2CTB815704R1200 ABB OVR T2 40-275s P QS Surge Protective Device

2CTB815704R1200 ABB OVR T2 40-275s P QS Surge Protective Device

ABB OVR T2 40-275s P QS is a single-pole pluggable Type 2 surge protective device with Safety Reserve technology, 20 kA nominal discharge current, 40 kA maximum discharge current, 275 V AC maximum continuous operating voltage and a 1.4 kV protection level.

SKU: 2CTB815704R1200MPN: 2CTB815704R1200
Price
List Price £72.21 ex VAT
Your Price (ex VAT) Save 25%
£54.16 25% OFF
You save £18.05 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £54.16
Trade pricing is personalised to your account

Manufacturer Lead Time

£54.16

Why Choose the ABB OVR T2 40-275s P QS Surge Protective Device?

The ABB OVR T2 40-275s P QS, order code 2CTB815704R1200, is a compact Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning effects and switching events. It is suitable for coordinated surge protection in residential, commercial and industrial distribution systems.

Designed for 230 V AC networks with a maximum continuous operating voltage of 275 V AC, the OVR T2 40-275s P QS provides a nominal discharge current In of 20 kA and a maximum discharge current Imax of 40 kA using the 8/20 µs waveform. Its voltage protection level Up of 1.4 kV helps limit transient voltage reaching downstream electrical and electronic equipment.

This single-pole SPD combines ABB QuickSafe technology with a Safety Reserve preventive-maintenance function. Rather than leaving the installation completely unprotected when the primary varistor reaches end of life, the reserve protection stage continues to provide basic surge protection until the cartridge can be replaced. Its pluggable construction and visual status indication further simplify inspection and maintenance.

Key Advantages

  • Reliable Type 2 / Class II surge protection for low-voltage installations.
  • 40 kA maximum discharge current using the 8/20 µs waveform.
  • 20 kA nominal discharge current for effective transient surge suppression.
  • 1.4 kV voltage protection level helps protect sensitive downstream equipment.
  • Safety Reserve function maintains basic protection after the primary protection stage reaches end of life.
  • ABB QuickSafe technology supports dependable thermal disconnection.
  • Pluggable cartridge construction simplifies maintenance and replacement.
  • Visual status indication enables straightforward inspection.
  • 100 kA short-circuit withstand capability supports demanding installations.
  • Compact 17.8 mm single-module width conserves DIN-rail space.

Key Features

  • ABB OVR T2 QuickSafe series.
  • Type 2 / Class II surge protective device.
  • Single-pole, single protected-line configuration.
  • Suitable for use in TT, TN-C and TN-S systems as part of the appropriate SPD arrangement.
  • 230 V AC nominal voltage.
  • 275 V AC maximum continuous operating voltage Uc.
  • 20 kA nominal discharge current In.
  • 40 kA maximum discharge current Imax.
  • 2 kA impulse-current capability using a 10/350 µs waveform.
  • 1.4 kV voltage protection level Up.
  • Safety Reserve preventive-maintenance feature.
  • Pluggable protection cartridge.
  • Optical/mechanical status indication.
  • IP20 degree of protection.

Type 2 Surge Protection with Safety Reserve Technology

Type 2 SPDs are designed to safely discharge transient currents characterised by the 8/20 µs waveform before damaging overvoltages can reach sensitive equipment. The ABB OVR T2 40-275s P QS combines a 20 kA nominal discharge current, 40 kA maximum discharge current and 1.4 kV protection level in a compact single-module format suitable for coordinated surge protection.

The distinguishing Safety Reserve feature provides an additional level of protection availability. When the main varistor reaches the end of its service life, a reserve varistor continues to provide basic surge protection until maintenance can be performed. Combined with visual status indication and a replaceable cartridge, this allows maintenance personnel to identify deterioration and schedule replacement without unnecessarily changing the complete SPD assembly.

Typical Applications

  • Main low-voltage distribution boards.
  • Sub-distribution boards and local electrical panels.
  • Residential electrical installations.
  • Commercial buildings and offices.
  • Industrial electrical and control panels.
  • Protection of sensitive electronic and automation equipment.
  • TT, TN-C and TN-S low-voltage distribution systems.
  • Installations requiring preventive SPD maintenance indication.
  • Coordinated surge protection systems using pluggable ABB OVR devices.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal No
Device Type Surge protection device
SPD Type Type 2
Poles 1-pole
Impulse Current Iimp (kA) 2 kA
Series OVR T2 QuickSafe
ABB order code 2CTB815704R1200
EAN / GTIN 3660308525291
Product group Surge Protection Devices
Product type Type 2 surge protective device
SPD classification Type 2 / Class II
Standard IEC 61643-11 / EN 61643-11
Low-voltage distribution systems TT / TN-C / TN-S
Number of poles 1
Number of protected lines 1
Nominal voltage Un 230 V AC
Nominal system voltage 230 / 400 V AC
Maximum continuous operating voltage Uc 275 V AC
Temporary overvoltage test value UT 337 V
Impulse current Iimp (10/350 µs) 2 kA
Nominal discharge current In (8/20 µs) 20 kA
Maximum discharge current Imax (8/20 µs) 40 kA
Voltage protection level Up 1.4 kV
Short-circuit withstand capability 100 kA
Rated service short-circuit breaking capacity Ics 100 kA
Maximum backup circuit breaker 125 A, B or C curve
Safety Reserve Yes
QuickSafe technology Yes
Status indicator Yes
Remote signalling No
Construction Pluggable
Replacement cartridge OVR T2 40-275s C QS
Replacement cartridge order code 2CTB815704R2600
Degree of protection IP20
Operating temperature -40 to +80 °C
Power loss 28 mW
Mounting type 35 mm DIN rail
Module width 1 module
Width 17.8 mm
Height 88 mm
Depth 76.7 mm
Weight approx. 0.15 kg

Frequently Asked Questions

What is the ABB OVR T2 40-275s P QS used for?

It is a Type 2 surge protective device designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning effects and electrical switching events.

What are the discharge-current ratings of the OVR T2 40-275s P QS?

The device has a nominal discharge current In of 20 kA and a maximum discharge current Imax of 40 kA using the 8/20 µs waveform.

What does the “s” mean in OVR T2 40-275s?

The “s” identifies ABB's Safety Reserve version. A reserve varistor continues to provide basic protection after the primary protection stage reaches end of life, giving maintenance personnel time to replace the cartridge while retaining a level of surge protection.

Does the OVR T2 40-275s P QS have remote signalling?

No. ABB order code 2CTB815704R1200 is the version without the TS auxiliary remote-signalling contact. The corresponding TS version is available where remote SPD condition monitoring is required.

Can the protection cartridge be replaced?

Yes. The OVR T2 40-275s P QS uses a pluggable protection cartridge. The compatible replacement cartridge is the ABB OVR T2 40-275s C QS, order code 2CTB815704R2600.

Trusted ABB Surge Protection Technology

ABB OVR Type 2 surge protective devices combine high surge-current capability, compact pluggable construction and QuickSafe technology, with the OVR T2 40-275s P QS adding Safety Reserve functionality to maintain basic protection and support planned maintenance when the primary protection stage reaches end of life.