ABB OVR T2 N 80-440s C QS is a Type 2 N-PE surge protection cartridge with 440 V AC maximum continuous operating voltage, 30 kA nominal discharge current and 80 kA maximum discharge current for compatible ABB OVR QuickSafe surge protective devices.
£72.76
The ABB OVR T2 N 80-440s C QS is a high-performance Type 2 neutral surge protection cartridge designed for use with compatible ABB OVR QuickSafe surge protective devices. As part of the proven ABB OVR QuickSafe surge protection range, it provides N-PE protection against transient overvoltages caused by indirect lightning activity and electrical switching events.
Designed as a replaceable neutral cartridge, the OVR T2 N 80-440s C QS enables the protection element in compatible ABB OVR assemblies to be replaced without changing the complete surge protection device. Its N-PE protection mode makes it suitable for neutral-to-protective-earth surge protection in appropriate low-voltage electrical distribution systems.
With a maximum discharge current (Imax) of 80 kA, nominal discharge current (In) of 30 kA and 440 V AC maximum continuous operating voltage, the OVR T2 N 80-440s C QS provides robust surge protection performance in a compact cartridge format. The cartridge is supplied under ABB order code 2CTB815708R5700.
Type 2 surge protective devices are designed to limit transient overvoltages within low-voltage electrical installations. Their replaceable protection cartridges provide a practical way to maintain surge protection performance, allowing an affected protection element to be replaced without replacing the complete compatible SPD assembly.
The ABB OVR QuickSafe range is designed for coordinated surge protection in electrical distribution systems. The OVR T2 N 80-440s C QS provides the neutral protection element for compatible ABB OVR devices, combining high discharge capability, N-PE protection and a compact replaceable cartridge design for straightforward maintenance.
Tick the specs you need, then view products that match.
| Device Type | Replacement cartridge | |
|---|---|---|
| Impulse Current Iimp (kA) | 6.25 kA | |
| Series | OVR T2 QuickSafe | |
| ABB order code | 2CTB815708R5700 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protection cartridge | |
| Test class | Type 2 / Class II | |
| Protection mode | N-PE | |
| Number of protected lines | 1 | |
| Nominal system voltage | 400 V AC | |
| Maximum continuous operating voltage (Uc) | 440 V AC | |
| Nominal discharge current In (8/20 µs) | 30 kA | |
| Maximum discharge current Imax (8/20 µs) | 80 kA | |
| Impulse current Iimp (10/350 µs) | 6.25 kA | |
| Voltage protection level (Up) | 1 kV | |
| Response time | <25 ns | |
| Protection rating | IP20 | |
| Fire resistance | UL 94 V-0 | |
| Operating frequency | 47–63 Hz | |
| Maximum operating altitude | 2,000 m | |
| Replacement type | Neutral cartridge |
This product is a Type 2 neutral surge protection cartridge designed to provide N-PE protection when installed in a compatible ABB OVR QuickSafe surge protective device.
The cartridge has a maximum discharge current Imax of 80 kA using an 8/20 µs waveform and a nominal discharge current In of 30 kA.
The ABB OVR T2 N 80-440s C QS has a maximum continuous operating voltage Uc of 440 V AC.
The OVR T2 N 80-440s C QS provides N-PE neutral-to-protective-earth protection and has a voltage protection level Up of 1 kV.
The ABB order code is 2CTB815708R5700.
ABB OVR QuickSafe surge protection products are designed for dependable protection of low-voltage electrical installations, helping safeguard electrical and electronic equipment against damaging transient overvoltages in industrial, commercial and infrastructure applications.