Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T1-T2 N 100-255 P TS is a pluggable Type 1+2 neutral-to-earth surge protection device with 100 kA impulse current, 100 kA nominal discharge current, 255 V AC maximum continuous operating voltage and remote signalling for 230/400 V TT and TN-S electrical systems.
£512.27
The ABB OVR T1-T2 N 100-255 P TS, order code 2CTB813011R2300, is a pluggable Type 1+2 surge protection device (SPD) designed for neutral-to-earth protection in low-voltage TT and TN-S electrical systems. Using spark-gap technology, it combines high lightning-current discharge capability with a low residual voltage to provide coordinated protection at main and subdistribution boards.
Designed for 230/400 V AC networks, the OVR T1-T2 N 100-255 P TS provides an exceptional 100 kA impulse current (Iimp) with a 10/350 µs waveform between neutral and protective earth. It also has a 100 kA nominal discharge current (In) with an 8/20 µs waveform and a maximum continuous operating voltage (Uc) of 255 V AC.
The device provides a voltage protection level (Up) of ≤1.5 kV and incorporates a visual end-of-life indicator for straightforward condition checking. The TS version includes remote signalling contacts, allowing SPD status to be incorporated into monitoring or alarm systems, while its pluggable construction enables convenient replacement of the protection cartridge when required.
Type 1+2 surge protection devices combine the ability to discharge high-energy lightning currents with protection against transient overvoltages. The ABB OVR T1-T2 N 100-255 P TS is specifically configured for neutral-to-earth protection, using spark-gap technology to handle substantial lightning-current impulses while maintaining a voltage protection level of ≤1.5 kV.
The device is typically installed within main AC distribution switchboards or subdistribution boards as part of a coordinated surge protection system. Its 100 kA 10/350 µs impulse-current capability, visual condition indication and remote signalling contacts make it particularly suitable for installations where high-capacity surge protection and ongoing SPD status monitoring are required.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| SPD Type | Type 1+2 | |
| Poles | 1-pole | |
| Device Type | Surge protection device | |
| Impulse Current Iimp (kA) | 100 kA | |
| Series | OVR T1-T2 | |
| Order code / MPN | 2CTB813011R2300 | |
| Product group | Surge Protection Devices | |
| Product type | Type 1+2 surge protection device | |
| SPD classification | Type 1+2 / Class I+II | |
| Protection mode | N-PE | |
| Number of poles | 1 | |
| Number of protected lines | 1 | |
| Low-voltage distribution systems | TT, TN-S | |
| Nominal system voltage (Un) | 230/400 V AC | |
| Maximum continuous operating voltage (Uc, N-PE) | 255 V AC | |
| System frequency | 47–63 Hz | |
| Impulse current (Iimp, N-PE, 10/350 µs) | 100 kA | |
| Nominal discharge current (In, N-PE, 8/20 µs) | 100 kA | |
| Voltage protection level (Up, N-PE) | ≤1.5 kV | |
| Follow current interrupted (Ifi, N-PE) | 0.1 kA | |
| Maximum prospective short-circuit current (PSCC, N-PE) | 0.1 kA | |
| Rated service short-circuit breaking capacity (Ics) | 100 kA | |
| Short-circuit withstand (Icc) | 100 kA | |
| Leakage current (Ipe) | <1 mA | |
| Response time | <100 ns | |
| TOV withstand (N-PE, 200 ms) | 1200 V | |
| Technology | Spark gap | |
| End-of-life indicator | Green = functional / red = replace | |
| Remote signalling | Yes | |
| Normally open auxiliary contacts | 1 | |
| Normally closed auxiliary contacts | 1 | |
| Mounting type | DIN rail | |
| Operating temperature | -40 to +70 °C | |
| Maximum operating altitude | 2000 m | |
| Dimensions (H × W × D) | 99 × 36 × 73 mm | |
| Weight | 0.305 kg | |
| Standards | IEC 61643-11, EN 61643-11, UL 1449 5th Edition, GB/T 18802.11-2020 | |
| Construction | Pluggable |
The ABB OVR T1-T2 N 100-255 P TS is a Type 1+2 neutral-to-earth surge protection device designed for coordinated protection against lightning currents and transient overvoltages in compatible 230/400 V AC TT and TN-S electrical systems.
The device has an impulse current (Iimp) rating of 100 kA between N-PE with a 10/350 µs waveform, providing very high lightning-current discharge capability.
The OVR T1-T2 N 100-255 P TS provides a neutral-to-earth voltage protection level (Up) of ≤1.5 kV and has a maximum continuous operating voltage (Uc) of 255 V AC.
Yes. The TS version provides remote status signalling through one normally open and one normally closed auxiliary contact, allowing the condition of the SPD to be incorporated into an external monitoring or alarm system.
Yes. The OVR T1-T2 N 100-255 P TS has a pluggable construction. The corresponding replacement cartridge is the ABB OVR T1-T2 N 100-255 C, order code 2CTB813012R2300.
ABB OVR surge protection devices provide coordinated protection for low-voltage electrical installations, with the OVR T1-T2 range combining high lightning-current discharge capability with protection against damaging transient overvoltages.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.