ABB OVR T1-T2 N 100-255 P is a pluggable spark-gap combined Type 1 and Type 2 neutral-to-earth surge protective device for 230/400 V AC TN-S and TT systems, with 100 kA impulse-current capability, 255 V AC maximum continuous operating voltage and a protection level of 1.5 kV or less.
£465.71
The ABB OVR T1-T2 N 100-255 P, order code 2CTB813010R2300, is a high-capacity combined Type 1 and Type 2 neutral-to-earth surge protective device (SPD) designed for TN-S and TT low-voltage networks. Using spark-gap technology, it is intended for installation in main AC distribution switchboards and sub-distribution boards where substantial lightning-current and transient-overvoltage protection is required.
Designed for 230/400 V AC electrical systems, the OVR T1-T2 N 100-255 P provides an exceptional 100 kA impulse-current capability using the 10/350 µs lightning-current waveform. It also provides a nominal discharge current of 100 kA on the N-PE protection path and limits the voltage protection level to 1.5 kV.
The device provides a dedicated neutral-to-earth (N-PE) protection path with a maximum continuous operating voltage of 255 V AC. Its pluggable construction allows the protection module to be replaced when required, while the compact two-module DIN-rail format makes it straightforward to integrate into coordinated lightning and surge protection systems.
In TN-S and TT electrical systems, the neutral-to-earth protection path plays an important role in a coordinated surge protection arrangement. The ABB OVR T1-T2 N 100-255 P uses spark-gap technology to conduct high-energy lightning currents between neutral and protective earth while maintaining electrical separation during normal operation.
Its exceptional 100 kA 10/350 µs impulse-current capability makes it suitable for demanding lightning protection applications at the origin of an installation. When combined with suitable line protection SPDs, it can form part of a coordinated Type 1 and Type 2 protection system for main switchboards, helping reduce transient stress on downstream distribution equipment and sensitive electronic loads.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Poles | 1-pole | |
| Impulse Current Iimp (kA) | 100 kA | |
| Series | OVR T1-T2 | |
| ABB order code | 2CTB813010R2300 | |
| EAN / GTIN | 4053546053234 | |
| Product group | Surge Protection Devices | |
| Product type | Combined Type 1 + Type 2 neutral surge protective device | |
| SPD classification | Type 1 + Type 2 / Class I + II | |
| Standards | IEC 61643-11 / EN 61643-11 / UL 1449 5th Edition | |
| Technology | Spark gap | |
| Low-voltage distribution systems | TN-S / TT | |
| Protection mode | N-PE | |
| Number of poles | 1 | |
| Number of protected lines | 1 | |
| Nominal system voltage | 230 / 400 V AC | |
| Maximum continuous operating voltage Uc | 255 V AC | |
| System frequency | 47–63 Hz | |
| Impulse current Iimp (10/350 µs), N-PE | 100 kA | |
| Nominal discharge current In (8/20 µs), N-PE | 100 kA | |
| Voltage protection level Up, N-PE | ≤ 1.5 kV | |
| Maximum prospective short-circuit current, N-PE | 0.1 kA | |
| Follow-current interrupting capability Ifi, N-PE | 0.1 kA | |
| Leakage current Ipe | <1 mA | |
| Response time | <100 ns | |
| TOV withstand, N-PE | 1200 V for 200 ms | |
| Remote signalling | No | |
| Construction | Pluggable | |
| Degree of protection | IP20 | |
| Maximum operating altitude | 2000 m | |
| Operating temperature | -40 to +70 °C | |
| Mounting type | DIN rail | |
| Module width | 2 modules | |
| Dimensions (H × W × D) | 90 × 36 × 73 mm | |
| Weight | approx. 0.30 kg |
It is a combined Type 1 and Type 2 neutral-to-earth surge protective device designed to discharge high-energy lightning currents and transient surges in TN-S and TT low-voltage electrical systems.
The device has an N-PE impulse-current rating Iimp of 100 kA using the 10/350 µs lightning-current waveform.
The OVR T1-T2 N 100-255 P provides an N-PE voltage protection level Up of 1.5 kV or less.
It is designed for TN-S and TT low-voltage distribution systems and provides a dedicated neutral-to-earth protection path.
No. ABB order code 2CTB813010R2300 is the version without an auxiliary remote-signalling contact; ABB also offers a separate TS version where remote status signalling is required.
ABB OVR combined Type 1 and Type 2 surge protective devices provide high-capacity lightning-current discharge and effective transient-overvoltage limitation, with the OVR T1-T2 N 100-255 P delivering dedicated spark-gap neutral-to-earth protection for demanding TN-S and TT electrical installations.