ABB OVR T2 4L 40-275s P TS QS four-pole Type 2 pluggable surge protective device for 230/400 V AC TN-S systems, with 20 kA nominal discharge current, 40 kA maximum discharge current, Safety Reserve technology and remote signalling.
£376.52
The ABB OVR T2 4L 40-275s P TS QS is a four-pole Type 2 surge protective device (SPD) designed to protect three-phase low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and switching events. Identified by ABB order code 2CTB815704R1100, it is designed for 230/400 V AC TN-S networks and protects four lines within a compact DIN rail assembly.
This ABB OVR model combines varistor technology with patented QuickSafe technology and the Safety Reserve system. The Safety Reserve function provides an additional protection stage, helping maintain a level of surge protection after the primary protection stage reaches its end-of-life condition and giving maintenance personnel an opportunity to arrange cartridge replacement.
The OVR T2 4L 40-275s P TS QS provides a 20 kA nominal discharge current (In) and 40 kA maximum discharge current (Imax) using an 8/20 µs waveform, together with a 1.5 kV voltage protection level (Up). Pluggable cartridges, local status indication and the integrated TS remote signalling contact support straightforward inspection, monitoring and maintenance.
Type 2 SPDs are intended to discharge surge currents associated with indirect lightning effects and switching transients, with their primary discharge performance characterised using the 8/20 µs waveform. The ABB OVR T2 4L 40-275s P TS QS combines a 20 kA nominal discharge current with a 40 kA maximum discharge current and 1.5 kV protection level to help limit transient voltages reaching downstream equipment.
ABB's Safety Reserve system adds a secondary protection stage to support preventive maintenance, while QuickSafe technology provides integrated thermal disconnection. Together with replaceable cartridges, visual status indication and the TS auxiliary contact, these features make the SPD suitable for installations where protection availability and clear maintenance indication are important.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 4-pole | |
| Earthing System | TN-S | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2 | |
| ABB order code | 2CTB815704R1100 | |
| Product group | Surge Protection Devices | |
| Product type | Surge protective device | |
| SPD classification | Type 2 / Class II | |
| Technology | Varistor / ABB QuickSafe | |
| Safety Reserve | Yes | |
| Number of poles | 4 | |
| Number of protected lines | 4 | |
| Low-voltage distribution system | TN-S | |
| Nominal system voltage | 230/400 V AC | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 40 kA | |
| Impulse current (Iimp, 10/350 µs) | 2 kA | |
| Voltage protection level (Up) | 1.5 kV | |
| Voltage protection level at 3 kA | 0.5 kV | |
| Voltage protection level at 5 kA | 0.7 kV | |
| Voltage protection level at 10 kA | 0.9 kV | |
| Response time | ≤25 ns | |
| Short-circuit withstand capability | 100 kA | |
| Maximum backup fuse | 160 A gG/gL | |
| Maximum backup circuit breaker | 125 A, B or C curve | |
| Integrated thermal disconnector | Yes | |
| Status indication | Yes | |
| Remote signalling | Yes, TS auxiliary contact | |
| Auxiliary contact configuration | 1NO + 1NC | |
| Minimum auxiliary-contact load | 12 V DC / 10 mA | |
| Maximum auxiliary-contact load | 250 V AC / 1 A | |
| Auxiliary-contact connection cross-section | 1.5 mm² | |
| Solid conductor range | 2.5–25 mm² | |
| Stranded conductor range | 2.5–16 mm² | |
| Stripping length | 12.5 mm | |
| Terminal tightening torque | 2.5 N·m | |
| Protection rating | IP20 | |
| Operating and storage temperature | -40 to +80 °C | |
| Maximum operating altitude | 5000 m | |
| Fire resistance | UL 94 V-0 | |
| Mounting | DIN rail | |
| Construction | Pluggable | |
| Width | 4 modular spaces | |
| Dimensions with TS contact (H × W × D) | 95.8 × 71.2 × 76.7 mm | |
| Weight | 0.6 kg | |
| Power loss | 49 mW | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| EAN | 3660308525284 |
It is a four-pole Type 2 surge protective device designed to protect 230/400 V AC TN-S electrical networks against transient overvoltages caused by indirect lightning effects and switching events.
The OVR T2 4L 40-275s P TS QS provides a nominal discharge current (In) of 20 kA and a maximum discharge current (Imax) of 40 kA using an 8/20 µs waveform.
The “s” denotes ABB's Safety Reserve functionality. This provides an additional protection stage so that reserve surge protection remains available when the primary protection stage reaches its end-of-life condition, allowing planned replacement of the cartridge.
The TS designation indicates remote signalling. This version provides a 1NO + 1NC auxiliary contact for external monitoring of the SPD's protection status.
Yes. The device uses pluggable protection cartridges, allowing individual modules to be replaced during maintenance without replacing the complete DIN rail base assembly.
ABB OVR Type 2 surge protective devices combine high surge-current capability with QuickSafe technology, Safety Reserve functionality, pluggable modules and condition signalling to support reliable protection and planned maintenance in low-voltage distribution systems.