is personalised to your account

Manufacturer Lead Time

£72.76

Why Choose the ABB OVR T2 N 80-440s C QS Surge Protection Cartridge?

The ABB OVR T2 N 80-440s C QS is a high-performance Type 2 neutral surge protection cartridge designed for use with compatible ABB OVR QuickSafe surge protective devices. As part of the proven ABB OVR QuickSafe surge protection range, it provides N-PE protection against transient overvoltages caused by indirect lightning activity and electrical switching events.

Designed as a replaceable neutral cartridge, the OVR T2 N 80-440s C QS enables the protection element in compatible ABB OVR assemblies to be replaced without changing the complete surge protection device. Its N-PE protection mode makes it suitable for neutral-to-protective-earth surge protection in appropriate low-voltage electrical distribution systems.

With a maximum discharge current (Imax) of 80 kA, nominal discharge current (In) of 30 kA and 440 V AC maximum continuous operating voltage, the OVR T2 N 80-440s C QS provides robust surge protection performance in a compact cartridge format. The cartridge is supplied under ABB order code 2CTB815708R5700.

Key Advantages

  • High-performance Type 2 / Class II neutral surge protection cartridge.
  • Designed specifically for N-PE surge protection.
  • 80 kA maximum discharge current (8/20 µs) for demanding surge conditions.
  • 30 kA nominal discharge current (8/20 µs).
  • 440 V AC maximum continuous operating voltage.
  • 1 kV voltage protection level (Up).
  • ABB QuickSafe technology for dependable surge protection performance.
  • Replaceable cartridge format simplifies maintenance of compatible ABB OVR surge protective devices.

Key Features

  • ABB OVR Type 2 QuickSafe surge protection series.
  • Type 2 / Class II surge protection cartridge.
  • Single protected line with N-PE protection mode.
  • 80 kA Imax maximum discharge current.
  • 30 kA In nominal discharge current.
  • 6.25 kA Iimp (10/350 µs) impulse current capability.
  • 440 V AC maximum continuous operating voltage (Uc).
  • 1 kV voltage protection level (Up).
  • Fast response time of <25 ns.
  • Compact replaceable cartridge for compatible ABB OVR QuickSafe assemblies.

Reliable Neutral-to-Earth Surge Protection

Type 2 surge protective devices are designed to limit transient overvoltages within low-voltage electrical installations. Their replaceable protection cartridges provide a practical way to maintain surge protection performance, allowing an affected protection element to be replaced without replacing the complete compatible SPD assembly.

The ABB OVR QuickSafe range is designed for coordinated surge protection in electrical distribution systems. The OVR T2 N 80-440s C QS provides the neutral protection element for compatible ABB OVR devices, combining high discharge capability, N-PE protection and a compact replaceable cartridge design for straightforward maintenance.

Typical Applications

  • Replacement neutral cartridge for compatible ABB OVR QuickSafe surge protective devices.
  • N-PE surge protection in low-voltage electrical distribution systems.
  • Industrial electrical distribution boards.
  • Commercial building electrical systems.
  • Machine and automation control panels.
  • Building services and infrastructure installations.
  • Protection systems for sensitive electrical and electronic equipment.

Technical Specifications

Tick the specs you need, then view products that match.

Device Type Replacement cartridge
Impulse Current Iimp (kA) 6.25 kA
Series OVR T2 QuickSafe
ABB order code 2CTB815708R5700
Product group Surge Protection Devices
Product type Type 2 surge protection cartridge
Test class Type 2 / Class II
Protection mode N-PE
Number of protected lines 1
Nominal system voltage 400 V AC
Maximum continuous operating voltage (Uc) 440 V AC
Nominal discharge current In (8/20 µs) 30 kA
Maximum discharge current Imax (8/20 µs) 80 kA
Impulse current Iimp (10/350 µs) 6.25 kA
Voltage protection level (Up) 1 kV
Response time <25 ns
Protection rating IP20
Fire resistance UL 94 V-0
Operating frequency 47–63 Hz
Maximum operating altitude 2,000 m
Replacement type Neutral cartridge

Frequently Asked Questions

What is the ABB OVR T2 N 80-440s C QS used for?

This product is a Type 2 neutral surge protection cartridge designed to provide N-PE protection when installed in a compatible ABB OVR QuickSafe surge protective device.

What is the maximum discharge current of the OVR T2 N 80-440s C QS?

The cartridge has a maximum discharge current Imax of 80 kA using an 8/20 µs waveform and a nominal discharge current In of 30 kA.

What is the maximum continuous operating voltage?

The ABB OVR T2 N 80-440s C QS has a maximum continuous operating voltage Uc of 440 V AC.

What protection mode does this surge protection cartridge provide?

The OVR T2 N 80-440s C QS provides N-PE neutral-to-protective-earth protection and has a voltage protection level Up of 1 kV.

What is the ABB order code for the OVR T2 N 80-440s C QS?

The ABB order code is 2CTB815708R5700.

Trusted ABB Surge Protection Technology

ABB OVR QuickSafe surge protection products are designed for dependable protection of low-voltage electrical installations, helping safeguard electrical and electronic equipment against damaging transient overvoltages in industrial, commercial and infrastructure applications.