2CTB804200R1100 ABB OVR T2 20-275 Type 2 Surge Protective Device x20 Pack

2CTB804200R1100 ABB OVR T2 20-275 Type 2 Surge Protective Device x20 Pack

ABB OVR T2 20-275 order code 2CTB804200R1100 is a 20-piece pack of single-pole non-pluggable Type 2 surge protective devices rated at 20 kA maximum discharge current, 5 kA nominal discharge current and 275 V AC maximum continuous operating voltage.

SKU: 2CTB804200R1100MPN: 2CTB804200R1100
Price
List Price £103.04 ex VAT
Your Price (ex VAT) Save 25%
£77.28 25% OFF
You save £25.76 per unit
Manufacturer Lead Time Estimated Delivery 5 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £77.28
Trade pricing is personalised to your account

Manufacturer Lead Time

£77.28

Why Choose the ABB OVR T2 20-275 Surge Protective Device?

The ABB OVR T2 20-275, order code 2CTB804200R1100, is a compact Type 2 surge protective device (SPD) designed to protect low-voltage electrical installations and connected equipment against transient overvoltages caused by indirect lightning effects and electrical switching events. This order code identifies ABB's x20 multipack of the OVR T2 20-275, providing 20 individual SPDs for larger installations, panel-building projects and stock requirements.

Each OVR T2 20-275 is a single-pole, non-pluggable Type 2 SPD with a maximum discharge current of 20 kA and a nominal discharge current of 5 kA using the standard 8/20 µs surge waveform. Its voltage protection level of 1.0 kV helps limit transient voltage reaching downstream electrical and electronic equipment.

With a nominal voltage of 230 V AC and maximum continuous operating voltage of 275 V AC, the OVR T2 20-275 is suitable for common low-voltage distribution applications. Each device occupies only 17.8 mm of DIN-rail width and weighs approximately 0.12 kg, providing a space-efficient surge protection solution for distribution boards and control panels.

Key Advantages

  • Supplied as an x20 pack containing 20 OVR T2 20-275 devices.
  • Reliable Type 2 protection against transient overvoltages.
  • 20 kA maximum discharge current using an 8/20 µs waveform.
  • 5 kA nominal discharge current for effective surge suppression.
  • Low 1.0 kV voltage protection level helps protect sensitive equipment.
  • 275 V AC maximum continuous operating voltage.
  • Compact 17.8 mm single-module width saves distribution-board space.
  • Non-pluggable construction provides a simple integrated surge protection solution.

Key Features

  • ABB OVR Type 2 series.
  • Type 2 surge protective device.
  • 20-piece multipack under ABB order code 2CTB804200R1100.
  • Single protected line per device.
  • 20 kA maximum discharge current Imax.
  • 5 kA nominal discharge current In.
  • 1.0 kV voltage protection level Up.
  • 230 V AC nominal voltage Un.
  • 275 V AC maximum continuous operating voltage Uc.
  • Designed for surge currents with an 8/20 µs waveform.
  • Compact non-pluggable construction.
  • DIN-rail mounting for modular electrical distribution equipment.

Reliable Type 2 Surge Protection for Electrical Installations

Type 2 surge protective devices are installed in low-voltage distribution systems to limit transient overvoltages before they can damage connected equipment. Each ABB OVR T2 20-275 in this multipack provides an effective discharge path for surge currents characterised by an 8/20 µs waveform, helping protect downstream electrical and electronic loads.

The combination of a 20 kA maximum discharge current, 1.0 kV protection level and compact single-pole DIN-rail construction makes the OVR T2 20-275 suitable for coordinated surge protection in distribution boards and control panels. The 20-piece packaging is particularly convenient for panel builders, contractors and projects requiring multiple identical SPDs.

Typical Applications

  • Low-voltage electrical distribution boards.
  • Residential and commercial electrical installations.
  • Industrial electrical and control panels.
  • Protection of sensitive electronic equipment.
  • Building automation and control systems.
  • Electrical panel-building and OEM projects.
  • Multi-panel installations requiring multiple identical Type 2 SPDs.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal No
Device Type Surge protection device
SPD Type Type 2
Poles 1-pole
Series OVR Type 2
ABB order code 2CTB804200R1100
Product group Surge Protection Devices
Product type Type 2 surge protective device multipack
SPD classification Type 2
Pack quantity 20 devices
Protected lines per device 1
Construction Non-pluggable
Nominal voltage Un 230 V AC
Maximum continuous operating voltage Uc 275 V AC
Maximum discharge current Imax (8/20 µs) 20 kA
Nominal discharge current In (8/20 µs) 5 kA
Voltage protection level Up 1.0 kV
Mounting type DIN rail
Width per device 17.8 mm
Height per device 88 mm
Depth per device 64.8 mm
Weight per device approx. 0.12 kg

Frequently Asked Questions

What is the ABB OVR T2 20-275 used for?

It is a Type 2 surge protective device designed to protect low-voltage electrical installations and connected equipment against transient overvoltages caused by indirect lightning effects and switching events.

How many devices are supplied under ABB order code 2CTB804200R1100?

ABB order code 2CTB804200R1100 identifies the OVR T2 20-275 (x20) multipack containing 20 individual OVR T2 20-275 surge protective devices.

What is the maximum discharge current of each OVR T2 20-275?

Each device has a maximum discharge current Imax of 20 kA using an 8/20 µs surge waveform and a nominal discharge current In of 5 kA.

What voltage is the OVR T2 20-275 designed for?

Each device has a nominal voltage of 230 V AC and a maximum continuous operating voltage Uc of 275 V AC.

Is the ABB OVR T2 20-275 pluggable?

No. The OVR T2 20-275 is a single-pole non-pluggable Type 2 SPD designed for compact DIN-rail installation.

Trusted ABB Surge Protection Technology

ABB OVR Type 2 surge protective devices provide dependable protection against transient overvoltages, combining effective surge-current discharge with compact DIN-rail construction for residential, commercial and industrial low-voltage electrical installations.