Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2 80-440s P TS QS single-pole Type 2 pluggable surge protective device for 400/690 V AC systems, with 440 V AC maximum continuous operating voltage, 30 kA nominal discharge current, 80 kA maximum discharge current, Safety Reserve functionality and remote signalling.
£132.80
The ABB OVR T2 80-440s P TS QS is a single-pole Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning effects and electrical switching events. Identified by ABB order code 2CTB815708R2900, it is suitable for 400/690 V AC systems and TT, TN-C, TN-S and IT low-voltage distribution arrangements.
Designed for applications requiring high surge-current capability, the OVR T2 80-440s P TS QS provides a 30 kA nominal discharge current (In), an 80 kA maximum discharge current (Imax) using an 8/20 µs waveform and a 6.25 kA impulse-current capability (Iimp) using a 10/350 µs waveform. Its 440 V AC maximum continuous operating voltage (Uc) and 1.8 kV voltage protection level (Up) suit higher-voltage AC distribution applications.
ABB combines QuickSafe technology with a Safety Reserve function, which retains basic protection through an additional varistor when the primary protection stage reaches the end of its service life. The device is pluggable for straightforward maintenance, while its local status indicator and TS 1NO + 1NC remote signalling contacts allow both visual and external monitoring of protection condition.
Type 2 SPDs are designed to discharge currents produced by indirect lightning strikes and conducted or induced overvoltages on the power distribution network. The ABB OVR T2 80-440s P TS QS combines an 80 kA maximum discharge-current capability with a 30 kA nominal discharge current and 1.8 kV protection level, providing substantial transient protection for compatible higher-voltage AC distribution systems.
The Safety Reserve function provides an additional level of protection when the main protection stage reaches the end of its service life, allowing the installation to retain basic protection until cartridge replacement can be carried out. Combined with pluggable construction, local status indication and 1NO + 1NC TS contacts, this supports efficient inspection, remote condition monitoring and planned SPD maintenance.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| SPD Type | Type 2 | |
| Poles | 1-pole | |
| Device Type | Surge protection device | |
| Impulse Current Iimp (kA) | 6.25 kA | |
| Series | OVR T2 | |
| ABB order code | 2CTB815708R2900 | |
| Product group | Surge Protection Devices | |
| Product type | Surge protective device | |
| SPD classification | Type 2 / Class II | |
| Technology | Varistor / ABB QuickSafe | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Low-voltage distribution systems | TT / TN-C / TN-S / IT | |
| Nominal voltage | 400 V AC | |
| Nominal system voltage | 400/690 V AC | |
| Maximum continuous operating voltage (Uc) | 440 V AC | |
| Impulse current (Iimp, 10/350 µs) | 6.25 kA | |
| Nominal discharge current (In, 8/20 µs) | 30 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 80 kA | |
| Voltage protection level (Up) | 1.8 kV | |
| Response time | ≤25 ns | |
| Rated service short-circuit breaking capacity (Ics) | 100 kA | |
| Short-circuit withstand (Icc) | 100 kA | |
| Maximum backup fuse | 125 A | |
| Maximum backup MCB | 125 A | |
| Safety Reserve / preventive-maintenance function | Yes | |
| Status indicator | Yes | |
| Remote signalling | Yes | |
| Auxiliary contacts | 1NO + 1NC | |
| Minimum auxiliary-contact load | 12 V DC / 10 mA | |
| Maximum auxiliary-contact load | 250 V AC / 1 A | |
| Auxiliary-contact conductor cross-section | 1.5 mm² | |
| Solid conductor range | 2.5–35 mm² | |
| Stranded conductor range | 2.5–25 mm² | |
| Stripping length | 12.5 mm | |
| Terminal tightening torque | 2.8 N·m | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Maximum operating altitude | 5000 m | |
| Fire resistance | UL 94 V-0 | |
| Mounting | DIN rail | |
| Construction | Pluggable | |
| Width | 1 modular space | |
| Dimensions (H × W × D) | 95.8 × 17.8 × 76.7 mm | |
| Weight | 0.15 kg | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| RoHS | Conforms to Directive 2011/65/EU | |
| Compatible replacement cartridge | OVR T2 80-440s C QS | |
| Replacement cartridge order code | 2CTB815708R5500 | |
| EAN | 3660308525567 |
It is a Type 2 surge protective device designed to protect compatible 400/690 V AC low-voltage installations against transient overvoltages caused by indirect lightning effects and electrical switching events.
The OVR T2 80-440s P TS QS has a nominal discharge current (In) of 30 kA and a maximum discharge current (Imax) of 80 kA using an 8/20 µs waveform. Its impulse-current capability (Iimp) is 6.25 kA using a 10/350 µs waveform.
The device has a maximum continuous operating voltage (Uc) of 440 V AC and a nominal voltage of 400 V AC.
The “s” denotes ABB's Safety Reserve functionality, which retains basic protection through an additional varistor when the primary stage reaches end of life. TS indicates remote signalling, with 1NO + 1NC auxiliary contacts for external monitoring of SPD status.
Yes. The device has a pluggable construction. Its compatible replacement module is the ABB OVR T2 80-440s C QS, order code 2CTB815708R5500.