Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2-T3 3N 20-275 P TS QS is a pluggable Type 2+3 surge protection device with 20 kA maximum discharge current, 5 kA nominal discharge current, 275 V AC maximum continuous operating voltage and remote signalling for 230/400 V TT and TN-S electrical installations.
£375.05
The ABB OVR T2-T3 3N 20-275 P TS QS, order code 2CTB803973R1600, is a pluggable Type 2+3 surge protection device (SPD) designed to protect low-voltage electrical installations and sensitive electronic equipment against transient overvoltages caused by indirect lightning and electrical switching events. As part of the ABB OVR QuickSafe surge protection range, it combines Type 2 surge-current handling with the low residual voltage characteristics associated with Type 3 protection.
Designed for 230/400 V AC three-phase plus neutral TT and TN-S networks, this SPD uses a 3+1 protection configuration and provides a maximum discharge current (Imax) of 20 kA, a nominal discharge current (In) of 5 kA and an impulse current (Iimp) of 2 kA. Its overall voltage protection level of 1.5 kV helps limit transient voltage reaching downstream electrical and electronic equipment.
The OVR T2-T3 3N 20-275 P TS QS has a 275 V AC maximum continuous operating voltage and features pluggable protection elements, optical status indication and integrated remote signalling auxiliary contacts. Its compact four-module DIN rail format makes it suitable for residential, commercial and industrial distribution boards where effective surge protection and remote status monitoring are required.
Type 2+3 surge protection devices combine the ability to discharge surge currents associated with indirect lightning strikes with a low residual voltage suitable for protecting sensitive electronic equipment. Type 2 performance addresses surge currents characterised by an 8/20 µs waveform, while Type 3 characteristics provide additional protection against transient overvoltages close to sensitive downstream equipment.
The ABB OVR T2-T3 3N 20-275 P TS QS combines these protection characteristics with pluggable QuickSafe construction, optical status indication and remote signalling. It can be installed in sub-distribution boards or close to sensitive equipment, making it suitable for installations where effective surge protection, straightforward maintenance and remote monitoring are required.
Tick the specs you need, then view products that match.
| Remote Signal | Yes | |
|---|---|---|
| SPD Type | Type 2+3 | |
| Poles | 3-pole + N | |
| Earthing System | TN-S, TT | |
| Device Type | Surge protection device | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR QuickSafe | |
| Order code / MPN | 2CTB803973R1600 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2+3 surge protection device | |
| SPD classification | Type 2+3 / Class II+III | |
| Protection configuration | 3+1 | |
| Number of poles | 4 | |
| Number of protected poles | 4 | |
| Nominal system voltage | 230/400 V AC | |
| Frequency | 45–65 Hz | |
| Maximum continuous operating voltage (Uc) | 275 V AC | |
| Nominal discharge current (In, 8/20 µs) | 5 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 20 kA | |
| Impulse current (Iimp, 10/350 µs) | 2 kA | |
| Voltage protection level (Up) | 1.5 kV | |
| Voltage protection level (L-N) | 1.4 kV | |
| Voltage protection level (N-PE) | 1.4 kV | |
| Distribution systems | TT, TN-S | |
| Rated service short-circuit breaking capacity | 100 kA | |
| Short-circuit withstand | 100 kA | |
| Maximum backup protection | 125 A | |
| Auxiliary contacts | 1 NO + 1 NC | |
| Status indication | Optical | |
| Mounting type | DIN rail | |
| Module width | 4 modules | |
| Protection rating | IP20 | |
| Operating temperature | -40 to +80 °C | |
| Power loss | 29 mW | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Dimensions (H × W × D) | 95 × 71.2 × 58 mm | |
| Weight | 0.48 kg | |
| Construction | Pluggable |
The ABB OVR T2-T3 3N 20-275 P TS QS is a Type 2+3 surge protection device designed to protect 230/400 V three-phase plus neutral electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning and electrical switching events.
The device has a maximum discharge current (Imax) of 20 kA with an 8/20 µs waveform and a nominal discharge current (In) of 5 kA.
The ABB OVR T2-T3 3N 20-275 P TS QS has a maximum continuous operating voltage (Uc) of 275 V AC and is designed for 230/400 V AC systems.
Yes. The TS version includes integrated auxiliary contacts for remote signalling, with one normally open and one normally closed contact for monitoring the SPD status.
The device is designed for DIN rail installation in sub-distribution and electrical distribution boards and can also be installed close to sensitive equipment in compatible TT and TN-S three-phase plus neutral networks.
ABB OVR QuickSafe surge protection devices provide coordinated protection for low-voltage electrical installations, helping safeguard residential, commercial and industrial electrical systems and sensitive electronic equipment against damaging transient overvoltages.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.