Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T1-T2 N 50-255 C single-pole neutral-to-earth replacement surge protection cartridge for compatible Type 1 and Type 2 OVR devices, with 255 V AC maximum continuous operating voltage, 50 kA impulse current and 1.5 kV voltage protection level.
£365.85
The ABB OVR T1-T2 N 50-255 C is a single-pole neutral-to-earth replacement surge protection cartridge for compatible ABB OVR combined Type 1 + Type 2 surge protective devices (SPDs). Identified by ABB order code 2CTB812522R2300, it is designed for the N-PE protection path of ABB OVR assemblies used in TT and TN-S low-voltage distribution systems.
This cartridge provides high-energy lightning-current protection through a 50 kA impulse current (Iimp) rating using the 10/350 µs waveform. It also provides a 25 kA nominal discharge current (In) and 60 kA maximum discharge current (Imax) using the 8/20 µs waveform, making it suitable for restoring the protection capability of compatible ABB OVR T1-T2 assemblies without replacing the complete surge protection device.
The OVR T1-T2 N 50-255 C has a 255 V AC maximum continuous operating voltage across N-PE and a 1.5 kV voltage protection level (Up). Its pluggable cartridge format enables straightforward replacement during maintenance and is used as the neutral protection module in products including the ABB OVR T1-T2 1N 50-255 P TS.
Combined Type 1 and Type 2 surge protective devices are designed to manage both high-energy lightning currents and transient overvoltages. The neutral-to-earth protection path is particularly important in 1+1 and 3+1 configurations, providing a controlled discharge route between neutral and protective earth while helping limit the voltage stress imposed on the installation.
The ABB OVR T1-T2 N 50-255 C provides a 50 kA 10/350 µs lightning impulse capability in a replaceable cartridge format. When a compatible neutral protection module requires replacement, this cartridge allows the ABB OVR assembly to be serviced without replacing the complete DIN rail base, helping simplify maintenance and reduce unnecessary component replacement.
Tick the specs you need, then view products that match.
| Device Type | Replacement cartridge | |
|---|---|---|
| Impulse Current Iimp (kA) | 50 kA | |
| Series | OVR T1-T2 | |
| ABB order code | 2CTB812522R2300 | |
| Product group | Surge Protection Devices | |
| Product type | Replacement surge protection cartridge | |
| SPD classification | Type 1 + Type 2 / Class I + Class II | |
| Protection path | Neutral to earth (N-PE) | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Low-voltage distribution systems | TT / TN-S | |
| Nominal AC system voltage | 239–400 V AC | |
| Maximum continuous operating voltage (Uc, N-PE) | 255 V AC | |
| Temporary overvoltage test value (N-PE) | 1200 V / 200 ms | |
| Impulse current (Iimp, 10/350 µs) | 50 kA | |
| Total discharge current (Itotal, 10/350 µs) | 50 kA | |
| Nominal discharge current (In, 8/20 µs) | 25 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 60 kA | |
| Voltage protection level (Up) | 1.5 kV | |
| Follow-current extinguishing capability | 0.1 kA | |
| Rated service short-circuit breaking capacity (Ics) | 100 kA | |
| Short-circuit withstand (Icc) | 100 kA | |
| Operating temperature | -40 to +70 °C | |
| Maximum operating altitude | 2000 m | |
| Construction | Pluggable replacement cartridge | |
| Standards | IEC 61643-11 / EN 61643-11 / UL 1449 5th Edition | |
| Dimensions (H × W × D) | 45 × 36 × 61 mm | |
| Weight | 0.24 kg | |
| EAN | 4053546114652 |
It is a single-pole neutral-to-earth replacement surge protection cartridge for compatible ABB OVR combined Type 1 and Type 2 surge protective devices.
The OVR T1-T2 N 50-255 C has an impulse current (Iimp) rating of 50 kA using a 10/350 µs lightning-current waveform.
The cartridge provides a nominal discharge current (In) of 25 kA and a maximum discharge current (Imax) of 60 kA using an 8/20 µs waveform.
The maximum continuous operating voltage (Uc) across the neutral-to-earth protection path is 255 V AC.
The cartridge is used as the N-PE replacement module in compatible ABB OVR assemblies including the OVR T1-T2 1N 50-255 P TS, allowing the neutral protection element to be replaced without changing the complete SPD.
ABB OVR replacement cartridges help maintain the specified lightning-current and transient overvoltage protection of compatible surge protective devices while allowing individual protection modules to be serviced without replacing the complete SPD assembly.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.