ABB OVR T2 40-275s P TS QS is a single-pole pluggable Type 2 surge protective device with Safety Reserve, 40 kA maximum discharge current, 20 kA nominal discharge current, 275 V AC maximum continuous operating voltage and remote status signalling.
£105.00
The ABB OVR T2 40-275s P TS QS, order code 2CTB815704R0000, is a compact Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and switching events. Suitable for installation in main distribution boards, sub-distribution boards and close to sensitive equipment, it combines ABB QuickSafe technology with Safety Reserve functionality for dependable surge protection and preventive maintenance.
Designed for 230/400 V AC systems, the OVR T2 40-275s P TS QS has a maximum continuous operating voltage of 275 V AC, a nominal discharge current In of 20 kA and a maximum discharge current Imax of 40 kA using the 8/20 µs waveform. It also has a 2 kA impulse-current rating using the 10/350 µs waveform and provides a voltage protection level Up of 1.4 kV.
The single-pole SPD features a pluggable cartridge, optical status indication, ABB's patented Safety Reserve system and TS remote signalling through one normally open and one normally closed auxiliary contact. Its compact 17.8 mm DIN-rail width and 100 kA short-circuit withstand capability make it suitable for residential, commercial and industrial distribution applications.
Type 2 SPDs are designed to discharge transient currents produced by indirect lightning events and switching operations before these overvoltages reach sensitive electrical equipment. The ABB OVR T2 40-275s P TS QS combines a 40 kA maximum 8/20 µs discharge capability with a low 1.4 kV protection level, making it suitable for coordinated protection in main and sub-distribution boards.
The Safety Reserve system distinguishes this 275s model by providing an additional preventive-maintenance function that helps indicate deterioration before complete protection is lost. Together with its visual status indicator, pluggable cartridge and TS auxiliary contacts, this allows maintenance personnel to monitor SPD condition and plan cartridge replacement while reducing the risk of unplanned protection downtime.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 1-pole | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2 QuickSafe | |
| ABB order code | 2CTB815704R0000 | |
| EAN / GTIN | 3660308525222 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device | |
| SPD classification | Type 2 / Class II | |
| Reference standards | IEC 61643-11 / EN 61643-11 | |
| Protection technology | Varistor | |
| Low-voltage distribution systems | TT / TN-C / TN-S | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Nominal system voltage | 230 / 400 V AC | |
| Nominal voltage | 230 V AC | |
| Maximum continuous operating voltage Uc | 275 V AC | |
| Impulse current Iimp (10/350 µs) | 2 kA | |
| Nominal discharge current In (8/20 µs) | 20 kA | |
| Maximum discharge current Imax (8/20 µs) | 40 kA | |
| Voltage protection level Up | 1.4 kV | |
| Short-circuit withstand capability Isccr | 100 kA | |
| Rated service short-circuit breaking capacity Ics | 100 kA | |
| Maximum backup fuse | 160 A | |
| Maximum backup circuit breaker | 125 A, B or C curve | |
| Safety Reserve | Yes | |
| Preventive maintenance function | Yes | |
| QuickSafe technology | Yes | |
| Remote signalling | Yes | |
| Normally open auxiliary contacts | 1 | |
| Normally closed auxiliary contacts | 1 | |
| Minimum auxiliary contact load | 12 V DC / 10 mA | |
| Maximum auxiliary contact load | 250 V AC / 1 A | |
| Status indication | Optical | |
| Construction | Pluggable | |
| Replacement cartridge | OVR T2 40-275s C QS | |
| Replacement cartridge order code | 2CTB815704R2600 | |
| Degree of protection | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Maximum operating altitude | 5000 m | |
| Power loss | 28 mW | |
| Mounting type | DIN rail | |
| Module width | 1 module | |
| Dimensions (H × W × D) | 95.8 × 17.8 × 76.7 mm | |
| Weight | approx. 0.15 kg |
It is a Type 2 surge protective device designed to protect low-voltage electrical installations and connected equipment against transient overvoltages caused by indirect lightning effects and electrical switching events.
The device has a nominal discharge current In of 20 kA and a maximum discharge current Imax of 40 kA using the 8/20 µs waveform, together with a 2 kA impulse-current rating using the 10/350 µs waveform.
The 275s version incorporates ABB's Safety Reserve function, which provides preventive-maintenance indication to help identify deterioration and plan replacement before surge protection is completely lost.
The TS version includes remote signalling contacts, with one normally open and one normally closed auxiliary contact for integration with suitable monitoring, alarm or building-management systems.
Yes. The OVR T2 40-275s P TS QS has a pluggable protection cartridge. The compatible replacement is the ABB OVR T2 40-275s C QS, order code 2CTB815704R2600.
ABB OVR Type 2 surge protective devices combine high surge-current capability, QuickSafe technology, pluggable construction and status monitoring, with the OVR T2 40-275s P TS QS adding Safety Reserve preventive maintenance and remote signalling for dependable low-voltage surge protection.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.