ABB OVR T2 1N 80-275s P TS QS two-pole Type 2 pluggable surge protective device for 230 V AC TT and TN-S systems, with 20 kA nominal discharge current, 80 kA maximum discharge current, Safety Reserve functionality and remote signalling.
£244.55
The ABB OVR T2 1N 80-275s P TS QS is a two-pole Type 2 surge protective device (SPD) designed to protect single-phase plus neutral low-voltage installations against transient overvoltages caused by indirect lightning effects and electrical switching events. Identified by ABB order code 2CTB815708R0200, it is designed for 230 V AC TT and TN-S systems and provides coordinated protection across the line-neutral and neutral-earth paths.
This high-capacity ABB OVR device provides a 20 kA nominal discharge current (In) and 80 kA maximum discharge current (Imax) using an 8/20 µs waveform. It also provides a 6.25 kA impulse current (Iimp) using a 10/350 µs waveform, with voltage protection levels of 1.4 kV across L-N and 1.4 kV across N-PE.
The OVR T2 1N 80-275s P TS QS combines ABB's patented QuickSafe technology with the Safety Reserve system, integrated thermal disconnection and pluggable cartridges. Visual end-of-life indication supports local inspection, while the TS remote signalling contact provides one normally open and one normally closed auxiliary contact for external condition monitoring.
Type 2 SPDs are designed to discharge surge currents generated by indirect lightning effects and switching events before damaging transient voltages propagate through the installation. The ABB OVR T2 1N 80-275s P TS QS combines an 80 kA maximum discharge-current capability with low L-N and N-PE protection levels, making it suitable for demanding single-phase plus neutral distribution-board applications.
ABB's Safety Reserve system uses an additional protection stage so the SPD is not left completely without surge protection when its primary protection stage reaches end of life. Together with QuickSafe thermal disconnection, replaceable cartridges, visual indication and remote signalling, this allows the device's condition to be identified promptly and replacement maintenance to be planned.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| SPD Type | Type 2 | |
| Poles | 1-pole + N | |
| Earthing System | TN-S, TT | |
| Device Type | Surge protection device | |
| Impulse Current Iimp (kA) | 6.25 kA | |
| Series | OVR T2 | |
| ABB order code | 2CTB815708R0200 | |
| Product group | Surge Protection Devices | |
| Product type | Surge protective device | |
| SPD classification | Type 2 / Class II | |
| Configuration | 1N / single-phase plus neutral | |
| Protection modes | L-N / L-PE / N-PE | |
| Number of poles | 2 | |
| Number of protected poles | 2 | |
| Low-voltage distribution systems | TT / TN-S | |
| Rated voltage | 230 V AC | |
| Nominal AC system voltage | 230/400 V AC | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Frequency | 47–63 Hz | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 80 kA | |
| Impulse current (Iimp, 10/350 µs) | 6.25 kA | |
| Total discharge current (Itotal) | 80 kA | |
| Voltage protection level (Up, L-PE) | 1.5 kV | |
| Voltage protection level (Up, L-N) | 1.4 kV | |
| Voltage protection level (Up, N-PE) | 1.4 kV | |
| Short-circuit withstand (Isccr) | 100 kA | |
| Ground residual current | <10 µA | |
| Response time | <25 ns | |
| Maximum backup fuse | 160 A gG/gL | |
| Maximum backup circuit breaker | 125 A, curve B or C | |
| Integrated thermal disconnector | Yes | |
| Safety Reserve | Yes | |
| End-of-life indicator | Yes | |
| Remote signalling | Yes | |
| Auxiliary contacts | 1NO + 1NC | |
| Protection rating | IP20 | |
| Maximum operating altitude | 5000 m | |
| Power loss | 28 mW | |
| Solid conductor range | 2.5–35 mm² | |
| Stranded conductor range | 2.5–25 mm² | |
| Stripping length | 12.5 mm | |
| Mounting | 35 mm DIN rail | |
| Construction | Pluggable | |
| Width | 2 modular spaces | |
| Dimensions (H × W × D) | 95.8 × 35.6 × 76.7 mm | |
| Weight | 0.3 kg | |
| Fire resistance | UL 94 V-0 | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Phase replacement cartridge | OVR T2 80-275s C QS | |
| Phase replacement cartridge order code | 2CTB815708R2600 | |
| Neutral replacement cartridge | OVR T2 N 80-275s C QS | |
| Neutral replacement cartridge order code | 2CTB815708R2800 | |
| EAN | 3660308525413 |
It is a Type 2 surge protective device for protecting 230 V AC single-phase plus neutral TT and TN-S installations against transient overvoltages caused by indirect lightning effects and switching events.
The device has a nominal discharge current (In) of 20 kA and a maximum discharge current (Imax) of 80 kA using an 8/20 µs waveform, plus a 6.25 kA impulse current (Iimp) using a 10/350 µs waveform.
The “s” denotes ABB's Safety Reserve functionality. An additional protection stage provides basic surge protection after the primary protection stage reaches its end-of-life condition, giving maintenance personnel time to replace the affected cartridge.
The TS designation indicates remote signalling. This version includes one normally open and one normally closed auxiliary contact so the SPD's condition can be monitored by an external control, alarm or building-management system.
The compatible phase cartridge is the ABB OVR T2 80-275s C QS, order code 2CTB815708R2600, while the neutral cartridge is the OVR T2 N 80-275s C QS, order code 2CTB815708R2800.
ABB OVR Type 2 surge protective devices combine high surge-current capability with QuickSafe technology, Safety Reserve functionality, pluggable modules and condition signalling to support effective protection and planned maintenance in low-voltage electrical distribution systems.