Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB OVR T2-T3 3N 20-440 P QS combined Type 2 and Type 3 pluggable surge protective device for 400/690 V AC TT and TN-S systems, with 440 V AC maximum continuous operating voltage and 20 kA maximum discharge current.
£253.82
The ABB OVR T2-T3 3N 20-440 P QS is a combined Type 2 and Type 3 surge protective device (SPD) designed to protect three-phase plus neutral low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and switching events. Identified by ABB order code 2CTB803973R1300, it is designed for 400/690 V AC TT and TN-S networks where dependable protection of sensitive electrical and electronic equipment is required.
As part of the ABB OVR QuickSafe surge protection range, the device combines Type 2 surge-current discharge capability with the low residual voltage characteristics associated with Type 3 protection. Its 3+1 protection configuration, pluggable construction and visual status indication make it suitable for intermediate distribution boards and installations close to sensitive terminal equipment.
The OVR T2-T3 3N 20-440 P QS has a 440 V AC maximum continuous operating voltage (Uc), a 5 kA nominal discharge current (In) and a 20 kA maximum discharge current (Imax) using an 8/20 µs waveform. With a voltage protection level of 1.5 kV, it provides effective transient protection for higher-voltage three-phase distribution systems.
Combined Type 2 and Type 3 surge protective devices provide coordinated protection against transient overvoltages. Their Type 2 characteristics enable them to discharge surge currents generated by indirect lightning events using an 8/20 µs waveform, while their Type 3 characteristics provide a low residual voltage suitable for protecting sensitive electronic equipment.
The ABB OVR T2-T3 3N 20-440 P QS is particularly suited to intermediate and sub-distribution boards or installation close to sensitive loads. Its pluggable QuickSafe design simplifies replacement, while the 3+1 configuration provides coordinated phase-to-neutral and neutral-to-earth surge protection for TT and TN-S three-phase systems.
Tick the specs you need, then view products that match.
| Remote Signal | No | |
|---|---|---|
| Device Type | Surge protection device | |
| SPD Type | Type 2+3 | |
| Poles | 3-pole + N | |
| Earthing System | TN-S, TT | |
| Impulse Current Iimp (kA) | 2 kA | |
| Series | OVR T2-T3 QuickSafe | |
| ABB order code | 2CTB803973R1300 | |
| Product group | Surge Protection Devices | |
| Product type | Combined Type 2 + Type 3 surge protective device | |
| SPD classification | Type 2 + Type 3 | |
| Protection configuration | 3+1 / 3L+N | |
| Number of poles | 4 | |
| Number of protected poles | 4 | |
| Nominal system voltage | 400/690 V AC | |
| Maximum continuous operating voltage (Uc) | 440 V AC | |
| Nominal discharge current (In, 8/20 µs) | 5 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 20 kA | |
| Impulse discharge current (Iimp, 10/350 µs) | 2 kA | |
| Voltage protection level (Up) | 1.5 kV | |
| Network systems | TT / TN-S | |
| Short-circuit withstand | 100 kA | |
| Protection rating | IP20 | |
| Maximum operating altitude | 5000 m | |
| Power loss | 156 mW | |
| Status indicator | Yes | |
| Mounting | DIN rail | |
| Version | Pluggable | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Dimensions (H × W × D) | 88 × 71.2 × 58 mm | |
| Weight | 0.48 kg | |
| EAN | 3660308519986 |
It is a combined Type 2 and Type 3 surge protective device used to protect 400/690 V AC three-phase plus neutral electrical installations and sensitive downstream equipment against transient overvoltages.
The OVR T2-T3 3N 20-440 P QS has a maximum discharge current (Imax) of 20 kA using an 8/20 µs waveform.
The maximum continuous operating voltage (Uc) is 440 V AC, with the device designed for 400/690 V AC electrical systems.
The device is designed for TT and TN-S networks and uses a 3+1 protection configuration for three-phase plus neutral systems.
Yes. The ABB OVR T2-T3 3N 20-440 P QS has a pluggable design, allowing the protection modules to be replaced while retaining the installed DIN rail base.
ABB OVR QuickSafe surge protective devices provide dependable transient overvoltage protection for industrial and commercial distribution systems, combining high surge-current capability, low residual voltage and convenient modular maintenance.
We use cookies