ABB OVR T2 3L 80-275s P QS three-pole Type 2 pluggable surge protective device for 230/400 V AC TN-C systems, with 20 kA nominal discharge current, 80 kA maximum discharge current and Safety Reserve functionality.
£338.07
The ABB OVR T2 3L 80-275s P QS is a three-pole Type 2 surge protective device (SPD) designed to protect three-phase low-voltage power distribution systems against transient overvoltages generated by indirect lightning strikes and electrical switching events. Identified by ABB order code 2CTB815708R1800, it is designed for 230/400 V AC TN-C distribution systems and provides protection across three lines.
Designed for installations requiring high surge-current capability, the OVR T2 3L 80-275s P QS provides a 20 kA nominal discharge current (In) and an 80 kA maximum discharge current (Imax) using an 8/20 µs waveform. It also has a 6.25 kA impulse-current capability (Iimp) using a 10/350 µs waveform, together with a 275 V AC maximum continuous operating voltage and 1.4 kV voltage protection level (Up).
ABB combines its patented QuickSafe technology with the Safety Reserve system to support safe operation and preventive maintenance. The pluggable construction allows individual protection cartridges to be replaced without changing the complete DIN rail base, while the integrated optical status indication provides a clear local indication of SPD condition.
Type 2 SPDs are designed to discharge surge currents caused by indirect lightning strikes and induced or conducted overvoltages on the power distribution network. The ABB OVR T2 3L 80-275s P QS combines a 20 kA nominal discharge current with an 80 kA maximum discharge-current capability, providing substantial transient protection for three-phase TN-C distribution systems.
ABB's patented Safety Reserve system is designed to extend protection availability and support preventive maintenance, while QuickSafe technology provides enhanced safety within the SPD. Together with the pluggable cartridge format and optical status indication, these features allow the protection condition to be checked easily and individual cartridges to be replaced when maintenance becomes necessary.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 3-pole | |
| Earthing System | TN-C | |
| Impulse Current Iimp (kA) | 6.25 kA | |
| Series | OVR T2 | |
| ABB order code | 2CTB815708R1800 | |
| Product group | Surge Protection Devices | |
| Product type | Surge protective device | |
| SPD classification | Type 2 / Class II | |
| Configuration | 3L / three-line | |
| Number of poles | 3 | |
| Number of protected poles | 3 | |
| Low-voltage distribution system | TN-C | |
| Nominal voltage | 230 V AC | |
| Nominal system voltage | 230/400 V AC | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Impulse current (Iimp, 10/350 µs) | 6.25 kA | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 80 kA | |
| Voltage protection level (Up) | 1.4 kV | |
| Rated service short-circuit breaking capacity (Ics) | 100 kA | |
| Short-circuit withstand (Icc) | 100 kA | |
| Safety Reserve / preventive-maintenance function | Yes | |
| QuickSafe technology | Yes | |
| Status indication | Optical | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Maximum operating altitude | 5000 m | |
| Power loss | 49 mW | |
| Maximum backup fuse | 160 A | |
| Maximum backup circuit breaker | 125 A | |
| Mounting | DIN rail | |
| Construction | Pluggable | |
| Width | 3 modular spaces | |
| Dimensions (H × W × D) | 88 × 53.4 × 76.7 mm | |
| Weight | 0.45 kg | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Compatible replacement cartridge | OVR T2 80-275s C QS | |
| Replacement cartridge order code | 2CTB815708R2600 | |
| EAN | 3660308525499 |
It is a three-pole Type 2 surge protective device designed to protect 230/400 V AC TN-C power distribution systems against transient overvoltages caused by indirect lightning effects and electrical switching events.
The SPD has a nominal discharge current (In) of 20 kA and a maximum discharge current (Imax) of 80 kA using an 8/20 µs waveform. Its impulse-current capability (Iimp) is 6.25 kA using a 10/350 µs waveform.
The OVR T2 3L 80-275s P QS has a maximum continuous operating voltage (Uc) of 275 V AC and is designed for 230/400 V AC systems.
The “s” identifies ABB's Safety Reserve version. Safety Reserve functionality is designed to extend protection availability and provide a preventive-maintenance indication so cartridge replacement can be planned.
Yes. The device has a pluggable construction and uses compatible ABB OVR T2 80-275s C QS replacement cartridges, order code 2CTB815708R2600.
ABB OVR Type 2 surge protective devices combine high surge-current capability with QuickSafe technology, Safety Reserve functionality, pluggable protection cartridges and clear local status indication to support effective transient overvoltage protection and planned maintenance.