2CTB813250R2300 ABB OVR T1-T2 1L 25-255 P Surge Protective Device

2CTB813250R2300 ABB OVR T1-T2 1L 25-255 P Surge Protective Device

ABB OVR T1-T2 1L 25-255 P single-pole combined Type 1 and Type 2 pluggable surge protective device for 230/400 V AC TT, TN-S and TN-C systems, with 25 kA impulse current, 60 kA maximum discharge current and a protection level of ≤1.5 kV.

SKU: 2CTB813250R2300MPN: 2CTB813250R2300
Price
List Price £539.69 ex VAT
Your Price (ex VAT) Save 25%
£404.77 25% OFF
You save £134.92 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £404.77
Trade pricing is personalised to your account

Manufacturer Lead Time

£404.77

Why Choose the ABB OVR T1-T2 1L 25-255 P Surge Protective Device?

The ABB OVR T1-T2 1L 25-255 P is a combined Type 1 + Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations against high-energy lightning currents and transient overvoltages. Identified by ABB order code 2CTB813250R2300, this single-pole device is suitable for TT, TN-S and TN-C distribution systems and is typically installed in main AC distribution boards or sub-distribution boards.

Using spark-gap technology, the OVR T1-T2 1L 25-255 P combines substantial lightning-current handling with a low residual protection voltage. It provides a 25 kA impulse current (Iimp) using the 10/350 µs waveform, together with a 25 kA nominal discharge current (In) and 60 kA maximum discharge current (Imax) using the 8/20 µs waveform.

The device operates on 230/400 V AC networks with a 264 V AC maximum continuous operating voltage (Uc) and provides a voltage protection level of ≤1.5 kV. Its pluggable construction enables the protection cartridge to be replaced independently of the DIN rail base, simplifying maintenance of lightning and surge protection systems.

Key Advantages

  • Combined Type 1 + Type 2 protection in a single compact SPD.
  • 25 kA impulse current (Iimp) using the 10/350 µs lightning-current waveform.
  • 60 kA maximum discharge current (Imax) using an 8/20 µs waveform.
  • 25 kA nominal discharge current (In) for dependable Type 2 surge protection.
  • Low ≤1.5 kV voltage protection level (Up) helps limit transient stress on downstream equipment.
  • Suitable for TT, TN-S and TN-C distribution networks.
  • 50 kA follow-current interruption capability supports demanding AC installations.
  • Pluggable cartridge construction simplifies servicing and replacement.

Key Features

  • ABB OVR T1-T2 surge protection range.
  • Type 1 + Type 2 / Class I + Class II surge protection.
  • Single protected line.
  • Spark-gap technology.
  • 230/400 V AC nominal network voltage.
  • 264 V AC maximum continuous operating voltage (Uc).
  • 25 kA impulse current (Iimp, 10/350 µs).
  • 25 kA nominal discharge current (In, 8/20 µs).
  • 60 kA maximum discharge current (Imax, 8/20 µs).
  • ≤1.5 kV voltage protection level (Up).
  • <100 ns response time.
  • Green/red end-of-life indication for straightforward condition checking.
  • Pluggable protection cartridge for convenient maintenance.

Reliable Type 1 and Type 2 Protection for AC Distribution Systems

Combined Type 1 and Type 2 SPDs are designed to handle both high-energy lightning-current impulses and transient overvoltages within low-voltage power systems. The ABB OVR T1-T2 1L 25-255 P withstands a 25 kA 10/350 µs impulse current while also providing Type 2 performance against 8/20 µs surge currents, helping coordinate lightning and surge protection within a single device.

Its spark-gap technology provides high lightning-current capability together with a ≤1.5 kV protection level. The pluggable architecture allows the protection cartridge to be replaced independently of the base, while the green/red indicator provides a clear visual indication of whether the installed protection module remains operational.

Typical Applications

  • Main AC electrical distribution switchboards.
  • Sub-distribution boards.
  • 230/400 V AC low-voltage installations.
  • TT, TN-S and TN-C distribution systems.
  • Commercial and industrial electrical installations.
  • Building power distribution systems.
  • Installations requiring combined Type 1 and Type 2 lightning and surge protection.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal No
Device Type Surge protection device
SPD Type Type 1+2
Poles 1-pole
Impulse Current Iimp (kA) 25 kA
Series OVR T1-T2
ABB order code 2CTB813250R2300
Product group Surge Protection Devices
Product type Combined lightning-current and surge protective device
SPD classification Type 1 + Type 2 / Class I + Class II
Technology Spark gap
Number of protected lines 1
Number of poles 1
Low-voltage distribution systems TT / TN-S / TN-C
Protection modes L-N / N-PE / L-PE (N), according to installation configuration
Nominal network voltage 230/400 V AC
Maximum continuous operating voltage (Uc) 264 V AC
System frequency 47–63 Hz
Impulse current (Iimp, 10/350 µs) 25 kA
Total discharge current (Itotal, 10/350 µs) 25 kA
Nominal discharge current (In, 8/20 µs) 25 kA
Maximum discharge current (Imax, 8/20 µs) 60 kA
Voltage protection level (Up) ≤1.5 kV
Short-circuit current rating (Isccr) 50 kA
Maximum prospective short-circuit current 100 kA
Follow current interrupted (Ifi) 50 kA
Maximum backup protection 315 A gG
Leakage current <1 mA
Response time <100 ns
TOV withstand L-N 440 V for 120 minutes
End-of-life indicator Green = functional / red = replace
Mounting DIN rail
Construction Pluggable
Maximum operating altitude 2000 m
Operating temperature -40 to +70 °C
Dimensions (H × W × D) 90 × 36 × 73 mm
Weight 0.3 kg
Standards IEC 61643-11 / EN 61643-11 / UL 1449 5th Edition / GB/T 18802.11-2020
Approvals VDE / KEMA / UL / UKCA / RCM / CMIM / CQC
Compatible replacement cartridge OVR T1-T2 1L 25-255 C
Replacement cartridge order code 2CTB813252R2300

Frequently Asked Questions

What is the ABB OVR T1-T2 1L 25-255 P used for?

It is a combined Type 1 and Type 2 surge protective device designed to protect low-voltage TT, TN-S and TN-C electrical installations against high-energy lightning currents and transient overvoltages.

What is the lightning impulse current rating?

The OVR T1-T2 1L 25-255 P has an impulse current (Iimp) rating of 25 kA using the 10/350 µs lightning-current waveform.

What are the Type 2 discharge-current ratings?

The device provides a nominal discharge current (In) of 25 kA and a maximum discharge current (Imax) of 60 kA using an 8/20 µs waveform.

What is the maximum continuous operating voltage?

The ABB OVR T1-T2 1L 25-255 P has a maximum continuous operating voltage (Uc) of 264 V AC and is designed for 230/400 V AC networks.

Can the protection cartridge be replaced?

Yes. The device has a pluggable construction. Its compatible replacement module is the ABB OVR T1-T2 1L 25-255 C, order code 2CTB813252R2300.

Trusted Lightning and Surge Protection from ABB

ABB OVR combined Type 1 and Type 2 surge protective devices provide high-capacity lightning-current and transient overvoltage protection for low-voltage distribution systems, combining spark-gap technology with pluggable construction for dependable protection and convenient maintenance.