ABB OVR T2 N 80-350 C QS is a Type 2 surge protection device cartridge with an 80 kA maximum discharge current, 30 kA nominal discharge current and 350 V AC maximum continuous operating voltage for low-voltage electrical installations.
£60.41
The ABB OVR T2 N 80-350 C QS, order code 2CTB803886R0000, is a Type 2 surge protection device (SPD) cartridge designed to protect low-voltage electrical installations and connected equipment against transient overvoltages caused by indirect lightning events and switching surges. As part of the ABB OVR QuickSafe surge protection range, it provides dependable protection for industrial, commercial and electrical distribution applications.
Designed for neutral-to-earth surge protection, the OVR T2 N 80-350 C QS combines a high maximum discharge current with a compact, replaceable cartridge format. It has a maximum discharge current (Imax) of 80 kA, a nominal discharge current (In) of 30 kA and a voltage protection level (Up) of 1.4 kV, helping divert damaging transient currents away from sensitive electrical equipment.
The device is intended for 230 V AC systems and has a maximum continuous operating voltage of 350 V AC. It is suitable for use in TT and TN-S low-voltage distribution systems and is manufactured in accordance with IEC 61643-11 / EN 61643-11.
Surge protection devices help safeguard electrical installations by diverting transient surge currents and limiting the voltage that reaches connected equipment. Type 2 SPDs are commonly installed within low-voltage distribution systems to protect against transient overvoltages associated with indirect lightning activity and electrical switching events.
The ABB OVR T2 range is designed for coordinated surge protection within electrical installations. The OVR T2 N 80-350 C QS provides high-capacity neutral-to-earth protection and its replaceable cartridge design allows the protection element to be serviced without replacing the complete surge protection assembly.
Tick the specs you need, then view products that match.
| Device Type | Replacement cartridge | |
|---|---|---|
| Impulse Current Iimp (kA) | 6.25 kA | |
| Series | OVR T2 QuickSafe | |
| Order code / MPN | 2CTB803886R0000 | |
| Product group | Surge Protection Devices | |
| Product type | Type 2 surge protection device cartridge | |
| SPD classification | Type 2 / Class II | |
| Number of poles | 1 | |
| Protected poles | 1 | |
| Nominal system voltage | 230 V AC | |
| Maximum continuous operating voltage (Uc) | 350 V AC | |
| Nominal discharge current (In, 8/20 µs) | 30 kA | |
| Maximum discharge current (Imax, 8/20 µs) | 80 kA | |
| Impulse current (Iimp, 10/350 µs) | 6.25 kA | |
| Voltage protection level (Up) | 1.4 kV | |
| Distribution systems | TT, TN-S | |
| Protection rating | IP20 | |
| Maximum operating altitude | 5000 m | |
| Standards | IEC 61643-11 / EN 61643-11 | |
| Dimensions (H × W × D) | 57 × 17.6 × 55.6 mm | |
| Weight | 0.12 kg | |
| Construction | Replaceable cartridge |
The ABB OVR T2 N 80-350 C QS is a Type 2 surge protection device cartridge used to protect low-voltage electrical installations and connected equipment against transient overvoltages caused by indirect lightning and switching events.
The device has a maximum discharge current (Imax) of 80 kA with an 8/20 µs waveform and a nominal discharge current (In) of 30 kA.
The ABB OVR T2 N 80-350 C QS has a maximum continuous operating voltage (Uc) of 350 V AC.
The OVR T2 N 80-350 C QS has a voltage protection level (Up) of 1.4 kV, helping limit transient voltage reaching downstream electrical equipment.
The device is manufactured in accordance with IEC 61643-11 / EN 61643-11 standards for low-voltage surge protective devices.
ABB OVR surge protection devices are designed for dependable protection of low-voltage electrical installations, helping safeguard industrial, commercial and building electrical systems against damaging transient overvoltages.