Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2 3N 40-350 P QS is a pluggable Type 2 surge protection device with 40 kA maximum discharge current, 20 kA nominal discharge current and 350 V AC maximum continuous operating voltage for 230/400 V TT and TN-S electrical installations.
£280.69
The ABB OVR T2 3N 40-350 P QS, order code 2CTB803983R1100, is a pluggable Type 2 surge protection device (SPD) designed to protect low-voltage electrical installations against transient overvoltages caused by indirect lightning and electrical switching events. As part of the ABB OVR QuickSafe surge protection range, it provides coordinated surge protection for three-phase plus neutral electrical distribution systems.
Designed for 230/400 V AC TT and TN-S networks, this SPD uses a 3+1 protection configuration and provides a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA. Its overall voltage protection level (Up) of 1.7 kV, together with L-N and N-PE protection levels of 1.5 kV and 1.4 kV respectively, helps limit transient overvoltages reaching downstream equipment.
The OVR T2 3N 40-350 P QS has a 350 V AC maximum continuous operating voltage and uses replaceable phase and neutral protection cartridges. Its four-pole DIN rail format, visual status indication and 100 kA short-circuit withstand capability make it suitable for residential, commercial and industrial distribution boards requiring dependable three-phase surge protection.
Type 2 surge protection devices are designed to protect low-voltage installations against transient overvoltages associated with indirect lightning and electrical switching events. They safely divert surge currents characterised by an 8/20 µs waveform while limiting the residual voltage that can reach connected electrical and electronic equipment.
The ABB OVR T2 3N 40-350 P QS combines a 3+1 protection arrangement with pluggable QuickSafe construction for TT and TN-S networks. Individual phase cartridges can be replaced with the ABB OVR T2 40-350 C QS, while the neutral protection element uses the OVR T2 N 80-350 C QS, simplifying maintenance without requiring replacement of the complete SPD assembly.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 3-pole + N | |
| Earthing System | TN-S, TT | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR QuickSafe | |
| Order code / MPN | 2CTB803983R1100 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protection device | |
| SPD classification | Type 2 / Class II | |
| Protection configuration | 3+1 | |
| Number of poles | 4 | |
| Nominal system voltage | 230/400 V AC | |
| Frequency | 45–65 Hz | |
| Maximum continuous operating voltage (Uc) | 350 V AC | |
| Nominal discharge current (In, 8/20 µs) | 20 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 40 kA | |
| Impulse current (Iimp, 10/350 µs) | 2 kA | |
| Total current | 80 kA | |
| Voltage protection level (Up) | 1.7 kV | |
| Voltage protection level (L-N) | 1.5 kV | |
| Voltage protection level (N-PE) | 1.4 kV | |
| Distribution systems | TT, TN-S | |
| Short-circuit withstand | 100 kA | |
| Maximum backup circuit breaker | 125 A, curve B or C | |
| Maximum backup fuse | 125 A, gG/gL | |
| Response time | <25 ns | |
| Ground residual current | <10 µA | |
| Mounting type | 35 mm DIN rail | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Maximum operating altitude | 2000 m | |
| Solid conductor range | 2.5–25 mm² | |
| Stranded conductor range | 2.5–16 mm² | |
| Stripping length | 12.5 mm | |
| Fire resistance | UL 94 V-0 | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Dimensions (H × W × D) | 88 × 71.2 × 58 mm | |
| Weight | 0.48 kg | |
| Construction | Pluggable |
The ABB OVR T2 3N 40-350 P QS is a Type 2 surge protection device designed to protect 230/400 V three-phase plus neutral electrical installations against transient overvoltages caused by indirect lightning and electrical switching events.
The device has a maximum discharge current (Imax) of 40 kA and a nominal discharge current (In) of 20 kA, based on an 8/20 µs surge-current waveform.
The ABB OVR T2 3N 40-350 P QS has a maximum continuous operating voltage (Uc) of 350 V AC and is designed for 230/400 V AC electrical systems.
The OVR T2 3N 40-350 P QS has an overall voltage protection level (Up) of 1.7 kV, with protection levels of 1.5 kV between L-N and 1.4 kV between N-PE.
Yes. The OVR T2 3N 40-350 P QS has a pluggable construction. ABB specifies the OVR T2 40-350 C QS as the replacement phase cartridge and the OVR T2 N 80-350 C QS as the replacement neutral cartridge.
ABB OVR QuickSafe surge protection devices provide dependable protection for low-voltage electrical installations, helping safeguard residential, commercial and industrial electrical systems against damaging transient overvoltages.
We use cookies