ABB OVR T1-T2 N 100-255 TT C is a Type 1+2 neutral-to-earth surge protection device cartridge with 100 kA impulse current, 60 kA maximum discharge current and 255 V AC maximum continuous operating voltage for TT and TN-S low-voltage electrical systems.
£390.65
The ABB OVR T1-T2 N 100-255 TT C, order code 2CTB812022R2300, is a high-capacity Type 1+2 surge protection device (SPD) cartridge designed for neutral-to-earth protection in low-voltage electrical installations. As part of the ABB OVR surge protection range, it combines lightning-current and surge protection capabilities to help protect electrical systems against transient overvoltages and high-energy surge events.
Designed for TT and TN-S low-voltage distribution systems, this single-pole neutral protection module provides a 100 kA impulse current (Iimp) with a 10/350 µs waveform, a 60 kA maximum discharge current (Imax) with an 8/20 µs waveform and a 25 kA nominal discharge current (In). Its high discharge capability makes it suitable for coordinated surge protection systems where substantial lightning-current handling is required.
The OVR T1-T2 N 100-255 TT C is designed for systems with a nominal AC voltage of 240–400 V AC and has a maximum continuous operating voltage (Uc) of 255 V AC between N-PE. With a 1.5 kV voltage protection level, 100 kA short-circuit withstand capability and compact DIN rail-compatible cartridge format, it provides robust protection for demanding electrical distribution applications.
Type 1+2 surge protection devices combine protection against high-energy lightning currents with protection against transient overvoltages generated by indirect lightning and electrical switching events. This combined capability enables coordinated protection at the electrical distribution level while helping limit potentially damaging transient voltages reaching downstream equipment.
The ABB OVR T1-T2 N 100-255 TT C is specifically designed as a neutral-to-earth protection element for compatible TT and TN-S systems. Its 100 kA 10/350 µs impulse-current capability, high short-circuit withstand and compact cartridge construction make it suitable for demanding surge protection installations where substantial neutral discharge capacity is required.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 1+2 | |
| Poles | 1-pole | |
| Impulse Current Iimp (kA) | 100 kA | |
| Series | OVR T1-T2 | |
| Order code / MPN | 2CTB812022R2300 | |
| Product group | Surge Protection Devices | |
| Product type | Type 1+2 surge protection device cartridge | |
| SPD classification | Type 1+2 | |
| Protection configuration | Neutral-to-earth | |
| Number of poles | 1 | |
| Number of protected poles | 1 | |
| Nominal system voltage | 240–400 V AC | |
| Maximum continuous operating voltage (Uc, N-PE) | 255 V AC | |
| Impulse current (Iimp, 10/350 µs) | 100 kA | |
| Nominal discharge current (In, 8/20 µs) | 25 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 60 kA | |
| Voltage protection level (Up) | 1.5 kV | |
| Temporary overvoltage test value (N-PE) | 1200 V / 200 ms | |
| Distribution systems | TT, TN-S | |
| Rated service short-circuit breaking capacity (Ics) | 100 kA | |
| Short-circuit withstand (Icc) | 100 kA | |
| Operating temperature | -40 to +70 °C | |
| Maximum operating altitude | 2000 m | |
| Mounting type | DIN rail | |
| Standards | IEC 61643-11, EN 61643-11, UL 1449 5th Edition | |
| Dimensions (H × W × D) | 45 × 36 × 61 mm | |
| Weight | 0.24 kg |
The ABB OVR T1-T2 N 100-255 TT C is a Type 1+2 neutral-to-earth surge protection device cartridge designed for coordinated lightning and transient surge protection in compatible TT and TN-S low-voltage electrical systems.
The device has an impulse current (Iimp) rating of 100 kA with a 10/350 µs waveform, providing high-capacity protection against lightning-current surges.
The OVR T1-T2 N 100-255 TT C has a nominal discharge current (In) of 25 kA and a maximum discharge current (Imax) of 60 kA, measured using an 8/20 µs waveform.
The ABB OVR T1-T2 N 100-255 TT C has a maximum continuous operating voltage (Uc) of 255 V AC between neutral and protective earth.
The OVR T1-T2 N 100-255 TT C is designed for compatible TT and TN-S low-voltage distribution systems with nominal system voltages from 240–400 V AC.
ABB OVR surge protection devices are engineered for coordinated protection of low-voltage electrical installations, helping safeguard commercial and industrial electrical systems against lightning currents and damaging transient overvoltages.