Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T1-T2 3N 100-255 P TS is a pluggable combined Type 1 and Type 2 surge protective device for 230/400 V AC TN-S and TT systems, with 100 kA total impulse-current capability, 60 kA maximum discharge current and remote status signalling.
£1,353.20
The ABB OVR T1-T2 3N 100-255 P TS is a high-performance combined Type 1 and Type 2 surge protective device (SPD) designed for the main distribution boards of three-phase plus neutral TN-S and TT low-voltage systems. It provides protection against high-energy lightning currents and transient overvoltages, making it suitable for industrial facilities, offices, public buildings and large residential installations.
Designed for 230/400 V AC systems, the OVR T1-T2 3N 100-255 P TS provides an impulse current Iimp of 25 kA per protected path using the 10/350 µs lightning-current waveform and a total impulse-current capability of 100 kA. It also provides a nominal discharge current of 25 kA and a maximum discharge current of 60 kA using the 8/20 µs waveform.
The device features a 3+1 configuration with four protected poles, pluggable protection modules, visual status indication and TS remote signalling through one normally open and one normally closed auxiliary contact. With a voltage protection level of 1.5 kV and short-circuit withstand capability of 100 kA, it provides robust incoming surge protection for demanding electrical installations.
Type 1 surge protective devices are designed to conduct the high-energy 10/350 µs lightning-current impulses that can enter an installation through the incoming electrical supply, while Type 2 protection limits lower-energy transient overvoltages further within the distribution system. The ABB OVR T1-T2 3N 100-255 P TS combines both functions in one pluggable assembly, making it particularly suitable for installation at the main distribution board.
Its 100 kA total lightning impulse-current capability, 60 kA maximum 8/20 µs discharge current and 1.5 kV protection level provide robust protection for downstream electrical and electronic equipment. Visual indication and TS remote contacts support both local and remote monitoring of the SPD's operating condition.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Poles | 3-pole + N | |
| Earthing System | TN-S, TT | |
| Impulse Current Iimp (kA) | 25 kA | |
| Series | OVR T1-T2 | |
| ABB order code | 2CTB812111R2300 | |
| GTIN / EAN | 4053546114645 | |
| Product group | Surge Protection Devices | |
| Product type | Combined Type 1 + Type 2 surge protective device | |
| SPD classification | Type 1 + Type 2 | |
| Standards | IEC 61643-11 / EN 61643-11 / UL 1449 5th Edition | |
| Network systems | TT / TN-S | |
| Configuration | 3+1 | |
| Number of poles | 4 | |
| Number of protected poles | 4 | |
| Nominal system voltage | 230 / 400 V AC | |
| Maximum continuous operating voltage MCOV (L-N) | 255 V AC | |
| Maximum continuous operating voltage MCOV (L-PE) | 255 V AC | |
| Maximum continuous operating voltage MCOV (N-PE) | 255 V AC | |
| Maximum continuous operating voltage MCOV (L-L) | 510 V AC | |
| Impulse current Iimp (10/350 µs) | 25 kA | |
| Total impulse current Itotal (10/350 µs) | 100 kA | |
| Nominal discharge current In (8/20 µs) | 25 kA | |
| Maximum discharge current Imax (8/20 µs) | 60 kA | |
| Follow current interrupting rating | 50 / 0.1 kA | |
| Voltage protection level Up (L-N) | 1.5 kV | |
| Voltage protection level Up (N-PE) | 1.5 kV | |
| Voltage protection level Up (L-PE) | 1.5 kV | |
| Short-circuit withstand capability | 100 kA | |
| Rated service short-circuit breaking capacity | 100 kA | |
| Remote signalling | Yes | |
| Normally open auxiliary contacts | 1 | |
| Normally closed auxiliary contacts | 1 | |
| Status indicator | Yes | |
| Construction | Pluggable | |
| Operating temperature | -40 to +70 °C | |
| Maximum operating altitude | 2000 m | |
| Mounting type | DIN rail | |
| Dimensions (H × W × D) | 90 × 144 × 73 mm |
It is a combined Type 1 and Type 2 surge protective device designed for main distribution boards in 230/400 V AC TN-S and TT systems, providing protection against lightning currents and transient overvoltages.
The OVR T1-T2 3N 100-255 P TS has an impulse current Iimp of 25 kA using a 10/350 µs waveform and a total impulse-current capability of 100 kA.
The device has a nominal discharge current In of 25 kA and a maximum discharge current Imax of 60 kA using an 8/20 µs waveform.
The TS version provides remote status signalling through one normally open and one normally closed auxiliary contact, allowing the SPD condition to be integrated into monitoring or alarm systems.
The OVR T1-T2 3N 100-255 P TS is designed for 230/400 V AC three-phase plus neutral TN-S and TT systems and provides four protected poles in a 3+1 configuration.
ABB OVR combined Type 1 and Type 2 surge protective devices provide high-capacity lightning-current discharge, low residual protection levels, pluggable construction and remote status monitoring for demanding main-distribution applications in commercial, industrial and large residential electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.