Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T1-T2 1L 25-255 P TS single-pole combined Type 1 and Type 2 pluggable surge protective device for 230/400 V AC TT, TN-S and TN-C systems, with 25 kA impulse current, 60 kA maximum discharge current and remote status signalling.
£421.63
The ABB OVR T1-T2 1L 25-255 P TS is a combined Type 1 + Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations against high-energy lightning currents and transient overvoltages. Identified by ABB order code 2CTB813251R2300, this single-pole SPD is suitable for TT, TN-S and TN-C distribution systems and is intended for installation in main AC distribution switchboards and sub-distribution boards.
Using spark-gap technology, the OVR T1-T2 1L 25-255 P TS provides a 25 kA lightning impulse current (Iimp) using the 10/350 µs waveform, together with a 25 kA nominal discharge current (In) and 60 kA maximum discharge current (Imax) using the 8/20 µs waveform. Its voltage protection level of ≤1.5 kV helps limit transient voltage stress on downstream equipment.
The device is designed for 230/400 V AC networks and has a 264 V AC maximum continuous operating voltage (Uc). Its pluggable construction enables straightforward cartridge replacement, while the integrated TS 1NO + 1NC remote signalling contact allows the SPD condition to be monitored from an external control, alarm or building-management system.
Combined Type 1 and Type 2 SPDs provide coordinated protection against both high-energy lightning-current impulses and transient overvoltages. The ABB OVR T1-T2 1L 25-255 P TS handles a 25 kA 10/350 µs lightning impulse while also providing 8/20 µs Type 2 surge protection, making it suitable for installation at main and sub-distribution levels where substantial surge-current capability is required.
Its spark-gap technology combines high lightning-current capability with a ≤1.5 kV protection level. The pluggable cartridge facilitates maintenance, while the visual end-of-life indicator and 1NO + 1NC TS contact provide both local and remote indication of protection status, supporting planned maintenance of electrical distribution systems.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Poles | 1-pole | |
| Impulse Current Iimp (kA) | 25 kA | |
| Series | OVR T1-T2 | |
| ABB order code | 2CTB813251R2300 | |
| Product group | Surge Protection Devices | |
| Product type | Combined lightning-current and surge protective device | |
| SPD classification | Type 1 + Type 2 / Class I + Class II | |
| Technology | Spark gap | |
| Number of protected lines | 1 | |
| Number of poles | 1 | |
| Low-voltage distribution systems | TT / TN-S / TN-C | |
| Protection modes | L-N / N-PE / L-PE (N), according to installation configuration | |
| Nominal network voltage | 230/400 V AC | |
| Maximum continuous operating voltage (Uc) | 264 V AC | |
| System frequency | 47–63 Hz | |
| Impulse current (Iimp, 10/350 µs) | 25 kA | |
| Total discharge current (Itotal, 10/350 µs) | 25 kA | |
| Nominal discharge current (In, 8/20 µs) | 25 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 60 kA | |
| Voltage protection level (Up) | ≤1.5 kV | |
| Short-circuit current rating (Isccr) | 50 kA | |
| Maximum prospective short-circuit current | 100 kA | |
| Follow current interrupted (Ifi) | 50 kA | |
| Backup protection | ≤315 A gG | |
| Leakage current | <1 mA | |
| Response time | <100 ns | |
| TOV withstand L-N | 440 V for 120 minutes | |
| End-of-life indicator | Green = functional / red = replace | |
| Remote signalling | Yes | |
| Auxiliary contact | 1NO + 1NC | |
| Minimum auxiliary-contact load | 12 V DC / 10 mA | |
| Maximum auxiliary-contact load | 250 V AC / 1 A | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Maximum operating altitude | 2000 m | |
| Relative humidity | 95% non-condensing | |
| Flexible conductor cross-section | 10–35 mm² | |
| Solid/stranded conductor cross-section | 10–50 mm² | |
| Stripping length | 16.5 mm | |
| Main-terminal tightening torque | 7 N·m | |
| Mounting | DIN rail | |
| Construction | Pluggable | |
| Dimensions (H × W × D) | 99 × 36 × 73 mm | |
| Weight | 0.33 kg | |
| Enclosure material rating | UL 94 V-0 | |
| Enclosure colour | Grey RAL 7035 | |
| Standards | IEC 61643-11 / EN 61643-11 / UL 1449 5th Edition / GB/T 18802.11-2020 | |
| Approvals | VDE / KEMA / UL / UKCA / RCM / CMIM / CQC | |
| Compatible replacement cartridge | OVR T1-T2-T3 1L 25-255 C | |
| Replacement cartridge order code | 2CTB813252R2300 |
It is a combined Type 1 and Type 2 surge protective device for protecting low-voltage TT, TN-S and TN-C electrical installations against high-energy lightning currents and transient overvoltages.
The OVR T1-T2 1L 25-255 P TS has an impulse current (Iimp) rating of 25 kA using the 10/350 µs lightning-current waveform.
The device provides a nominal discharge current (In) of 25 kA and a maximum discharge current (Imax) of 60 kA using an 8/20 µs waveform.
The TS designation indicates remote signalling. This model incorporates a 1NO + 1NC auxiliary contact rated up to 250 V AC / 1 A, allowing SPD status to be monitored by an external system.
Yes. The SPD has a pluggable construction. Its compatible replacement cartridge is the ABB OVR T1-T2-T3 1L 25-255 C, order code 2CTB813252R2300.
ABB OVR combined Type 1 and Type 2 surge protective devices provide high-capacity lightning-current and transient overvoltage protection for low-voltage distribution systems, with pluggable modules and remote signalling options that support efficient inspection and maintenance.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.