2CTB804201R0100 ABB OVR T2 40-275 Type 2 Surge Protective Device

2CTB804201R0100 ABB OVR T2 40-275 Type 2 Surge Protective Device

ABB OVR T2 40-275 single-pole Type 2 surge protective device for 230 V AC low-voltage systems, with 275 V AC maximum continuous operating voltage, 20 kA nominal discharge current and 40 kA maximum discharge current.

SKU: 2CTB804201R0100MPN: 2CTB804201R0100
Price
List Price £154.46 ex VAT
Your Price (ex VAT) Save 25%
£115.85 25% OFF
You save £38.62 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £115.85
Trade pricing is personalised to your account

Manufacturer Lead Time

£115.85

Why Choose the ABB OVR T2 40-275 Surge Protective Device?

The ABB OVR T2 40-275 is a compact Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and electrical switching events. Identified by ABB order code 2CTB804201R0100, this single-pole surge arrester is designed for a nominal system voltage of 230 V AC.

As part of the ABB OVR surge protection range, the OVR T2 40-275 provides dependable surge-current diversion in a compact, non-pluggable DIN rail format. It is suitable for installation in electrical distribution boards and control panels where Type 2 protection is required to reduce the risk of transient overvoltages damaging downstream electrical and electronic equipment.

The device has a 275 V AC maximum continuous operating voltage (Uc), a 20 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax) using an 8/20 µs waveform. Its 1.4 kV voltage protection level (Up) helps limit the transient voltage reaching connected equipment.

Key Advantages

  • Compact Type 2 / Class II surge protective device for low-voltage power systems.
  • 40 kA maximum discharge current (Imax) for effective surge-current diversion.
  • 20 kA nominal discharge current (In) using an 8/20 µs waveform.
  • 275 V AC maximum continuous operating voltage for 230 V AC systems.
  • 1.4 kV voltage protection level (Up) helps protect downstream equipment.
  • Single-pole construction occupies only 17.8 mm of DIN rail width.
  • Non-pluggable construction provides a simple, integrated surge protection solution.
  • Suitable for distribution boards, industrial control panels and building electrical systems.

Key Features

  • ABB OVR Type 2 surge protection series.
  • Type 2 / Class II surge protective device.
  • Single-pole protection.
  • 230 V AC nominal system voltage.
  • 275 V AC maximum continuous operating voltage (Uc).
  • 20 kA nominal discharge current (In, 8/20 µs).
  • 40 kA maximum discharge current (Imax, 8/20 µs).
  • 1.4 kV voltage protection level (Up).
  • Compact 17.8 mm single-module width.
  • DIN rail mounting for modular electrical distribution equipment.
  • IP20 protection rating.
  • Non-pluggable monobloc construction.

Reliable Type 2 Protection Against Transient Overvoltages

Type 2 surge protective devices are used to limit transient overvoltages caused by indirect lightning effects and electrical switching operations. By diverting surge current away from downstream circuits, an SPD helps reduce electrical stress on insulation, electronic controls and other sensitive equipment.

The ABB OVR T2 40-275 combines a 40 kA maximum discharge capability with a compact single-module design, making it suitable for installations where DIN rail space is limited. Its integrated non-pluggable construction provides a straightforward Type 2 surge protection solution for low-voltage electrical distribution systems.

Typical Applications

  • 230 V AC low-voltage electrical installations.
  • Main and sub-distribution boards.
  • Industrial electrical control panels.
  • Commercial building electrical systems.
  • Automation and process-control installations.
  • Protection of sensitive electronic equipment.
  • Electrical systems exposed to switching and indirect lightning transients.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal No
Device Type Surge protection device
SPD Type Type 2
Poles 1-pole
Series OVR T2
ABB order code 2CTB804201R0100
Product group Surge Protection Devices
Product type Surge protective device (SPD)
SPD classification Type 2 / Class II
Number of poles 1
Number of protected poles 1
Nominal system voltage 230 V AC
Maximum continuous operating voltage (Uc) 275 V AC
Nominal discharge current (In, 8/20 µs) 20 kA
Maximum discharge current (Imax, 8/20 µs) 40 kA
Voltage protection level (Up) 1.4 kV
Protection rating IP20
Construction Non-pluggable / monobloc
Mounting DIN rail
Dimensions (H × W × D) 88 × 17.8 × 58 mm
Net weight approx. 125 g
EAN 3660308514103

Frequently Asked Questions

What is the ABB OVR T2 40-275 used for?

It is a Type 2 surge protective device designed to protect low-voltage electrical installations and downstream equipment against transient overvoltages caused by indirect lightning effects and electrical switching events.

What is the maximum discharge current of the OVR T2 40-275?

The maximum discharge current (Imax) is 40 kA using an 8/20 µs waveform, while the nominal discharge current (In) is 20 kA.

What is the maximum continuous operating voltage?

The OVR T2 40-275 has a maximum continuous operating voltage (Uc) of 275 V AC and is intended for a nominal system voltage of 230 V AC.

What is the voltage protection level of this SPD?

The ABB OVR T2 40-275 has a voltage protection level (Up) of 1.4 kV.

Is the ABB OVR T2 40-275 a pluggable surge protector?

No. This version uses a non-pluggable monobloc construction and mounts directly on a DIN rail as a compact single-pole Type 2 surge protective device.

Trusted Surge Protection from ABB

ABB OVR surge protective devices provide dependable protection against transient overvoltages in low-voltage electrical systems, helping safeguard distribution equipment, industrial controls and sensitive electronic loads.