ABB OVR T2 1N 40-350 P TS QS is a pluggable two-pole Type 2 surge protective device with 40 kA maximum discharge current, 20 kA nominal discharge current, 350 V AC maximum continuous operating voltage and remote signalling for TT and TN-S electrical installations.
£197.04
The ABB OVR T2 1N 40-350 P TS QS is a high-performance Type 2 surge protective device (SPD) designed to protect single-phase plus neutral low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and switching events. As part of the ABB OVR QuickSafe surge protection range, it combines dependable surge suppression, pluggable protection cartridges and remote status signalling for residential, commercial and industrial electrical systems.
Designed for TT and TN-S networks, the OVR T2 1N 40-350 P TS QS provides a nominal discharge current of 20 kA and a maximum discharge current of 40 kA using the standard 8/20 µs surge waveform. Its two-pole configuration protects the phase and neutral paths, while a short-circuit withstand capability of 100 kA supports installation in demanding low-voltage distribution systems.
With a nominal system voltage of 230/400 V AC, maximum continuous operating voltage of 350 V AC and voltage protection levels of 1.5 kV L-N and 1.4 kV N-PE, this SPD provides effective protection for sensitive downstream equipment. The TS auxiliary signalling contacts provide one normally open and one normally closed contact for remote status monitoring, while the pluggable design simplifies servicing and cartridge replacement.
Type 2 surge protective devices are used to limit transient overvoltages before they can damage electrical and electronic equipment. The ABB OVR T2 1N 40-350 P TS QS safely diverts surge currents away from protected circuits, helping safeguard building systems, automation equipment, controls, power supplies and other sensitive loads against the effects of indirect lightning and switching surges.
The TS version adds remote operating-status signalling through one normally open and one normally closed auxiliary contact. These contacts can be incorporated into monitoring, alarm or building-management systems, allowing maintenance personnel to monitor SPD condition remotely while the device's local status indicator provides convenient visual inspection at the distribution board.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2 | |
| Poles | 1-pole + N | |
| Earthing System | TN-S, TT | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2 QuickSafe | |
| ABB order code | 2CTB803982R0500 | |
| EAN | 3660308519726 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protective device | |
| SPD classification | Type 2 / Class II | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Network systems | TT / TN-S | |
| Number of poles | 2 | |
| Number of protected poles | 2 | |
| Nominal voltage | 230 V AC | |
| Nominal system voltage | 230 / 400 V AC | |
| Maximum continuous operating voltage Uc | 350 V AC | |
| Maximum discharge current Imax (8/20 µs) | 40 kA | |
| Nominal discharge current In (8/20 µs) | 20 kA | |
| Impulse current Iimp (10/350 µs) | 2 kA | |
| Total current | 80 kA | |
| Voltage protection level Up (L-N) | 1.5 kV | |
| Voltage protection level Up (N-PE) | 1.4 kV | |
| TOV withstand (L-N / N-PE) | 462 / 1200 V | |
| Voltage combination wave Uoc | 20 kV | |
| Short-circuit withstand Isccr | 100 kA | |
| Rated service short-circuit breaking capacity | 100 kA | |
| Maximum backup circuit breaker | 125 A, curve B or C | |
| Maximum backup fuse | 125 A gG / gL | |
| Response time | <25 ns | |
| Remote signalling | Yes | |
| Auxiliary contacts | 1 NO + 1 NC | |
| Status indicator | Yes | |
| Cartridge type | Pluggable | |
| Phase replacement cartridge | OVR T2 40-350 C QS | |
| Phase cartridge order code | 2CTB803886R1000 | |
| Neutral replacement cartridge | OVR T2 N 80-350 C QS | |
| Neutral cartridge order code | 2CTB803886R0000 | |
| Solid conductor range | 2.5–25 mm² | |
| Stranded conductor range | 2.5–16 mm² | |
| Stripping length | 12.5 mm | |
| Protection rating | IP20 | |
| Fire resistance | UL 94 V-0 | |
| Mounting type | 35 mm DIN rail | |
| Modular width | 2 modules | |
| Dimensions (H × W × D) | approx. 95 × 35.6 × 58 mm | |
| Weight | approx. 0.24 kg |
It is a Type 2 surge protective device designed to protect TT and TN-S low-voltage electrical installations and connected equipment against transient overvoltages caused by indirect lightning and switching events.
The OVR T2 1N 40-350 P TS QS has a maximum discharge current Imax of 40 kA and a nominal discharge current In of 20 kA, measured using an 8/20 µs waveform.
The TS version includes auxiliary signalling contacts for remote monitoring of the SPD's operating status, providing one normally open and one normally closed contact.
The device is designed for 230/400 V AC TT and TN-S systems and has a maximum continuous operating voltage Uc of 350 V AC.
Yes. The OVR T2 1N 40-350 P TS QS has a pluggable construction and uses replaceable OVR T2 40-350 C QS phase and OVR T2 N 80-350 C QS neutral cartridges.
ABB OVR Type 2 surge protective devices combine high surge discharge capability, pluggable construction and remote status signalling to provide dependable protection for modern residential, commercial and industrial low-voltage electrical installations.