2CTB803983R0500 ABB OVR T2 3N 40-350 P TS QS Type 2 Surge Protective Device

2CTB803983R0500 ABB OVR T2 3N 40-350 P TS QS Type 2 Surge Protective Device

ABB OVR T2 3N 40-350 P TS QS Type 2 pluggable surge protective device for 230/400 V AC TT and TN-S three-phase plus neutral systems, with 350 V AC maximum continuous operating voltage, 20 kA nominal discharge current, 40 kA maximum discharge current and remote signalling.

SKU: 2CTB803983R0500MPN: 2CTB803983R0500
Price
List Price £585.16 ex VAT
Your Price (ex VAT) Save 25%
£438.87 25% OFF
You save £146.29 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £438.87
Trade pricing is personalised to your account

Manufacturer Lead Time

£438.87

Why Choose the ABB OVR T2 3N 40-350 P TS QS Surge Protective Device?

The ABB OVR T2 3N 40-350 P TS QS is a high-performance Type 2 surge protective device (SPD) designed to protect three-phase plus neutral low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and switching events. Identified by ABB order code 2CTB803983R0500, it provides coordinated surge protection for 230/400 V AC TT and TN-S networks.

As part of the ABB OVR Type 2 QuickSafe surge protection range, this four-pole SPD uses a 3+1 protection configuration and pluggable protection cartridges for convenient maintenance. The TS remote signalling contact allows the operating status of the SPD to be monitored remotely, making the device particularly suitable for commercial and industrial distribution systems where centralised condition monitoring is required.

The OVR T2 3N 40-350 P TS QS has a 350 V AC maximum continuous operating voltage (Uc), a 20 kA nominal discharge current (In) and a 40 kA maximum discharge current (Imax) using an 8/20 µs waveform. Its low voltage protection level helps limit damaging transient voltages before they reach sensitive downstream electrical and electronic equipment.

Key Advantages

  • High-performance Type 2 surge protection for three-phase plus neutral systems.
  • 40 kA maximum discharge current (Imax) for effective transient overvoltage protection.
  • 20 kA nominal discharge current (In) using an 8/20 µs waveform.
  • 350 V AC maximum continuous operating voltage.
  • 3+1 protection configuration for TT and TN-S 230/400 V AC networks.
  • Integrated TS auxiliary contact provides remote SPD status signalling.
  • Pluggable protection cartridges simplify maintenance and replacement.
  • DIN rail mounting and ABB System pro M compact design support straightforward distribution-board integration.

Key Features

  • ABB OVR Type 2 QuickSafe surge protection series.
  • Type 2 / Class II surge protective device.
  • 3+1 / three-phase plus neutral protection configuration.
  • 230/400 V AC nominal system voltage.
  • 350 V AC maximum continuous operating voltage (Uc).
  • 20 kA nominal discharge current (In, 8/20 µs).
  • 40 kA maximum discharge current (Imax, 8/20 µs).
  • Low voltage protection level (Up) for downstream equipment protection.
  • Fast <25 ns response time.
  • TS remote signalling contact rated up to 250 V AC / 1 A.
  • Pluggable phase and neutral protection cartridges.
  • IP20 protection rating for installed modular applications.

Reliable Type 2 Protection for Three-Phase Distribution Systems

Type 2 surge protective devices are designed to discharge surge currents generated by indirect lightning strikes and switching operations before damaging transient voltages reach downstream equipment. Their performance is characterised using an 8/20 µs current waveform, making them suitable for installation in main and sub-distribution switchboards where effective protection against conducted and induced overvoltages is required.

The ABB OVR T2 3N 40-350 P TS QS combines high surge-current capability with pluggable QuickSafe construction and remote status signalling. Its replaceable phase and neutral cartridges simplify maintenance, while the TS contact enables integration with monitoring systems so that changes in SPD condition can be identified remotely.

Typical Applications

  • 230/400 V AC three-phase electrical distribution boards.
  • TT and TN-S low-voltage distribution systems.
  • Main and sub-distribution switchboards.
  • Industrial control panels and automation systems.
  • Commercial and industrial building installations.
  • Protection of PLCs, controllers and sensitive electronic equipment.
  • Installations requiring remote surge protection status monitoring.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal Yes
Device Type Surge protection device
SPD Type Type 2
Poles 3-pole + N
Earthing System TN-S, TT
Series OVR T2 QuickSafe
ABB order code 2CTB803983R0500
Product group Surge Protection Devices
Product type Surge protective device (SPD)
SPD classification Type 2 / Class II
Protection configuration 3+1 / three-phase plus neutral
Number of poles 4
Nominal system voltage 230/400 V AC
Maximum continuous operating voltage (Uc) 350 V AC
Nominal discharge current (In, 8/20 µs) 20 kA
Maximum discharge current (Imax, 8/20 µs) 40 kA
Network systems TT / TN-S
Response time <25 ns
Remote signalling TS auxiliary contact
Auxiliary contact maximum rating 250 V AC / 1 A
Protection rating IP20
Operating temperature -40 to +80 °C
Maximum operating altitude 2000 m
Fire resistance UL 94 V-0
Solid conductor capacity 2.5–25 mm²
Stranded conductor capacity 2.5–16 mm²
Stripping length 12.5 mm
Terminal tightening torque 2.8 N·m
Mounting DIN rail
Version Pluggable
Standards IEC 61643-11 / EN 61643-11
Dimensions (H × W × D) 95 × 71.2 × 58 mm
Weight 480 g
Phase replacement cartridge OVR T2 40-350 C QS, 2CTB803886R1000
Neutral replacement cartridge OVR T2 N 80-350 C QS, 2CTB803886R0000
EAN 3660308519979

Frequently Asked Questions

What is the ABB OVR T2 3N 40-350 P TS QS used for?

It is a Type 2 surge protective device designed to protect 230/400 V AC three-phase plus neutral TT and TN-S electrical installations against transient overvoltages caused by indirect lightning effects and switching events.

What is the maximum discharge current of this SPD?

The OVR T2 3N 40-350 P TS QS has a maximum discharge current (Imax) of 40 kA using an 8/20 µs waveform, with a nominal discharge current (In) of 20 kA.

What is the maximum continuous operating voltage?

The maximum continuous operating voltage (Uc) is 350 V AC, with the device intended for 230/400 V AC TT and TN-S electrical systems.

What does TS mean on the OVR T2 3N 40-350 P TS QS?

The TS designation indicates remote signalling capability through an auxiliary contact, allowing the status of the surge protective device to be monitored remotely.

Can the protection cartridges be replaced?

Yes. The device uses pluggable replacement cartridges. The compatible phase cartridge is ABB OVR T2 40-350 C QS, order code 2CTB803886R1000, and the neutral cartridge is OVR T2 N 80-350 C QS, order code 2CTB803886R0000.

Trusted Surge Protection from ABB