2CTB803883R2500 ABB OVR T2 3L 40-350 P TS QS Surge Protective Device

2CTB803883R2500 ABB OVR T2 3L 40-350 P TS QS Surge Protective Device

ABB OVR T2 3L 40-350 P TS QS is a three-pole Type 2 surge protective device with 40 kA maximum discharge current, 20 kA nominal discharge current, 350 V AC maximum continuous operating voltage and remote signalling contacts for TN-C electrical installations.

SKU: 2CTB803883R2500MPN: 2CTB803883R2500
Price
List Price £354.81 ex VAT
Your Price (ex VAT) Save 25%
£266.11 25% OFF
You save £88.70 per unit
Manufacturer Lead Time Estimated Delivery 10 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £266.11
Trade pricing is personalised to your account

Manufacturer Lead Time

£266.11

Why Choose the ABB OVR T2 3L 40-350 P TS QS Surge Protective Device?

The ABB OVR T2 3L 40-350 P TS QS is a high-performance Type 2 surge protective device (SPD) designed to protect three-phase low-voltage electrical installations against transient overvoltages caused by indirect lightning effects and electrical switching events. As part of the ABB OVR QuickSafe surge protection range, it combines dependable surge protection with pluggable cartridges, visual status indication and remote signalling contacts for integration into monitored electrical systems.

Designed for TN-C 230/400 V AC networks, the OVR T2 3L 40-350 P TS QS protects three lines and provides a nominal discharge current of 20 kA and a maximum discharge current of 40 kA per pole using the standard 8/20 µs surge waveform. Its QuickSafe design incorporates thermal disconnection to provide reliable end-of-life isolation of the surge protection elements.

With a maximum continuous operating voltage of 350 V AC, a voltage protection level of 1.5 kV and a short-circuit withstand rating of 100 kA, this three-pole SPD is suitable for distribution boards, intermediate panels and installations close to sensitive equipment. The TS auxiliary signalling contacts enable remote monitoring of SPD status, making this version particularly useful in industrial and commercial installations where maintenance visibility is important.

Key Advantages

  • Reliable Type 2 surge protection for three-phase TN-C electrical systems.
  • 40 kA maximum discharge current per pole for effective transient overvoltage protection.
  • 20 kA nominal discharge current per pole using an 8/20 µs waveform.
  • 350 V AC maximum continuous operating voltage.
  • TS remote signalling contacts allow SPD status to be monitored remotely.
  • Pluggable cartridges simplify inspection, maintenance and replacement.
  • Integrated ABB QuickSafe technology with thermal disconnection.
  • Visual status indication enables rapid local inspection.
  • Compact DIN-rail design for straightforward distribution-board installation.

Key Features

  • ABB OVR T2 QuickSafe series.
  • Type 2 / Class II surge protective device.
  • Three protected lines for TN-C systems.
  • 40 kA maximum discharge current Imax per pole.
  • 20 kA nominal discharge current In per pole.
  • 1.5 kV voltage protection level Up.
  • 350 V AC maximum continuous operating voltage Uc.
  • 100 kA short-circuit withstand capability.
  • One normally open and one normally closed auxiliary signalling contact.
  • Pluggable phase cartridges for convenient maintenance.
  • Integrated thermal disconnector and QuickSafe technology.
  • Visual operating status indicator.
  • DIN-rail mounting with a width of three modular spaces.

Reliable Surge Protection with Remote Status Monitoring

Type 2 surge protective devices are installed in low-voltage distribution systems to limit transient overvoltages before they can damage connected electrical and electronic equipment. The ABB OVR T2 range diverts surge currents safely away from protected circuits, helping safeguard automation equipment, control systems, drives, communications hardware and other sensitive loads.

The OVR T2 3L 40-350 P TS QS adds remote status signalling to the benefits of ABB's pluggable QuickSafe platform. Its auxiliary NO and NC contacts can be incorporated into monitoring or alarm circuits, allowing maintenance teams to identify a change in SPD condition without relying solely on local visual inspection.

Typical Applications

  • Three-phase TN-C low-voltage distribution boards.
  • Commercial and industrial electrical installations.
  • Industrial machinery and automation panels.
  • Building electrical distribution systems.
  • Protection of PLCs, drives and electronic control equipment.
  • Switchgear and power distribution assemblies.
  • Installations requiring remote SPD status monitoring.

Technical Specifications

Tick the specs you need, then view products that match.

Remote Signal Yes
Device Type Surge protection device
SPD Type Type 2
Poles 3-pole
Earthing System TN-C
Series OVR T2 QuickSafe
ABB order code 2CTB803883R2500
Product group Surge Protection Devices
Product type Type 2 surge protective device
SPD classification Type 2 / Class II
Standards IEC 61643-11 / EN 61643-11
Protected lines 3
Number of poles 3
System network TN-C
Nominal system voltage 230/400 V AC
Rated voltage 230 V AC
Maximum continuous operating voltage Uc 350 V AC
Frequency 45–65 Hz
Maximum discharge current Imax (8/20 µs) 40 kA
Nominal discharge current In (8/20 µs) 20 kA
Voltage protection level Up 1.5 kV
Total discharge current 120 kA
Short-circuit withstand Isccr 100 kA
Maximum backup circuit breaker 125 A, curve B or C
Maximum backup fuse 125 A gG/gL
Response time <25 ns
Auxiliary contacts 1 NO + 1 NC
Status indicator Yes
Cartridge type Pluggable
Replacement phase cartridge OVR T2 40-350 C QS, 2CTB803886R1000
Technology QuickSafe
Protection rating IP20
Mounting type DIN rail
Width 53.4 mm
Modular width 3 modules
Dimensions (H × W × D) 95 × 53.4 × 58 mm
Solid conductor range 2.5–25 mm²
Stranded conductor range 2.5–16 mm²
Stripping length 12.5 mm
Weight approx. 0.36 kg

Frequently Asked Questions

What is the ABB OVR T2 3L 40-350 P TS QS used for?

It is a Type 2 surge protective device designed to protect three-phase TN-C low-voltage installations and connected equipment against transient overvoltages caused by indirect lightning and switching events.

What is the maximum discharge current of this SPD?

The OVR T2 3L 40-350 P TS QS has a maximum discharge current Imax of 40 kA per pole using an 8/20 µs waveform.

What does TS mean on the OVR T2 3L 40-350 P TS QS?

The TS version provides auxiliary signalling contacts for remote monitoring of the surge protective device's operating status, with one normally open and one normally closed contact.

What voltage system is the OVR T2 3L 40-350 P TS QS designed for?

It is designed for 230/400 V AC TN-C systems and has a maximum continuous operating voltage Uc of 350 V AC.

Can the surge protection cartridges be replaced?

Yes. The OVR T2 3L 40-350 P TS QS uses pluggable phase cartridges, allowing the protection cartridges to be replaced while retaining the DIN-rail base assembly.

Trusted ABB Surge Protection Technology

ABB OVR surge protective devices combine high surge discharge capability, pluggable QuickSafe construction and practical status monitoring to provide dependable protection for commercial and industrial low-voltage electrical installations.