Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2 40-440s C QS is a replaceable single-pole Type 2 surge protection cartridge with 40 kA maximum discharge current, 20 kA nominal discharge current, 440 V AC maximum continuous operating voltage, 1.5 kV voltage protection level and Safety Reserve functionality for compatible ABB OVR QuickSafe surge protection assemblies.
£53.25
The ABB OVR T2 40-440s C QS, order code 2CTB815704R5500, is a replaceable Type 2 / Class II surge protection cartridge from the ABB OVR QuickSafe range. Designed for compatible ABB OVR pluggable surge protection assemblies, this single-pole cartridge provides protection against transient overvoltages associated with indirect lightning and electrical switching events.
The OVR T2 40-440s C QS provides a 20 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax) with an 8/20 µs waveform, together with a 2 kA impulse current (Iimp) using a 10/350 µs waveform. ABB specifies a 400 V AC system voltage, 440 V AC maximum continuous operating voltage (Uc) and a 1.5 kV voltage protection level (Up).
The cartridge incorporates ABB's Safety Reserve and preventive-maintenance functionality, along with visual status indication for straightforward condition checking. Its replaceable cartridge format allows a compatible OVR SPD to be serviced without replacing the complete surge protection assembly, supporting efficient maintenance in TT, TN-C, TN-S and compatible IT low-voltage networks.
Type 2 surge protection devices are designed to limit transient overvoltages associated with indirect lightning and electrical switching events. They are commonly installed in distribution equipment to divert surge current away from sensitive downstream electrical and electronic equipment. A replaceable cartridge allows the active protection element to be renewed while retaining the compatible installed SPD base.
The ABB OVR T2 40-440s C QS combines a 40 kA maximum 8/20 µs discharge current with Safety Reserve and preventive-maintenance functionality. The cartridge is used as the phase replacement element in compatible ABB OVR assemblies, including the OVR T2 40-440s P QS family, allowing surge protection to be restored quickly without disturbing the permanent wiring to the SPD base.
Tick the specs you need, then view products that match.
| Device Type | Replacement cartridge | |
|---|---|---|
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2 QuickSafe | |
| Order code / MPN | 2CTB815704R5500 | |
| Product group | Surge Protection Devices | |
| Product type | Replacement surge protection cartridge | |
| SPD classification | Type 2 / Class II | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Compatible distribution systems | TT, TN-C, TN-S, IT | |
| System voltage | 400/690 V AC | |
| Maximum continuous operating voltage (Uc) | 440 V AC | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 40 kA | |
| Impulse current (Iimp, 10/350 µs) | 2 kA | |
| Voltage protection level (Up) | 1.5 kV | |
| Rated service short-circuit breaking capacity (Ics) | 100 kA | |
| Short-circuit withstand (Icc) | 100 kA | |
| Safety Reserve | Yes | |
| Preventive-maintenance function | Yes | |
| Status indicator | Yes | |
| Protection rating | IP20 | |
| Maximum operating altitude | 5000 m | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Dimensions (H × W × D) | 57 × 17.6 × 67 mm | |
| Weight | 0.075 kg | |
| Construction | Replaceable cartridge |
The ABB OVR T2 40-440s C QS is a replaceable Type 2 / Class II surge protection cartridge used in compatible ABB OVR QuickSafe surge protection assemblies to protect low-voltage electrical systems against transient overvoltages.
The cartridge has a 20 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax) with an 8/20 µs waveform, together with a 2 kA impulse current (Iimp) using a 10/350 µs waveform.
ABB specifies a 440 V AC maximum continuous operating voltage (Uc) and a 1.5 kV voltage protection level (Up) for the OVR T2 40-440s C QS cartridge.
Yes. The “s” version incorporates ABB Safety Reserve functionality together with preventive-maintenance and status-indication features, supporting continued protection and planned replacement of the cartridge.
The OVR T2 40-440s C QS, order code 2CTB815704R5500, is the replacement phase cartridge specified by ABB for compatible OVR T2 40-440s pluggable surge protection assemblies, including the OVR T2 40-440s P QS family.