ABB OVR T1-T2 4L 100-255 P TS four-pole combined Type 1 and Type 2 pluggable surge protective device for 230/400 V AC TN-S systems, with 25 kA impulse current per pole, 100 kA total lightning-current capability and remote signalling.
£1,312.59
The ABB OVR T1-T2 4L 100-255 P TS is a high-capacity combined Type 1 + Type 2 surge protective device (SPD) designed to protect three-phase low-voltage electrical installations against lightning currents and transient overvoltages. Identified by ABB order code 2CTB812101R2300, this four-pole device is designed for TN-S distribution systems with a nominal system voltage of 230/400 V AC.
The device combines Type 1 lightning-current protection and Type 2 surge protection in a pluggable DIN rail assembly. Each protected path provides an impulse discharge current (Iimp) of 25 kA using a 10/350 µs waveform, giving a total lightning-current discharge capability of 100 kA across the four protected poles.
For transient surge protection, the OVR T1-T2 4L 100-255 P TS provides a 25 kA nominal discharge current (In) and a 60 kA maximum discharge current (Imax) per protected path using an 8/20 µs waveform. A 1.5 kV voltage protection level (Up), replaceable protection modules, local status indication and integrated TS remote signalling contacts make it particularly suitable for demanding commercial and industrial power-distribution applications.
Combined Type 1 and Type 2 SPDs provide protection against both high-energy lightning-current impulses and lower-energy transient overvoltages. Type 1 performance is tested using the 10/350 µs lightning-current waveform, while Type 2 performance uses the 8/20 µs surge-current waveform. Combining both functions in one device helps provide coordinated protection at the electrical installation level.
The ABB OVR T1-T2 4L 100-255 P TS provides 25 kA Iimp per protected pole and 100 kA total lightning-current capability, together with a 1.5 kV protection level. Its pluggable construction simplifies maintenance, while visual indication and TS remote contacts allow protection status to be checked locally or integrated into a remote monitoring system.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| SPD Type | Type 1+2 | |
| Poles | 4-pole | |
| Earthing System | TN-S | |
| Device Type | Surge protection device | |
| Impulse Current Iimp (kA) | 25 kA | |
| Series | OVR T1-T2 | |
| ABB order code | 2CTB812101R2300 | |
| Product group | Surge Protection Devices | |
| Product type | Combined lightning-current and surge protective device | |
| SPD classification | Type 1 + Type 2 / Class I + Class II | |
| Number of poles | 4 | |
| Number of protected poles | 4 | |
| Nominal system voltage | 230/400 V AC | |
| Maximum continuous operating voltage (Uc) | 264 V AC | |
| Impulse discharge current (Iimp, 10/350 µs) | 25 kA per pole | |
| Total discharge current (Itotal, 10/350 µs) | 100 kA | |
| Nominal discharge current (In, 8/20 µs) | 25 kA per pole | |
| Maximum discharge current (Imax, 8/20 µs) | 60 kA per pole | |
| Voltage protection level (Up) | 1.5 kV | |
| Short-circuit withstand | 100 kA | |
| Low-voltage distribution system | TN-S | |
| Remote signalling | Yes | |
| Auxiliary contacts | 1NO + 1NC | |
| Status indicator | Yes | |
| Operating temperature | -40 to +70 °C | |
| Maximum operating altitude | 2000 m | |
| Mounting | DIN rail | |
| Construction | Pluggable | |
| Standards | IEC 61643-11, EN 61643-11, UL 1449 5th Edition | |
| Dimensions (H × W × D) | 90 × 144 × 73 mm | |
| Weight | 1.2 kg | |
| EAN | 4053546114638 |
It is a combined Type 1 and Type 2 surge protective device designed to protect 230/400 V AC TN-S electrical systems against lightning currents and transient overvoltages.
The device has an impulse discharge current (Iimp) of 25 kA per protected pole using a 10/350 µs waveform, providing a total discharge current of 100 kA across its four poles.
The OVR T1-T2 4L 100-255 P TS provides a nominal discharge current (In) of 25 kA and a maximum discharge current (Imax) of 60 kA per protected path using an 8/20 µs waveform.
The TS designation indicates remote signalling. The device incorporates auxiliary contacts that allow its protection status to be monitored remotely.
Yes. The device uses a pluggable modular construction, allowing protection modules to be serviced or replaced without replacing the complete DIN rail base assembly.
ABB OVR combined Type 1 and Type 2 surge protective devices provide high-capacity lightning-current and transient overvoltage protection for low-voltage distribution systems, with modular construction and remote status monitoring to support dependable electrical installations.