ABB OVR T2 3L 40-275s P TS QS is a pluggable three-pole Type 2 surge protection device with 40 kA maximum discharge current, 20 kA nominal discharge current, 275 V AC maximum continuous operating voltage, Safety Reserve technology and remote signalling for 230/400 V TN-C electrical systems.
£303.22
The ABB OVR T2 3L 40-275s P TS QS, order code 2CTB815704R0600, is a pluggable Type 2 surge protection device (SPD) designed to protect three-phase low-voltage electrical installations against transient overvoltages caused by indirect lightning and switching events. Part of the ABB OVR QuickSafe range, it combines high surge-discharge capability with ABB Safety Reserve technology for use in TN-C power distribution systems.
Designed for 230/400 V AC systems, the OVR T2 3L 40-275s P TS QS provides a 20 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax) with an 8/20 µs waveform. Its maximum continuous operating voltage (Uc) is 275 V AC, while its voltage protection level (Up) is 1.4 kV, helping limit transient voltages reaching downstream equipment.
The Safety Reserve system provides an additional level of protection and supports planned maintenance, while patented QuickSafe technology improves disconnection performance. The TS version includes remote signalling through one normally open and one normally closed auxiliary contact, complemented by local status indication and preventive-maintenance functionality.
Type 2 surge protection devices are designed to discharge surge currents generated by indirect lightning strikes and switching events that cause induced or conducted overvoltages on low-voltage power distribution networks. They are commonly installed in main distribution switchboards and subdistribution boards, where their low residual voltage helps protect downstream electrical and electronic equipment.
The ABB OVR T2 3L 40-275s P TS QS combines 40 kA maximum discharge capability with ABB's Safety Reserve and QuickSafe technologies. Its visual status indication, preventive-maintenance function and remote signalling contacts provide multiple ways to monitor SPD condition, helping maintenance teams identify when servicing or replacement is required while reducing the risk of unplanned loss of surge protection.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 3-pole | |
| Earthing System | TN-C | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2 QuickSafe | |
| Order code / MPN | 2CTB815704R0600 | |
| EAN | 3660308525253 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protection device | |
| SPD classification | Type 2 / Class II | |
| Number of poles | 3 | |
| Number of protected poles | 3 | |
| Low-voltage distribution system | TN-C | |
| Nominal voltage | 230 V AC | |
| Nominal system voltage | 230/400 V AC | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 40 kA | |
| Impulse current (Iimp, 10/350 µs) | 2 kA | |
| Voltage protection level (Up) | 1.4 kV | |
| Rated service short-circuit breaking capacity (Ics) | 100 kA | |
| Short-circuit withstand (Icc) | 100 kA | |
| Safety Reserve | Yes | |
| Preventive-maintenance function | Yes | |
| Status indicator | Yes | |
| Remote signalling | Yes | |
| Normally open auxiliary contacts | 1 | |
| Normally closed auxiliary contacts | 1 | |
| Maximum backup fuse | 160 A | |
| Maximum backup MCB | 125 A | |
| Power loss | 49 mW | |
| Mounting type | DIN rail | |
| Module width | 3 modules | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Maximum operating altitude | 5000 m | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Dimensions (H × W × D) | 95.8 × 53.4 × 76.7 mm | |
| Weight | 0.45 kg | |
| Construction | Pluggable |
The ABB OVR T2 3L 40-275s P TS QS is a three-pole Type 2 surge protection device designed to protect 230/400 V AC TN-C low-voltage electrical installations against transient overvoltages caused by indirect lightning and electrical switching events.
The device has a 20 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax), measured using an 8/20 µs waveform.
ABB's Safety Reserve system provides an additional protection stage that supports continued protection and planned maintenance when the primary protection stage has reached the end of its service life, helping reduce the risk of unexpected downtime.
Yes. The TS version includes remote signalling through one normally open and one normally closed auxiliary contact, allowing SPD condition information to be incorporated into an external monitoring or alarm system.
The device provides a voltage protection level (Up) of 1.4 kV and has a maximum continuous operating voltage (Uc) of 275 V AC for use in compatible 230/400 V AC TN-C systems.
ABB OVR Type 2 surge protection devices are designed to help protect low-voltage electrical distribution systems against transient overvoltages, with QuickSafe, Safety Reserve and remote signalling features supporting effective protection, condition monitoring and planned maintenance.