2CTB803886R0100 ABB OVR T2-T3 N 80-440 C QS Surge Protection Device Cartridge

2CTB803886R0100 ABB OVR T2-T3 N 80-440 C QS Surge Protection Device Cartridge

ABB OVR T2-T3 N 80-440 C QS is a Type 2+3 surge protection device cartridge with an 80 kA maximum discharge current, 30 kA nominal discharge current and 440 V AC maximum continuous operating voltage for low-voltage electrical installations.

SKU: 2CTB803886R0100MPN: 2CTB803886R0100
Price
List Price £85.96 ex VAT
Your Price (ex VAT) Save 25%
£64.47 25% OFF
You save £21.49 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £64.47
Trade pricing is personalised to your account

Manufacturer Lead Time

£64.47

Why Choose the ABB OVR T2-T3 N 80-440 C QS Surge Protection Device?

The ABB OVR T2-T3 N 80-440 C QS, order code 2CTB803886R0100, is a high-performance Type 2+3 surge protection device (SPD) cartridge designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning events and electrical switching surges. As part of the ABB OVR QuickSafe surge protection range, it is designed for use in intermediate distribution boards and close to terminal equipment requiring effective surge protection.

This single-pole neutral protection cartridge combines a maximum discharge current (Imax) of 80 kA with a nominal discharge current (In) of 30 kA and an impulse current (Iimp) of 6.25 kA. Its Type 2+3 classification makes it suitable for coordinated protection against surge currents while providing a low residual voltage level for sensitive downstream electrical and electronic equipment.

With a 400 V AC nominal voltage, 440 V AC maximum continuous operating voltage and 1.4 kV voltage protection level (Up), the OVR T2-T3 N 80-440 C QS is suited to TT and TN-S low-voltage distribution systems. Its compact replaceable-cartridge construction enables straightforward servicing within compatible ABB OVR surge protection assemblies.

Key Advantages

  • Combined Type 2+3 surge protection for low-voltage electrical installations.
  • 80 kA maximum discharge current (Imax) for handling high transient surge currents.
  • 30 kA nominal discharge current (In) for dependable surge protection performance.
  • 6.25 kA impulse current (Iimp) capability with a 10/350 µs waveform.
  • 1.4 kV voltage protection level (Up) helps limit transient voltage reaching downstream equipment.
  • Designed for neutral-to-earth protection in compatible low-voltage distribution systems.
  • Replaceable cartridge design simplifies maintenance of compatible ABB OVR assemblies.

Key Features

  • ABB OVR QuickSafe surge protection range.
  • Type 2+3 surge protection device cartridge.
  • 80 kA maximum discharge current (8/20 µs).
  • 30 kA nominal discharge current (8/20 µs).
  • 6.25 kA impulse current (10/350 µs).
  • 440 V AC maximum continuous operating voltage.
  • 1.4 kV voltage protection level.
  • Single-pole neutral protection configuration.
  • IP20 protection rating for indoor installation.
  • Designed for TT and TN-S low-voltage distribution systems.
  • Compliant with IEC 61643-11 / EN 61643-11.

Reliable Type 2+3 Protection for Electrical Systems

Surge protection devices help safeguard electrical installations by diverting transient surge currents and limiting the voltage reaching connected equipment. Type 2+3 SPDs combine distribution-level surge protection with enhanced protection suitable for installation closer to sensitive terminal equipment, helping protect against indirect lightning effects and switching transients.

The ABB OVR QuickSafe range is designed for coordinated surge protection in modern low-voltage installations. The OVR T2-T3 N 80-440 C QS provides neutral-to-earth surge protection with high discharge capacity, while its replaceable cartridge format allows the protection element to be replaced as part of routine electrical system maintenance.

Typical Applications

  • Low-voltage electrical distribution systems.
  • Intermediate electrical distribution boards.
  • Industrial electrical control and distribution panels.
  • Commercial and building electrical installations.
  • TT and TN-S distribution networks.
  • Protection of sensitive electrical and electronic equipment.
  • Protection against indirect lightning-induced surges.
  • Protection against electrical switching transients.

Technical Specifications

Tick the specs you need, then view products that match.

Device Type Replacement cartridge
Impulse Current Iimp (kA) 6.25 kA
Series OVR QuickSafe
Order code / MPN 2CTB803886R0100
Product group Surge Protection Devices
Product type Surge protection device cartridge
SPD classification Type 2+3
Number of poles 1
Number of protected poles 1
Nominal voltage 400 V AC
Nominal system voltage 400 / 690 V AC
Maximum continuous operating voltage (Uc) 440 V AC
Nominal discharge current (In, 8/20 µs) 30 kA
Maximum discharge current (Imax, 8/20 µs) 80 kA
Impulse current (Iimp, 10/350 µs) 6.25 kA
Voltage protection level (Up) 1.4 kV
Distribution systems TT, TN-S
Protection rating IP20
Maximum operating altitude 5000 m
Standards IEC 61643-11 / EN 61643-11
Dimensions (H × W × D) 57 × 17.6 × 55.6 mm
Weight 0.12 kg
Construction Replaceable cartridge

Frequently Asked Questions

What is the ABB OVR T2-T3 N 80-440 C QS used for?

The ABB OVR T2-T3 N 80-440 C QS is a Type 2+3 surge protection device cartridge designed to protect low-voltage electrical installations and sensitive equipment against transient overvoltages caused by indirect lightning and switching events.

What is the maximum discharge current of the OVR T2-T3 N 80-440 C QS?

The device has a maximum discharge current (Imax) of 80 kA with an 8/20 µs waveform and a nominal discharge current (In) of 30 kA.

What is the maximum continuous operating voltage?

The ABB OVR T2-T3 N 80-440 C QS has a maximum continuous operating voltage (Uc) of 440 V AC.

What voltage protection level does this SPD provide?

The OVR T2-T3 N 80-440 C QS provides a voltage protection level (Up) of 1.4 kV, helping limit transient overvoltages reaching downstream electrical and electronic equipment.

Where is the ABB OVR T2-T3 N 80-440 C QS typically used?

This Type 2+3 surge protection cartridge is suitable for low-voltage distribution systems, including intermediate distribution boards and installations close to sensitive terminal equipment, and is designed for compatible TT and TN-S systems.

Trusted Surge Protection from ABB

ABB OVR surge protection devices provide coordinated protection for low-voltage electrical installations, helping safeguard industrial, commercial and building electrical systems and sensitive equipment against damaging transient overvoltages.